ML22332A001
Letter Sequence Meeting | |
---|---|
EPID:L-2022-LRM-0093, November 30, 2022, Observation Pre-Submittal Meeting Held with Southern Nuclear Operating Company, Inc., Regarding a Proposed License Amendment Request for Vogtle Electric Generating Plant, Units 1 and 2 (Open) | |
MONTHYEARPMNS20221161, Pre-submittal Meeting - Meeting Between NRC and SNC Regarding Proposed Vogtle TS 5.5.11, Ventilation Filter Testing Program, License Amendment Request2022-11-0707 November 2022
[Table View]Pre-submittal Meeting - Meeting Between NRC and SNC Regarding Proposed Vogtle TS 5.5.11, Ventilation Filter Testing Program, License Amendment Request Project stage: Meeting ML22335A5122022-11-0707 November 2022, 28 November 2022, 2 December 2022 November 30, 2022, Observation Pre-Submittal Meeting Held with Southern Nuclear Operating Company, Inc., Regarding a Proposed License Amendment Request for Vogtle Electric Generating Plant, Units 1 and 2 Project stage: Request ML22332A0012022-11-28028 November 2022 SNC Slides - Pre-Submittal Meeting on November 30, 2022 - Vogtle TS 5.5.11 License Amendment Request Project stage: Meeting ML22335A4922022-12-0202 December 2022 Summary of Observation Pre-Submittal Meeting Held with Southern Nuclear Operating Company, Inc., Regarding a Proposed License Amendment Request for Vogtle Electric Generating Plant, Units 1 and 2 Project stage: Meeting 2022-11-07 |
ML22332A001 | |
Person / Time | |
---|---|
Site: | Vogtle ![]() |
Issue date: | 11/28/2022 |
From: | Gayheart C Southern Nuclear Operating Co |
To: | John Lamb Plant Licensing Branch II |
References | |
Download: ML22332A001 (1) | |
Similar Documents at Vogtle | |
---|---|
Category:Meeting Agenda
MONTHYEARPMNS20240142, Notice of Meeting with Southern Nuclear Operating Company2024-02-0101 February 2024
[Table view]Notice of Meeting with Southern Nuclear Operating Company PMNS20240140, Notice of Meeting with Southern Nuclear Operating Company2024-02-0101 February 2024 Notice of Meeting with Southern Nuclear Operating Company PMNS20240143, Notice of Meeting with Southern Nuclear Operating Company2024-02-0101 February 2024 Notice of Meeting with Southern Nuclear Operating Company PMNS20240141, Notice of Meeting with Southern Nuclear Operating Company2024-02-0101 February 2024 Notice of Meeting with Southern Nuclear Operating Company PMNS20231396, Pre-Submittal Meeting with Southern Nuclear Operating Company (SNC) Regarding a Proposed Relief Request for Explosively Actuated Valves at Vogtle Electric Generating Plant (Vogtle), Units 3 and 42023-12-15015 December 2023 Pre-Submittal Meeting with Southern Nuclear Operating Company (SNC) Regarding a Proposed Relief Request for Explosively Actuated Valves at Vogtle Electric Generating Plant (Vogtle), Units 3 and 4 PMNS20231383, Pre-submittal Meeting with Southern Nuclear Operating Company, Inc. (SNC) Regarding the Proposed Transition of the Vogtle Electric Generating Plant, Units 3 and 4 Ndqam Into the SNC Fleet QATR2023-12-11011 December 2023 Pre-submittal Meeting with Southern Nuclear Operating Company, Inc. (SNC) Regarding the Proposed Transition of the Vogtle Electric Generating Plant, Units 3 and 4 Ndqam Into the SNC Fleet QATR PMNS20231357, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231360, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231355, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231363, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231358, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231364, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231356, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231365, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231359, Notice of Meeting with Southern Nuclear Operating Company2023-11-30030 November 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231347, Notice