__

Q

@ Pennsylvania Power & Light Company Two North Ninth Street

  • Allentown, PA 18101
  • 215 / 770-5151 Harold W. Keiser Vice President-Nuclear Operations 215/770-7502 MA,1,0 9 g.

Dr. Thomas E. Murley Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 SUSQUEHANNA STEAM ELECTRIC STATION RESPONSE TO IE BULLETIN 85-03

, Docket Nos. 50-387 PLA-2632 FILE R41-1A.R41-2 50-388

Dear Dr. Murley:

In response to IE Bulletin 85-03, the attached information provides Pennsylvania Power & Light Company's results for item (a) of the bulletin and our program and schedule for completion of items (b) through (d).

Very truly yours, H.

eiser Vice President-Nuclear Operations Affidavit Attachments cc:

U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 (w/ original)

Mr. R. H. Jacobs - USNRC Ms. M. J. Campagnone - USNRC T.b 8605200088 860509 DR ADOCK 05000387 PDR k

1 p

F AFFIDAVIT COMMONWEALTH OF PENNSYLVANIA)

SS COUNTY OF LEHIGH

)

I, HAROLD W. KEISER, being duly sworn according to law, state that I am Vice President, Nuclear Operations of Pennsylvania Power & Light Company and that the facts set forth on the attached response to IE Bulletin 85-03 are true and correct to the best of my knowledge, information and belief.

o e

OA

' Harold W. Keiser Vice President, Nuclear Cperations Sworn to and sub ribed 4

before me this day of May, 1986.

JY Notary Public twTM C. Ento, um a,onq:c Authicteri, t!mw c0 joy rr c r e tnron c n q y;9, g g Faber, Pergive;3,mgy;g,,i.g

,,g I

rmh/msc2003681

7 Attachment PLA-2632 RESPONSE TO IE BULLETIN 85-03 The attached tables list motor-operated valves in the HPCI and RCIC systems at Susquehanna SES Units 1 and 2 that are required to be tested for operational readiness in accordance with 10CFR50.55a(g). PP&L has reviewed the design basis for operation of each of these valves including maximum differential pressure expected during both opening and closing for both normal and abnormal events to the extent that these valve operations and events are included in the existing, approved design basis. This information is summarized on the attached tables.

DETERMINATION OF LIST OF AFFECTED VALVES:

The list of valves was extracted from the Susquehanna Steam Electric Station Pump and Valve Inservice Inspection Testing Program. All motor operated valves subject to quarterly stroke tests in accordance with 10 CFR 50.55a(g) were included. For the HPCI system this included all motor operated valves which may be required to actuate in support of a HPCI initiation plus all containment isolation valves. Since RCIC is not an ECCS system, the only RCIC valves subject to 10 CFR 50.55a(g) requirements are the containment isolation valves. Tlie final list ~ numbered twenty-two valves for each unit (13-HPCI; 9-RCIC). This list was cross-checked with the applicable system drawings (P&ID's) to verify that no valves were inadvertently omitted.

DETERMINATION OF VALVE OPERATING DESIGN BASIS:

The design btsis for each valve consists of (1) the maximum differential pressure expected during opening and/or closing of the valve for both normal and abnormal events, and (2) the temperature corresponding to these conditions.

Normal events include those operations performed during normal plant conditions (i.e., startup, shutdown, power operation, etc.).

Also included are the system's designed safety functions and test modes.

Abnormal events are those system conditions resulting from postulated single equipment failures and recovery from inadvertent valve openings or closures to the extent that these valve operations and events are included in the existing, approved design basis. Line breaks are not included in this category unless the mitigation of a line break is part of the valve's design basis. The purpose of the two main steam isolation valves in each system is to mitigate a possible steam line break so that case is considered an abnormal event.

l L

~

,e Attachment PLA-2632 OUTLINE OF PROGRAM TO COMPLETE BULLETIN ACTION PP&L expects to complete its review of switch settings by August 1986.

Program and procedural changes, if required, are expected to be completed by March, 1987.

Individual switch settings will be verified and/or changed, as necessary, on the affected SSES Unit 2 valves prior to the end of the Unit 2 first refueling outage (currently scheduled to end in November 1986).

Individual switch settings en affected Unit 1 valves will be verified and/or changed, as necessary, prior to the end of the Unit 1 third refueling outage (currently scheduled to end in November, 1987).

