From:
Shawn Williams To:
Treadway, Ryan I Cc:
Edwards, Nicole D; Vaughan, Jordan L
Subject:
Catawba Nuclear Station, Units 1 and 2 - Request for Confirmation RE: License Amendment Application to Revise Control Room Cooling TS 3.7.11 (EPID L-2023-LLA-0093)
Date:
Thursday, September 28, 2023 1:58:07 PM
Dear Mr. Treadway,
By letter dated June 19, 2023 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML23170A015), Duke Energy Carolinas, LLC, (the licensee, Duke Energy) submitted a license amendment request (LAR) for Catawba Nuclear Station, Units 1 and 2. The proposed change would revise Catawba Technical Specification (TS) 3.7.11, Control Room Area Chilled Water System (CRACWS), to modify the TS Actions for two inoperable CRACWS trains.
The NRC staff has reviewed the application and determined that additional information is needed to complete the review. Please respond within 30 days of the date of this e-mail.
Please note that the NRC staffs review is continuing and further requests for information may be developed.
As described in LIC-115, Revision 1, Processing Requests for Additional Information (ML21141A238), NRC staff requests the following requests for confirmation of information (RCI).
RCI No. 1
Section 2.4 of the LAR states:
A new Condition E is added. The new Condition E states, Required Action and associated Completion Time of Condition E not met in MODE 1, 2, 3, or 4.
The TS markup page states:
Required Action and associated Completion Time of Condition D not met in MODE 1, 2, 3, or 4.
The TS markup page appears to be correct. Please confirm the apparent editorial error in LAR Section 2.4.
If you have any questions, please contact Shawn Williams at 301-415-1009 or via e-mail at Shawn.Williams@nrc.gov.
Sincerely, Shawn A. Williams, Senior Project Manager Plant Licensing Branch, II-1 Division of Operating Reactor Licensing
Office of Nuclear Reactor Regulation
Docket Nos. 50-413, 50-414