RA-23-0277, Response to Request for Confirmation of Information (RCI) Regarding Application to Revise Technical Specification 3.7.11, Control Room Area Chilled Water System (Cracws)
| ML23299A041 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 10/26/2023 |
| From: | Flippin N Duke Energy Carolinas |
| To: | Office of Nuclear Reactor Regulation, Document Control Desk |
| References | |
| RA-23-0277 | |
| Download: ML23299A041 (1) | |
Text
Nicole L. Flippin Vice President Catawba Nuclear Station Duke Energy CN01VP / 4800 Concord Road York, SC 29745 o: 803.701.3340 Nicole.Flippin@duke-energy.com Serial: RA-23-0277 10 CFR 50.90 October 26, 2023 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Catawba Nuclear Station, Unit Nos. 1 and 2 Docket Nos. 50-413 and 50-414 Renewed License Nos. NPF-35 and NPF-52
Subject:
Response to Request for Confirmation of Information (RCI) Regarding Application to Revise Technical Specification 3.7.11, Control Room Area Chilled Water System (CRACWS)
References:
- 1. Duke Energy letter, License Amendment Application to Revise Control Room Cooling Technical Specifications, dated June 19, 2023 (ADAMS Accession No. ML23170A015).
- 2. NRC E-Mail, Catawba Nuclear Station, Units 1 and 2 - Request for Confirmation RE:
License Amendment Application to Revise Control Room Cooling TS 3.7.11 (EPID L-2023-LLA-0093), dated September 28, 2023 (ADAMS Accession No. ML23271A179).
By letter dated June 19, 2023 (Reference 1), Duke Energy Carolinas, LLC (Duke Energy) submitted a license amendment request (LAR) for Catawba Nuclear Station (CNS) Units 1 and
- 2. The proposed change would revise CNS Technical Specification (TS) 3.7.11, Control Room Area Chilled Water System (CRACWS), to modify the Actions for two inoperable CRACWS trains. Specifically, with two CRACWS trains inoperable, 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> would be permitted to restore one train to operable status provided mitigating actions are taken to ensure control room temperature is appropriately maintained.
By correspondence dated September 28, 2023 (Reference 2), the Nuclear Regulatory Commission (NRC) staff notified Duke Energy that additional information is needed to complete the review.
The enclosure to this letter provides Duke Energys response to the NRC request for confirmation of information (RCI). The information contained within this response does not change the No Significant Hazards Consideration Determination provided in Reference 1.
There are no new regulatory commitments contained in this submittal.
(~ DUKE ENERGY
U.S. Nuclear Regulatory Commission RA-23-0277 Page2 If there are any questions or if additional information is needed, please contact Mr. Ryan Treadway, Director - Nuclear Fleet Licensing at (980) 373-5873.
I declare under penalty of perjury that the foregoing is true and correct. Executed on October 26, 2023.
Sincerely, Nicole L. Flippin Vice President, Catawba Nuclear Station
Enclosure:
Response to Request for Confirmation of Information
U.S. Nuclear Regulatory Commission RA-23-0277 Page 3 cc (with Enclosure):
L. Dudes, USNRC Region II - Regional Administrator D. Rivard, USNRC Senior Resident Inspector - CNS S. Williams, NRR Senior Project Manager - CNS L. Garner, Manager, Radioactive and Infectious Waste Management Section, SC DHEC S. Jenkins, Chief, Bureau of Radiological Health, SC DHEC
U.S. Nuclear Regulatory Commission RA-23-0277 Page 1 Catawba Nuclear Station, Units 1 and 2 Docket Nos. 50-413 and 50-414 Renewed License Nos. NPF-35 and NPF-52 Response to Request for Confirmation (RCI) Regarding Application to Revise Technical Specification 3.7.11, Control Room Area Chilled Water System (CRACWS)
Enclosure Response to Request for Confirmation of Information
U.S. Nuclear Regulatory Commission RA-23-0277 Page 2 Request for Confirmation of Information (RCI)
Note: Text from the NRC is in italics.
By letter dated June 19, 2023 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML23170A015), Duke Energy Carolinas, LLC, (the licensee, Duke Energy) submitted a license amendment request (LAR) for Catawba Nuclear Station, Units 1 and 2. The proposed change would revise Catawba Technical Specification (TS) 3.7.11, Control Room Area Chilled Water System (CRACWS), to modify the TS Actions for two inoperable CRACWS trains.
The NRC staff has reviewed the application and determined that additional information is needed to complete the review. Please respond within 30 days of the date of this e-mail.
Please note that the NRC staffs review is continuing and further requests for information may be developed.
As described in LIC-115, Revision 1, Processing Requests for Additional Information (ML21141A238), NRC staff requests the following requests for confirmation of information (RCI).
RCI No. 1 Section 2.4 of the LAR states:
A new Condition E is added. The new Condition E states, Required Action and associated Completion Time of Condition E not met in MODE 1, 2, 3, or 4.
The TS markup page states:
Required Action and associated Completion Time of Condition D not met in MODE 1, 2, 3, or 4.
The TS markup page appears to be correct. Please confirm the apparent editorial error in LAR Section 2.4.
Duke Energy Response to RCI No. 1 Duke Energy hereby confirms the editorial error in Section 2.4 of the LAR. The TS markup page from Attachment 1 of the LAR dated June 19, 2023 is correct. Section 2.4 of the LAR should have stated, Required Action and associated Completion Time of Condition D not met in MODE 1, 2, 3, or 4.