of Public, pre-submittal Meeting with Southern Nuclear Operating Company, Inc. (SNC) to Discuss a Proposed Fleet License Amendment Request (LAR) for Farley, Hatch, and Vogtle2023-11-29029 November 2023 Notice of Public, pre-submittal Meeting with Southern Nuclear Operating Company, Inc. (SNC) to Discuss a Proposed Fleet License Amendment Request (LAR) for Farley, Hatch, and Vogtle PMNS20231198, Closed Meeting - Security-Related - SNC Fleet Physical Barriers Exemptions.The Basis for the Closed Meeting Is the Discussion of Official Use Only - Security-Related Information2023-10-25025 October 2023 Closed Meeting - Security-Related - SNC Fleet Physical Barriers Exemptions.The Basis for the Closed Meeting Is the Discussion of Official Use Only - Security-Related Information PMNS20231197, Pre-Submittal Meeting for Proposed License Amendment Request (LAR) to Reduce Ultimate Heat Sink (UHS) and Nuclear Service Cooling Water (NSCW) Fan Mission Times2023-10-24024 October 2023 Pre-Submittal Meeting for Proposed License Amendment Request (LAR) to Reduce Ultimate Heat Sink (UHS) and Nuclear Service Cooling Water (NSCW) Fan Mission Times PMNS20231111, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231116, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231118, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231114, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231117, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231115, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231112, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231113, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231119, Notice of Meeting with Southern Nuclear Operating Company2023-10-0303 October 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230993, Pre-Submittal Meeting for a Proposed License Amendment Request to Technical Specification 3.7.6, Main Control Room Emergency Habitability System (Ves)2023-09-14014 September 2023 Pre-Submittal Meeting for a Proposed License Amendment Request to Technical Specification 3.7.6, Main Control Room Emergency Habitability System (Ves) PMNS20231002, Notice of Meeting with Southern Nuclear Operating Company2023-09-0707 September 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231001, Notice of Meeting with Southern Nuclear Operating Company2023-09-0707 September 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231003, Notice of Meeting with Southern Nuclear Operating Company2023-09-0707 September 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20231004, Notice of Meeting with Southern Nuclear Operating Company2023-09-0707 September 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230909, Notice of Meeting with Southern Nuclear Operating Company2023-08-29029 August 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230802, Notice of Meeting with Southern Nuclear Operating Company2023-08-11011 August 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230907, Notice of Meeting with Southern Nuclear Operating Company2023-08-0404 August 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230908, Notice of Meeting with Southern Nuclear Operating Company2023-08-0404 August 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230910, Notice of Meeting with Southern Nuclear Operating Company2023-08-0404 August 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230800, Notice of Meeting with Southern Nuclear Operating Company2023-07-0505 July 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230804, Notice of Meeting with Southern Nuclear Operating Company2023-07-0505 July 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230801, Notice of Meeting with Southern Nuclear Operating Company2023-07-0505 July 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230803, Notice of Meeting with Southern Nuclear Operating Company2023-07-0505 