PY-CEI-NRR-2158, Monthly Operating Rept for March 1997 for PNPP
| ML20137W637 | |
| Person / Time | |
|---|---|
| Site: | Perry |
| Issue date: | 03/31/1997 |
| From: | Coon H, Myers L CENTERIOR ENERGY |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| PY-CEI-NRR-2158, NUDOCS 9704180163 | |
| Download: ML20137W637 (4) | |
Text
.
C$
Rgi Power Generation Group
- Petry Nuclear Power Plant
' Mail Address:
216-2846915 Law W. Myers 10 corder Road RO. Box 97 FAX: 216-280-8029 Vice President Perry. ONo 44081 Perry. OH 44081 e
P April 14,1997 PY-CEl/NRR-2158L United States Nuclear Regulatory Commission Document Control Desk Washington, D.C.
20555 Perry Nuclear Power Plant Docket No. 50-440 License No. NPF-58 Monthly Operating Report Gentlemen:
Attached is the March 1997 Monthly Operating Report for Perry Unit 1. Page 1 is the Average Daily Unit Power Level, page 2 is the Operation Data Report, and page 3 is the Unit Shutdowns and Power Reductions Chart. This report is submitted in accordance with Technical Specification 5.6.4.
y If you have questions or require additional information, please contact Mr. llenry L. Hegrat, Manager - Regulatory Affairs at (216) 280-5606.
Very truly yours, I
&O ff
/
HMC:s Attachment
. cc: NRC Region 111 Administrator NRC Project Manager i
NRC Resident inspector w
'9704180163 970331
- = ^=" ""S*Ji appupppppp5 j
[
i
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-440 UNIT Pernt One DATE 4/14/97 CONTACT H. M. Coon TELEPHONE (216) 280-5434
+
MONTH Merch 1997 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Ne0 1
1181 17 1191 2
1190 18 1195 3
1193 19 1197 4
1192 20 1195 5
11.92 21 1188 9
6 1194 22 1195 7
1195 23 1197 8
1193 24 1196 s
9 903 25 1188 i
10 11gg 26 1192 11 1192 27 1?!I 12 1194 28 1183 13 11Q5 29 1186 14 1190 30 1187 15 1195 31 1194 16 11QQ page1 i
,. [
. OPERATING DATA REPORT UNIT: Perry One DATE:
4/14/97
' 1.
Docket: 50-440 2.
Reporting Period:J!ard 1997
'3.
Utility
Contact:
H M. Coon 4
Licensed Thermal Power (MWt): 3179 5.
Nameplate Rating (Gross MWe): j.210 6.
Design Electrical Rating (Net MWe):
1191 7.
. Maximum Dependable Capacity (Gross MWe):
12j.2
- 8..
Maximum Dependable Capacity (Net MWe):jj.QQ 9.
If Changes Occur in Capacity Ratings (item Numbers 4 through 8) Since Last Report, Give Reasons:
- d!B 10.
Power Level to Which Restricted, if any (Net MWe): 100 %
11.
Reasons for Restrictions, if Any:
Operatina License This Month Yr-to-Date Cumulative 12.
Hours in Repo'rting Period 744 0 2.160.0 82.116 0 13.
Hours Reactor was Critical 744 0 2.104 2 59.193.5 14.
Reactor Reserve Shutdown Hours 00 00 0.0 15.
Hours Generator On-Line 744 0 2.068.7 57.207.0 16.
Unit Reserve Shutdown Hours 0.0 0.0 0.0 17.
Gross Thermal Energy (MWtH) 2.640.943 7.247.353 195.290.322 18.
Gross Electrical Energy (MWeH) 922.395 2.515.520 66.967.297 5
19.
Net Electrical Energy (MWeH) 879.695 2.396.038 63.665.639 20.
Unit Service Factor 100.0 %
95 8%
69.7 %
21.
Unit Availability Factor 100.0 %
95.8%
69.7 %
22.
. Unit Capacity Factor (Using MDC Net) 101.9 %
95.6 %
67.0 %
23.
Unit Capacity Factor (Using DER Net) 99 3 %
93.1 %
65.1 %
24.
. Unit Forced Outage Rate 00%
42%
98%
25.-
Forced Outage Hours 0.0 91.3 6.193.0 26.
Shutdowns Scheduled Over Next 6 Months (Type. Date, and Duration of Each): Refueling Outage, i
starting September 12,1997 for 37 days.
. 27.
If Shutdown at end of Report Period, Estimated Date Of Startup: N/%
i
}
page 2
]
p
~i
UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH - MARCH 1997 DOCKET NO. 50-440 UNIT one NAME Perry One DATE 4/14/97 CONTACT H. M. Coon TELEPHONE C216) 280-5434 NO.
DATE TYPE DURATION REASON METHOD LER SYSTEM COMP.
CAUSE & CORRECTIVE ACTION TO PREVENT 1
HOURS 2
3 8
4 5
RECURRENCE 97-03 3/9/97 S
B 5
PLANNED: Rod Sequence Exchange
SUMMARY
- Perry Unit One remained on-line the entire month of March,1997
- 1. TYPE:
- 2. REASON:
- 3. METHOD:
- 4. EXHIBIT G-Instructens F: Forced A-Equiprnent Failure (explain) 1 - Manual for preparation of data S: Scheduled B - Maintenance or Test 2-Manual Scram entry sheets for Licensee C - Refueling 3 - Automatic Scram Event Report (LER) file D - Regulatory Restriction 4 - ContryJed (NUREG 1022)
E - Operating Training &
5-Reduced Load License Examinaton 9 - Other
- 5. EXHIBIT 1 - Same Source F-Administative G - Operational Error (explain)
H-Other (explain) page 3
- -