Nuclear Operating Company South Tas Project Electc Generatwin Station PO. Box 289 Wadsworth, Texas 77483 -
January 20, 2009 NOC-AE-09002381 File No: G25, T07.03.
10 CFR 50.55a U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852-2738 South Texas Project Unit 2 Docket No. STN 50-499 Inservice Inspection Summary Report - 2RE1 3 Attached are four copies of the South Texas Project Unit 2 summary report for inservice inspections performed prior to and during refueling outage 2RE13 completed in November, 2008. This summary.report satisfies the reporting requirements of ASME Code Section XI, Article IWA-6230.
There are no commitments in this report.
If there are any questions, please contact either Philip L. Walker at (361) 972-8392 or me at (361) 972-7431.
f~aon Jenewein Ma/ager,
,Tsting/Programs PLW
Attachment:
2RE13 Inservice Inspection Summary Report for Component Supports, Repair and Replacement, System Pressure Tests, Weld Inspections (IWB, IWC, IWD, IWF), and Containment Metal Liner (IWE)
STI No: 32421128
NOC-AE-09002381 Page 2 of 2 cc:
(paper copy) (electronic copy)
Regional Administrator, Region IV Kevin Howell U. S. Nuclear Regulatory Commission Catherine Callaway 612 East Lamar Blvd., Suite 400 Jim von Suskil Arlington, Texas 76011-8064 NRG South Texas LP Mohan C. Thadani J. J. Nesrsta Senior Project manager R. K. Temple U.S. Nuclear Regulatory Commission Kevin Polio One White flint North (MS 7 D 1) E. Alarcon 11555 Rockville Pike, City Public Service Rockville, MD 20852 C. M. Canady A. H. Gutterman, Esquire City of Austin Morgan, Lewis & Bockius LLP Electric Utility Department 721 Barton Springs Road Mohan Thadani Austin, TX 78704 U. S. Nuclear Regulatory Commission Richard A. Ratliff C. Kirksey Bureau of Radiation Control City. ofi Adistinlý.
Texas Department of Health 1100 West 49th Street Jon C.Wood
" 'Austin,TX 78756-3189 Cox Smith Matt*ews" Senior Resident Inspector U. S. Nuclear Regulatory Commission P. O. Box 289, Mail Code: MN116 Wadsworth, TX 77483 One copy of the attachment is provided.
SUMMARY
REPORT for the 2RE13 INSERVICE INSPECTION of UNIT 2 SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION COMPONENT SUPPORTS, REPAIR AND REPLACEMENT, SYSTEM PRESSURE TESTS, WELD INSPECTIONS (IWB, IWC, IWD, IWF), AND CONTAINMENT METAL LINER (IWE)
STP NUCLEAR OPERATING COMPANY December 2008
Attachment NOC-AE-09002381 Page 2 of 7 COVER SHEET 2RE13 INSERVICE INSPECTION
SUMMARY
REPORT COMPONENT SUPPORTS, REPAIR AND REPLACEMENT, SYSTEM PRESSURE TESTS, WELD INSPECTIONS (IWB, IWC, IWD, IWF), AND CONTAINMENT METAL LINER (IWE)
SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION;UNIT 2 P.O. BOX 289 WADSWORTH, TEXAS 77483 USNRC- DOCKET NO: 50-499 OPERATING LICENSE NO: NPF-80 COMMERCIAL OPERATION DATE: JUNE 19, 1989 Prepared by: .
JoMes Williams, Engineer Reviewed by: ----------
Lyl($piess, NDE Testing Supervisor
Attachment NOC-AE-09002381 Page 3 of 7 SCOPE COMPONENT SUPPORTS, REPAIR AND REPLACEMENT, SYSTEM PRESSURE TESTS, AND WELD INSPECTION PROGRAMS (IWB, IWC, IWD, IWF)
The examinations summarized in this report were performed in accordance with the 1989 Edition with no Addenda of the ASME Code,Section XI, which is applicable to the South Texas Project, Unit 2, second ten-year interval (10/19/2000-10/18/2010), third period (10/19/2007-10/18/2010). This report covers selected ASME Code Class 1, 2, and 3 systems and components, and component supports. The results are documented in accordance with the requirements of ASME Section XI Code Case N-532-4. Table 1 lists the relevant indications found and their disposition. Table 2 lists those systems and components for which repair or replacement was done.
Examinations and tests required by the Code are scheduled in accordance with "Inspection Program B" as defined in IWB-2412 for ASME Code Class 1 systems and components. IWC-2412 is applied to ASME Code Class 2 systems and components, IWD-2412 to ASME Code Class 3 systems and components, and IWF-2412 to component supports.
ASME Code Class 1 components are examined as prescribed by Table IWB-2500-1 and the applicable Examination Categories, which established the examination frequency at each refueling outage. ASME Code Class 2 systems and components are examined in accordance with Table IWC-2500-1, Examination Categories. ASME Code Class 3 systems and
-, components are examined in accordance with Table IWD-2500-1, Examination Categories....
Component Supports (Subsection. IWF). are examined in accordance with Table 2500 of0.Code .
Case N-491-2..