July 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230576, Notice of Meeting with Southern Nuclear Operating Company2023-06-28028 June 2023 Notice of Meeting with Southern Nuclear Operating Company ML23163A2362023-06-21021 June 2023 Agenda - Southern Nuclear Operating Company - Vogtle Electric Generating Plant, Units 1 & 2, LAR and Exeptions to Allow Use of Lead Test Assemblies for ATF - Sc - June 21, 2023 PMNS20230699, Notice of Meeting with Southern Nuclear Operating Company2023-05-31031 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230697, Notice of Meeting with Southern Nuclear Operating Company2023-05-31031 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230696, Notice of Meeting with Southern Nuclear Operating Company2023-05-31031 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230698, Notice of Meeting with Southern Nuclear Operating Company2023-05-31031 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230369, Notice of Meeting with Southern Nuclear Operating Company2023-05-19019 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230562, Notice of Meeting with Southern Nuclear Operating Company2023-05-0909 May 2023 Notice of Meeting with Southern Nuclear Operating Company PMNS20230367, Notice of Meeting with Southern Nuclear Operating Company2023-05-0909 May 2023 Notice of Meeting with Southern Nuclear Operating Company 2024-02-01 Category:Meeting Briefing Package/Handouts MONTHYEARML24022A1192024-01-24024 January 2024
[Table view]Slides - SNC Slides - Pre-Submittal Meeting on January 24, 2024 - Vogtle 3 & 4 Explosively Actuated Valves Relief Request ML23361A0812024-01-0808 January 2024 SNC Slides - Pre-Submittal Public Meeting on January 8, 2024 Related to Fleet QATR ML24004A1852024-01-0404 January 2024 SNC Slides - Pre-Submittal Public Meeting on January 8, 2024 Related to Fleet QATR Revised ML23257A2322023-09-28028 September 2023 SNC Presentation - Pre-Submittal Meeting on September 28, 2023 - Proposed Vogtle 3 and 4 TS 3.7.6 LAR ML23137A1162023-06-0202 June 2023 Draft Slides for Advisory Committee on Reactor Safeguards Subcommittee Meeting Regarding Use of Accident Tolerant Fuel Lead Test Assemblies ML23094A1402023-04-0404 April 2023 4 -- 2022 Aam Slides ML23055A0402023-02-24024 February 2023 VEGP, Unit 4, Potential License Amendment Request for Prior to Initial Criticality Overview Presentation ML23033A0232023-02-0202 February 2023 Dashboard Report 2-2-2023 ML22329A0192022-12-0101 December 2022 Southern Nuclear Company Slides - Pre-Submittal Meeting on December 1, 2022 - Vogtle SR 3.4.14.1 LAR and Alternative Relief Request 1 ML22335A0372022-12-0101 December 2022 Dashboard Report 12-1-2022 ML22332A0012022-11-28028 November 2022 SNC Slides - Pre-Submittal Meeting on November 30, 2022 - Vogtle TS 5.5.11 License Amendment Request ML22332A5372022-11-28028 November 2022 Draft LAR 23-001 for 12-8-22 Public Meeting ML22319A1232022-11-15015 November 2022 Kozak Slides for November 15, 2022 Public Meeting on Part 52 Lessons Learned ML22319A0052022-11-15015 November 2022 NEI Slides for November 15 2022 Public Meeting on Part 52 Lessons Learned ML22319A1242022-11-15015 November 2022 NRC Slides for November 15, 2022 Public Meeting on Part 52 Lessons Learned ML22251A0002022-09-30030 September 2022 Pre-Submittal Meeting on September 13, 2022 - Vogtle Online Monitoring LAR ML22265A0982022-09-22022 September 2022 NRC Slides on Part 52 Lessons Learned Construction Initiative for Public Meeting on 9/27/2022 ML22265A0972022-09-22022 September 2022 Southern Nuclear Company Slides on Lessons Learned from Part 52 Implementation for Public Meeting on 9/27/2022 ML22138A3952022-05-24024 May 2022 Slides - SNC Slides - Pre-Submittal Meeting on May 24, 2022 - Vogtle RR RWST Suction Check Valves ML22137A2812022-05-23023 May 2022 Slides - SNC Slides - Pre-Submittal