Since the maximum design basis for SSES Unit I and Unit 2 valves have been determined to be identical and where the Unit 1 and Unit 2 valves themselves are also identical, testing will only be performed on one unit or the other. Testing will be performed on Unit 2 valves, to the extent deemed practicable end necessary, prior to the end of the Unit 2 first refueling outage. Any testing not completed at that time will be performed on the identical Unit i valve, again to the extent practicable, prior to the end of the Unit I third refueling outage. Where testing under maximum differential pressure is not practical, alternative testing and/or justification will be provided. A final report will be submitted to NRC within 60 days of completion of the program.

j s

I i

F HICH PRESSURE COOLANT INJECTION (HPCI)

UNIT 1 OPERATING BASES MAKd P(PSI)/T("F)

LIMITORQUE VALVE SIZE VALVE PRESSURE OPERATOR'

. SERVICE NORMAL TAG NO.

(INCH)

TYPE MANUFACTURER CLASS SIZE DESCRIPTION POSITION OPEN CLOSE HV-155F001 10 Cate Anchor / Darling 900 SMB-1-60 Turbine Steam closed 1157/565 1157/565 Isolation 600 SMB-1-40 Steam Supply open 0/565 1157/565 IIV-155F002 10 Cate Inchor/ Darling Inboard' Isolation HV-155F003 10 Cate Anchor / Darling 600 SMB-1-40 Steam Supply open

l50/C65 1157/565 Outboard Isolation a

HV-155F004 16 Cate Anchor / Darling 150 SMB-00-7 CST Suction Open 40/100 40/100 I

HV-155F006 14 Cate Anchor / Darling 900 SMB-3-150 Injection Shutoff Closed 1162K546 1162/140 HV-155F007 14 Cate Anchor / Darling 900 SMB-3-150 Pump Discharge.

Open 1162/D46 HV-155F008 10 Globe Anchor / Darling 900 SMB-3-80 Full Flow Test closed 1342/100 1342/100 Valve to CST HV-155F012 4

Cate Anchor / Darling 600 SMB-00-15 Min Flow Bypass Closed 1367/140 1367/100 HV-155F042 16 Gate Anchor / Darling 150 SMB-00-7 Suppression Pool closed 44/140 29/140 Suction HV-155F066 20 Cate Anchor / Darling 150 SMB-0-10 HPCI Turbine Open 0/100 0/298 Exhaust HV-155F075 3

Cate Anchor / Darling 150 SMB-000-2 Outboard Turbine Open 50/298 44/140 Vacuum Breaker HV-155F079 3

Cate Anchor / Darling 150 SMB-000-2 Inboard Turbine Open 29/140 44/140 Vacuum Breaker HV-156F059 2

Clobe Yarway 1500 SMB-000-2 Lube 011 Cooling Closed 335/140 Water IActual temperature depends on proximity to feedwater pipe, included in its design basis.

eClosing of this valve is not required and therefore, is not ai d

.~

n

REACTOR CORE ISOLATION COOLING (RCIC)

UNIT 1 LIMITORQUE OPERATING BASES MAXd P(PSI)/T(*F)

VALVE SIZE VALVE PRESSURE OPERATOR SERVICE NORMAL TAG NO.

(INCH) TYPE MANUFACTURER CLASS SIZE DESCRIPTION POSITION OPEN CLOSE HV-149F007 4

Cate Anchor / Darling 900 SMB-00-7 Inboard Steam Open 0/565 1157/565 Isolation HV-149F008 4

Cate Anchor / Darling 900 SMB-00-10 Outboard Steam Open G 0/(565 1157/565 Isolation HV-149F013 6

Cate Anchor / Darling 900 SMB-00-25 RCIC Injection Closed ll62/Q46 1162/140 FV-149F019 2

Globe Yarway 1500 SMB-00-15 Min Flow Bypass Closed 1300/140 1300/100 HV-149F031 6

Cate Anchor / Darling 150 SMB-000-2 Pump Suction Closed 44/140 29/140 Suppression Pool HV-149F059 10 Cate Anchor / Darling 150 SMB-00-10' Turbine Exhaust Open 0/100 0/298 Isolation NY-149F060 2

Globe Yarway 1500 SMB-000-2 Vacuum Pump Open 20/160 20/160 Discharge HV-149F062 2

Cate Borg Warner 1500 SMB-000-5 Outboard vacuum Open 11/240 44/140 Breaker HV-149F084 2

Cate Borg Warner 1500 SMB-000-5 Inboard Vacuum Open 29/140 44/140 Breaker IActual temperature depends on proximity to feedvater pipe.

e

n. -..._

~ - - * - --

-- ~- ~'

"~^ **

O

r v

HIGH PRESSURE COOLANT INJECTION (HPCI)

UNIT 2 LIMITORQUE OPERATING BASES MAK AP(PSI)/T(*F)

VALVE SIZE VALVE PRESSURE OPERATOR SERVICE NORMAL

_T A'G No.