No relevant indications wereý fourndby ,.:.Augmented Inservice Inspectionof. Reactot:; Coolant'.
Pump flywheels in accordance witi R'egulatory Guide 1.14. .
- '*"Examination of Break. Exclusion .-Zone
- pipingin accordance with SRP 3.6.1:.Circumferential Welds found no relev'antfindication's.: ,
Risk-informed Inservice Inspection under ASME Section XI Code Case N-560 was applied to Class 1, Category B-J non-socket-welded locations in accordance with relief request RR-ENG-2-16 (December 30, 1999) (ML003676903). A risk-based approach was also applied to Class 1 socket-welded piping (Category B-J) and Class 2 piping weld (Categories C-F-1 and C-F-2) inspection as described in relief request RR-ENG-2-23 (February 27, 2001) (ML010650285).
No relevant indications were found.
The Reactor Pressure Vessel Upper Head was examined pursuant to Revision 1 of NRC Order EA-03-009 in accordance with Paragraph IV.C(5)(a) of the Order. The inspection identified no relevant conditions, evidence of cracks, leakage, or wastage.
CONTAINMENT METAL LINER (IWE)
The Containment Metal Liner examinations summarized in this report were performed in accordance with the 1992 Edition 1992 Addenda of the ASME Code,Section XI, which is applicable to the South Texas Project, Unit 2, first ten-year interval (09/09/1998-09/08/2009),
third period (09/09/05-09/08/09). This report covers selected ASME Code Class MC Components. No relevant indications were found.
Examinations and tests required by the Code are scheduled in accordance with "Inspection Program B" as defined in IWE-2412 for ASME Code Class CC liner and MC Components. The Containment Metal Liner components were examined in accordance with Table IWE-2500-1, Examination Categories.
Attachment NOC-AE-09002381 Page 4 of 7 FORM OAR-I OWNER'S ACTIVITY REPORT (Code Case N-532-4)
Report TIT.. -11 11 "nAD* "1 12 DI,.t, W,
Q tk ýr 13
-)-
- V1 t;
rZ f;
.5 Qt t;
m..
Unit No. 2 Commercial service date JUNE 19, 1989 Refueling outage no. 2RE13 (If applicable) 4 Current inspection interva I lWB I-WC, IWD, IWF -2'1I ;fWE -]s" (I", 2"d 3 d, 4h other)
Revision Current inspection period IWB IWC iwr. IwF -,r /- ip -ird (Is', 2 ýd, 3 1d) 2008 Edition and Addenda of Section XI applicable to the inspection plan. 1989 No Addenda for IWB. IWC. IWD. IWF and 1992 Edition 1992 Addenda for IWE September Date and revision of inspection plan September 2008 / Revision 4 Edition and Addenda of Section XI applicable to repairs/replacement activities, if different than the inspection plan N/A Code Cases used: N-435-1, N-568, N-627, N-307-3, N-532-4, N-491-2, N-652-1, N-460 CERTIFICATE OF CONFORMANCE I certify that. (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as.required by the ASME Code,Section XI; and (c) the repair/replacement activities and evaluations supporting thec6mpletion of 2RE13 conformr'to'the requirements§ofSectidn XI. . . .. . .-
(Refueling outage number)
,Signed -- Date t ner or Owner's Designee, Title) i CERTIFICATE OF INSERV ICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and pressure Vessel Inspectors and the State or Province of Texas and employed by ABS Boiler & Marine Insurance Co. of Houston, Texas have inspected the items described in this Owner's Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repairs/
replacements activities and evaluation described this report. Furthermore, neither the inspector nor his employer shall be liable in any manner fqr,ý sonal injury or pro y damage or a loss of any kind arising from the connected with this inspection.
( i Commoissions , '
Inspector's Signature -National Board, State, Province, and Endorsements Date
Attachment NOC-AE-09002381 Page 5 of 7 TABLE 1 ITEMS WITH FLAWS OR RELEVANT CONDITIONS THAT REQUIRE EVALUATION FOR CONTINUED SERVICE 2RE13 October 2008 Examination Item Item Description Evaluation Description Category Number Component Support CR 08-16072 Corroded Bolts F-A F1.30 ASME Class 3 EW-2188-HL5007 Repair/Replacement required.
Component Support Spring Can CR 08-15631 Out-of-tolerance F-A Fl.1OB ASME Class 1 load reading CV-2000-HL5001 Repair/Replacement required.
Component Support Spring Can CR 08-15631 Out-of-tolerance ASME Class 1 load reading F-A S F1.1013 RC-2000-SH02 Repair/Replacement required.
Comp*onenrt Support Spring Can CR 08-1'4960 Out of Plate Range F:A F1.J0B ASME-Class 1 .
,,<R;G t ,; -. : CRG-2320-HL5003. . . Repair/Replacement required.:,
RHR Pump 2A Integrally Welded CR 08-15937 Flaw indication.
Attachment C-C .CC3.30 Table IWB-3514-2 states flaw length of 1/8" is allowable per code.
NOTES:
- 1. Surveillance procedure OPSP1 1-RC-001 5, ASME Section Xl Inservice Inspection, documents Inservice Inspection activities during 2RE13.