Meeting on May 23, 2022 - Vogtle TS 3.8.1 and TSTF-163 LAR ML22126A0102022-05-11011 May 2022 Pre-Submittal Meeting on May 11, 2022 - Vogtle ATF LTAs LAR and Exemption Requests - Licensing Questions ML22123A3332022-05-10010 May 2022 Pre-Submittal Meeting 2: TSTF-51, TSTF-471, TSTF-490, and Alternative Source Term License Amendment Request - May 10, 2022 (EPID L-2022-LRM-0033)(slides) ML22110A1702022-04-20020 April 2022 4 2022 Annual Assessment Meeting.Final ML22021B6472022-01-27027 January 2022 Pre-Submittal for Westinghouse Increased Enrichment Accident Tolerant Fuel Lead Test Assemblies (EPID L-2022-LRM-0003) (Slides) ML21306A0242021-11-30030 November 2021 SNC Pre-Submittal Meeting for LAR to Relocate Augmented Piping Inspection Program Details from TSs to a Licensee Controlled Document for Farley Nuclear Plant, Units 1 & 2; and Vogtle Electric Generating Plant, Units 1 & 2 (EPID L-2021-LRM-0 ML21333A2172021-11-29029 November 2021 Readiness Group Presentation During 12-2-21 Public Meeting ML21230A2842021-08-18018 August 2021 SNC Slides - Vogtle MSIV Elimination LAR - Pre-submittal Meeting Part 2 - 08-25-2021 ML21187A0972021-07-0808 July 2021 Late Filed Allegations (Lfa) Process ML21193A0762021-07-0808 July 2021 ITAAC Related to Incore Instrument Thimble Assembly (Iita) ML21172A1312021-07-0101 July 2021 Pre-Submittal Meeting Alternate Source Term and TSTF-490 ML21193A0772021-06-24024 June 2021 Exemption from Operator Written Examination and Operating Test for Unit 4 Licenses, 6-24-21 Pre-submittal Meeting ML21085A4902021-05-19019 May 2021 Risk-informed Resolution of Generic Letter 2004-02 ML21064A3652021-03-0101 March 2021 Dashboard Report 3-1-2021 ML21027A2062021-02-28028 February 2021 Fixed 8-Hour Emergency Light Deviation Pre-Submittal Meeting, February 2021 (Slides) ML21057A0182021-02-26026 February 2021 Pre-Submittal Meeting Revise Technical Specification 3.2.1 Heat Flux Hot Channel Factor (Fq(Z)) (EPID L-2021-LRM-0023) (Slides) ML21036A1172021-02-0505 February 2021 SNC Slides - Pre-Submittal Meeting on February 16, 2021 - Beacon LAR ML20343A0742020-12-0202 December 2020 Dashboard Report 12-2-2020 ML20318A1032020-11-12012 November 2020 SNC ERO Staffing LAR RAI Responses ML20314A0962020-11-0202 November 2020 Dashboard Report 11/02/2020 ML20217L4312020-08-13013 August 2020 Edwin I Hatch, Units 1 and 2; and Vogtle Electric Plant, Units 1, 2, 3, and 4 - Meeting Slides a License Amendment Request for the Emergency Plan (EPID Nos L-2020-LLA-0150 and L-2020-LLA-051 ML20136A2832020-05-15015 May 2020 4 EOC Slides ML20114E3032020-04-23023 April 2020 Risk-Informed GL 2004--02 Pre-Submittal NRC Meeting - May 2020 ML20007D6772020-01-0808 January 2020 AP1000 Public Presentation Entitled Reactor Oversight Process (ROP) for Inspecting Vogtle Site with AP1000 Design ML19303A0252019-11-0404 November 2019 Risk-Informed GSI-191 NRC Public Meeting ML19295D4672019-10-30030 October 2019 Public Meeting for ITAAC Hearing Process, October 30, 2019 ML19239A1932019-08-29029 August 2019 SNC Slides for Public Pre-Submittal Meeting on August 29, 2019 (Eptd L-2019-LRM-0054) ND-19-0962, AP1000 Structural Reconciliation - Westinghouse Electric Company & Southern Nuclear Company Technical Exchange Meeting: August 13, 20192019-08-0202 August 2019 AP1000 Structural Reconciliation - Westinghouse Electric Company & Southern Nuclear Company Technical Exchange Meeting: August 13, 2019 ML19123A3562019-05-0202 May 2019 Public Meeting Summary - Vogtle Electric Generating Plant, Docket Nos. 50-424 and 50-425 ND-19-0152, Enclosure 2, Presentation Material: Functional Arrangement (FA) ITAAC, FA System Package Examples -Closed Meeting (Non-Proprietary)2019-02-14014 February 2019 Enclosure 2, Presentation Material: Functional Arrangement (FA) ITAAC, FA System Package Examples -Closed Meeting (Non-Proprietary) ML19025A0242019-01-25025 January 2019 SNC License Amendment Request for Proposed Changes to Emergency Response Organization Staffing and Augmentation 2024-01-08 Category:Slides and Viewgraphs MONTHYEARML24022A1192024-01-24024 January 2024