(INCH) TYPE MANUFACTURER CLASS SIZE DESCRIPTION POSITION OPEN CLOSE HV-207001 10 Gate Anchor / Darling 900 SMB-1-60 Turbine Steam closed 1157/565 1157/565 Isolation HV-255F002 10 Gate Anchor / Darling 600 SMB-1-40 Steam Supply Open 0/565 1157/565 Inboard Isolation HV-255F003 10 Cate Anchor / Darling 600 SMB-1-40 Steam Supply Open 0 0/(565 1157/565 Outboard Isolation HV-255F004 16 Ge*e Anchor / Darling 150 SMB-00-7\\

CST Suction

(

Open 40/100

' 40/100 I

HV-255F006 14 Gate Anchor / Darling 900 SMB-3-150 Injection Shutof ?'

Closed ll62/<546 1162/140 I

HV-255F007 14 Cate Anchor / Darling 900 SMB-3-150 Pump Discharge Open ll62/<546 HV-255F008 10 Globe Anchor / Darling 900 SMB-3-80 Full Flow Test closed 1342/100 1342/100 Valve to CST HV-255F012 4

Cate Anchor / Darling 600 SMB-00-15 Min Flow Bypass Closed 1367/140 1367/100 HV-255F042 16 Cate Anchor / Darling 150 SMB-00-7 Suppression Pool Closed 44/140 29/140 Suction HV-255F066 20 Gate Anchor / Darling 150 SMB-0-10 HPCI Turbine Open 0/100 0/298 Exhaust HV-255F075 3

Cate Anchor / Darling 150 SMB-000-2 Outboard Turbine Open 50/298 44/140 Vacuum Breaker HV-255F079 3

Cate Anchor / Darling 150 SMB-000-2 Inboard Turbine open 29/140 44/140 Vacuum Breaker HV-256F059 2

Globe Yarway 1500 SMB-000-2 Lube 011 Cooling Closed 335/140 Water IActual temperature depends on proximity to feedwater pipe.

Closing of this valve is not required and therefore, is not included in its design basis, s

as

-w-,

m+-e+.-

  • = ~..

,w+

~~%

e-

,e.,

wn W.,

w b

'a REACTOR CORE ISOLATION COOLING (RCIC)

UNIT 2 LIMITORQUE OPERATING BASES MAXf P(PSI)/T(*F)

VALVE SIZE VALVE PRESSURE OPERATOR SERVICE NORMAL TAG NO.

(INCH) TYPE MANUFACTURER CLASS SIZE DESCRIPTION POSITION OPEN CLOSE HV-249F007 4

Cate Anchor / Darling 900 SMB-00-7 Inboard, Steam Open 0/565 1157/565 Isolation HV-249F008 4

Cate Anchor / Darling 900 SMB-00-10 Outboard Steam open 5 0/<565 1157/565 Isolation HV-249F013 6

Cate Anchor / Darling 900 SMB-00-25 RCIC Injection Closed 1162/Q46 1162/140 FV-249F019 2

Clobe Yatvay 1500 SMB-00-15. Min Flow Bypass Closed 1300/140 1300/100 HV-249F031 6

Cate Anchor / Darling 150 SMB-000-2 Pump Suction Closed 44/140 29/140 Suppression Pool HV-249F059 10 Cate Anchor / Darling 150 SMB-00-5 Turbine Exhaust Open 0/100 0/298 Isolation HV-249F060 2

Globe Yarway 1500 SMB-000-2 Vacuum Pump Open 20/160 20/160 Discharge HV-249F062 2

Cate Borg Warner 1500 SMB-000-5 Outboard Vacuum open 11/240 44/140 Breaker HV-249F084 2

Cate Borg Warner 1500 SMB-000-5 Inboard Vacuum Open 29/140 44/140 Breaker I Actual temperature depends on proximity to feedwater pipe, dh/c408c:mg e

~

..