PLA-6429, Second Annual Amendment to the Application for Renewed Operating License Numbers NPF-14 and NPF-22 Pursuant to 10 CFR 54.21(b), PLA-6429

From kanterella
(Redirected from PLA-6429)
Jump to navigation Jump to search
Second Annual Amendment to the Application for Renewed Operating License Numbers NPF-14 and NPF-22 Pursuant to 10 CFR 54.21(b), PLA-6429
ML082950013
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 09/26/2008
From: Mckinney B
Susquehanna
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
PLA-6429
Download: ML082950013 (6)


Text

it/"

Britt T. McKinney PPL Susquehanna, LLC Sr. Vice President & Chief Nuclear Officer 769 Salem Boulevard Berwick, PA 18603 Tel. 570.542.3149 Fax 570.542.1504 btmckinney@pplweb.com I TM S EP '2 6 2008 U. S. Nuclear Regulatory Commission Document Control Desk Mail Stop OP1-17 Washington, DC 20555 SUSQUEHANNA STEAM ELECTRIC STATION SECOND ANNUAL AMENDMENT TO THE APPLICATION FOR RENEWED OPERATING LICENSE NUMBERS NPF-14 AND NPF-22 PURSUANT TO 10 CFR 54.21(b) Docket Nos. 50-387 PLA-6429 and 50-388

References:

1) PLA-6110, Mr. B. T. McKinney (PPL)to Document ControlDesk (USNRC),

"Applicationfor Renewed OperatingLicense Numbers NPF-14 and NPF-22, dated September 13, 2006.

2) PLA-62 71, Mr. B. T. McKinney (PPL)to Document ControlDesk (USNRC),

"Annual Amendment to the Applicationfor Renewed OperatingLicense Numbers NPF-14 and NPF-22 Pursuant to 10 CFR 54.21(b), "dated September 12, 2007.

3) PLA-6310, Mr. B. T McKinney (PPL)to Document ControlDesk (USNRC),

"Units 1 and 2 License Renewal Application (LRA) Extended Power Uprate (EPU)

Impacts on LRA " dated February7, 2008.

In accordance with the requirements of 10 CFR 50, 51, and 54, PPL Susquehanna, LLC (PPL) requested the renewal of the operating licenses for the Susquehanna Steam Electric Station (SSES) Units 1 and 2 in Reference 1.

The License Renewal Rule, 10 CFR 54.21(b), requires that each year following submittal of a license renewal application (LRA), and at least 3 months before scheduled completion of the NRC review, an amendment to the renewal application must be submitted that identifies any change to the current licensing basis (CLB) of the facility that materially affects the content of the LRA.

In accordance with this requirement, PPL performed a review of CLB changes since the submittal of Reference 2, to determine whether any sections of the LRA were affected by these changes.

The PPL review identified that NRC's issuance of SSES license amendments for implementation of Extended Power Uprate (EPU) on Units 1 and 2 did affect the SSES CLB. However, these amendments were previously anticipated and incorporated in the

Document Control Desk PLA-6429 LRA submittal in September 2006 (Reference 1), and PPL has confirmed that the final amendments, as issued, do not require any additional changes to the LRA, consistent with the discussion in Reference 3.

The PPL review also identified one engineering change that has been implemented at SSES subsequent to the Reference 2 submittal that materially affected the contents of the LRA. This change relocated an HVAC system air intake, which resulted in material and environment combinations that had not been previously evaluated in the SSES LRA. The enclosure to this letter provides an amendment to various sections of the SSES LRA to address this change.

If you have any questions, please contact Mr. Duane L Filchner at (610) 774-7819.

I declare, under penalty of perjury, that the foregoing is true and correct.

Executed on: 762 O&

B. T. McKinney

Enclosure:

Amendment to SSES License Renewal Application (LRA) Second Annual (2008) Update Copy: NRC Region I Ms. E. H. Gettys, NRC Project Manager, License Renewal, Safety Mr. R. Janati, DEP/BRP Mr. F. W. Jaxheimer, NRC Sr. Resident Inspector Mr. A. L. Stuyvenberg, NRC Project Manager, License Renewal, Environmental

Enclosure to PLA-6429 Amendment to SSES License Renewal Application (LRA)

Second Annual (2008) Update

Enclosure to PLA-6429 Page 1 of 3 LRA Amendment As part of implementation of the Alternate Source Term (AST), PPL modification EC 793950 extended the control room air intake ductwork. This extension added ductwork and supports on the exterior of the Control Structure and Reactor Building.

The environments for Ductwork, Duct Bolting, Flexible Connections (ductwork) and HVAC Duct Supports originally identified in the LRA do not account for Outdoor Air and Exposed to Weather environments. The added ductwork is evaluated with the Standby Gas Treatment System (SGTS) described in LRA Section 2.3.2.7, as it provides the path for outdoor makeup air to SGTS.

The SSES LRA is amended as follows:

3.2 AGING MANAGEMENT OF ENGINEERED SAFETY FEATURES 3.2.2.1.7 Standby Gas Treatment System

> The Environments discussion under Section 3.2.2.1.7 (LRA page 3.2-9) is revised by addition (bold italics).

Environments The Standby Gas Treatment System components are exposed to the following environments:

> The following bullet is added to the text (LRA page 3.2-9).

  • Indoor Air
  • OutdoorAir
  • Raw Water Ventilation

Enclosure to PLA-6429 Page 2 of 3 3.2 AGING MANAGEMENT OF ENGINEERED SAFETY FEATURES 3.2.3 Conclusions Table 3.2.2-7, Aging Management Review Results - Standby Gas Treatment System

> Table 3.2.2-7 (LRA pages 3.2-97 through 3.2-103) is revised by addition (bold italics).

Galvanized OutdoorAir Loss of Bolting Pressure Material Integrity N/A N/A H Duct Bolting Boundary Steel (External)

Program Ventilation None None (Internal) Identified Required Ductwork Pressure Galvanized Boundary Steel Outdoor Air Loss of System Walkdown N/A N/A H Material Program (external) Program Ventilation Change in System (internal) Material Walkdown V.B-4 3.2.1-11 E Flexible Pressure Properties Program Connections (Ductwork) ur Boundary Neoprene Norn Outdoor Air Change in System Material Walkdown N/A N/A G (external) Properties Program

Enclosure to PLA-6429 Page 3 of 3 3.5 AGING MANAGEMENT OF CONTAINMENTS, STRUCTURES, AND COMPONENT SUPPORTS 3.5.3 Conclusions Table 3.5.2-10, Aging Management Review Results - Bulk Commodities The following line Item in Table 3.5.2-10 (LRA page 3.5-119) is revised by addition (bolditalics).

Structures Protected from 3.5.1-39 A Carbon Steel Weather Loss of material Monitoring Program 1II.B2-10 HVAC Duct SNS, SRE, Galvanized Protected from None None Il1.12-5 3.5.1-58 A Supports SSR Steel Weather Exposed to Loss of Structures Galvanized material Monitoring lll.B2-7 3.5.1-50 A Steel Weather Program