Attachment
- NOC-AE-09002381 Page 6 of 7
- TABLE,2 ABSTRACT OF REPAIR/REPLACEMENT ACTIVITIESREQUIRED FOR CONTINUED SERVICE
ý2RE13-.
- "October 2008-.
Repair, -
Code Replacement, Item Description Description of Work Date Completed Repair/Replacement Class or Corrective Plan Number Measure 3 Replacement Valve Replaced valve bonnet bolting studs/nuts 10/11/2007 2-5-004 3 Repair Valve Tack-welded disk guides 10/11/2007 2-5-006 1 Replacement Valve Replaced valve seat 10/23/2008 2-6-041 3 Replacement Valve Replaced valve plug 06/19/2007 2-7-008 2 Replacement Valve Replaced valve internal parts (nozzle, disc, spindle) 02/04/2008 2-7-038 3 Replacement Valve Replaced valve disc. 05/15/2007 2-7-045 2 Repair Valve Replaced valve and attached piping 06/06/2007 2-7-046 3 Replacement Valve Replaced valve plug 10/24/2008 2-7-047 2 Replacement Valve Replaced flange studs and nuts 10/20/2008 2-7-049 2 Replacement Valve Replaced valve 01/10/2008 2-7-050 3 Replacement Valve Replaced valve 09/16/2008 2-7-053 3 Replacement Valve Replaced valve seat retainer 09/17/2008 2-7-054 3 Replacement Valve Replaced valve~ball assembly 09/16/2008 2-7-056 3 Replacement Piping Replaced flange studs and nuts 10/27/2007, 2-7-058 1 Repair RPV Stud Dressed stud sharp edges - spare RPV stud 01/17/2008 2-7-059 2 Repair Valve Seal welded stuffing box port plug 10/21/2008 2-8-006 2 Repair Valve Replaced valve, 10/21/2008 2-8-015 2 Repair Valve Replaced valve 10/16/2008 2-8-016 1 Repair Valve Replaced valvebonnet studs-: 10/29/2008 2-8-021 1 Replacement Pump Replaced RCP cartridge seal housing 10/22/2008 2-8-023 1 Replacement Pipe Support Replaced pipe suppor t - 10/28/2008 2-8-025 1 Replacement Valve Replaced pressurizerisafety1 valve 10/24/2008 2-8-027 1 Replacement Valve Replaced pressurizer safety valve 10/24/2008 2-8-028 3 Repair Valve Machined check, vaveq.plaes_. 10/17/2008 2-8-031 2 Repair Pipe Support Replaced pipe support and tube sheet 10/23/2008 2-8-033 3 Replacement Valve Replaced valVe 3all-:asserfimbly 10/17/2008 2-8-035 3 Repair Piping Replaced piping because of wall thinning 09/17/2008 2-8-037 2 Replacement Valve Replaced valve plug. 08/22/2008 2-8-038 3 Repair Piping -Replaced piping because of wall thinning 10/18/2008 2-8-039
,;Attachment
.NOC-AE-09002381 Page 7 of 7 TABLE 2I(cOntinued)
ABSTRACT OF REPAIR/REPLACEMENT-ACTIVITIES REQUIRED FOR CONTINUED SERVICE t "be 2008 c...
Code Repair, Replacement, "Repair/Replacement Code Replacement, Item Description Description of Work Date Completed P lacemen Class or Corrective Plan Number Measure 2 Repair RCB Personnel Fabricated and installed new valve clamps and cap 08/28/2008 2-8-040 Air Lock screws 3 Repair Piping Replaced piping because of wall thinning 10/19/2008 2-8-043 1 Replacement -Pump Replaced RCP cartridge seal housing 10/22/2008 2-8-046 1 Replacement Pipe Support Replaced pipe support 10/28/2008 2-8-047 3 Repair Piping Replaced piping because of wall thinning 10/20/2008 2-8-048 2 Replacement Snubber Replaced snubber 10/18/2008E 2-8-051 2 Replacement Control Valve Replaced damaged ASME parts (plug) 10/18/2008 2-8-052 2 Repair Isolation Valve Drilled/Tapped valve-bonnet for seal injection fitting 10/30/2008 2-8-053 2 Repair Isolation Valve Seal welded leakmoff,.line.plug to valve stuffing box 10/17/2008 2-8-004 1 Replacement Safety Valve Replaced Inlet flange studs 10/22/2008 2-8-026 2 Repair Isolation Valve Fabricated and installed plugs. in furmanite injection 11/01/2008 2-8-054 ports 2 Repair Control Valve Repaired existing.Valve pe&DCP 04-15252-4 10/15/2008 2-8-014 2 &3 Replacement Flange Replaced nut and studs.from RHR Heat Exchanger 09/17/2008 2-8-002 Fasteners 3 Replacement Ball Valve Replaced ball' assesbly' 06/18/2007 2-7-048 3 Replacement Piping Replaced piping because of wall thinning 06/18/2007 2-6-007 3 Repair Water Pump Repaired diffuser beaeingqhousing 10/25/2008 2-7-057