[Table view]Slides - SNC Slides - Pre-Submittal Meeting on January 24, 2024 - Vogtle 3 & 4 Explosively Actuated Valves Relief Request ML23361A0812024-01-0808 January 2024 SNC Slides - Pre-Submittal Public Meeting on January 8, 2024 Related to Fleet QATR ML24004A1852024-01-0404 January 2024 SNC Slides - Pre-Submittal Public Meeting on January 8, 2024 Related to Fleet QATR Revised ML23304A2682023-11-0707 November 2023 License Amendment Request to Revise the Ultimate Heat Sink Mission Time Pre Submittal Meeting on November 7, 2023 ML23311A2452023-11-0707 November 2023 Pre-Submittal Meeting on November 7, 2023 - License Amendment Request to Revise the Ultimate Heat Sink Mission Time (Slides) ML23293A0052023-10-20020 October 2023 Lessons Learned from the ITAAC Hearing Process for Vogtle 3 and 4 ML23257A2322023-09-28028 September 2023 SNC Presentation - Pre-Submittal Meeting on September 28, 2023 - Proposed Vogtle 3 and 4 TS 3.7.6 LAR ML23137A1162023-06-0202 June 2023 Draft Slides for Advisory Committee on Reactor Safeguards Subcommittee Meeting Regarding Use of Accident Tolerant Fuel Lead Test Assemblies ML23094A1402023-04-0404 April 2023 4 -- 2022 Aam Slides ML23072A1802023-03-13013 March 2023 2023 RIC Powerpoint Slide Presentation, Vogtle 3: Journey from Construction to Operations ML23055A0402023-02-24024 February 2023 VEGP, Unit 4, Potential License Amendment Request for Prior to Initial Criticality Overview Presentation ML23033A0232023-02-0202 February 2023 Dashboard Report 2-2-2023 ML22335A5542022-12-0101 December 2022 Slides - SNC Slides - Pre-Submittal Meeting on December 1, 2022 - Vogtle SR 3.4.14.1 LAR and Alternative Relief Request - ML22335A0372022-12-0101 December 2022 Dashboard Report 12-1-2022 ML22329A0192022-12-0101 December 2022 Southern Nuclear Company Slides - Pre-Submittal Meeting on December 1, 2022 - Vogtle SR 3.4.14.1 LAR and Alternative Relief Request 1 ML22332A0012022-11-28028 November 2022 SNC Slides - Pre-Submittal Meeting on November 30, 2022 - Vogtle TS 5.5.11 License Amendment Request ML22319A1242022-11-15015 November 2022 NRC Slides for November 15, 2022 Public Meeting on Part 52 Lessons Learned ML22319A1232022-11-15015 November 2022 Kozak Slides for November 15, 2022 Public Meeting on Part 52 Lessons Learned ML22319A0052022-11-15015 November 2022 NEI Slides for November 15 2022 Public Meeting on Part 52 Lessons Learned ML22278A0382022-10-0505 October 2022 Dashboard Report 10-5-2022 ML22251A0002022-09-30030 September 2022 Pre-Submittal Meeting on September 13, 2022 - Vogtle Online Monitoring LAR ML22265A0982022-09-22022 September 2022 NRC Slides on Part 52 Lessons Learned Construction Initiative for Public Meeting on 9/27/2022 ML22265A0972022-09-22022 September 2022 Southern Nuclear Company Slides on Lessons Learned from Part 52 Implementation for Public Meeting on 9/27/2022 ML22206A1712022-07-25025 July 2022 Dashboard Report 7-25-2022 ML22206A1682022-07-25025 July 2022 Dashboard Report 7-25-2022 ML22201A0442022-07-20020 July 2022 Voices Dashboard Report for Vogtle Unit 3 as of July 20, 2022 ML22138A3952022-05-24024 May 2022 Slides - SNC Slides - Pre-Submittal Meeting on May 24, 2022 - Vogtle RR RWST Suction Check Valves ML22144A0502022-05-24024 May 2022 Dashboard Report 5-24-2022 ML22144A0492022-05-24024 May 2022 Dashboard Report 5-24-2022 ML22137A2812022-05-23023 May 2022 Slides - SNC Slides - Pre-Submittal Meeting on May 23, 2022 - Vogtle TS 3.8.1 and TSTF-163 LAR ML22126A0102022-05-11011 May 2022 Pre-Submittal Meeting on May 11, 2022 - Vogtle ATF LTAs LAR and Exemption Requests - Licensing Questions ML22123A3332022-05-10010 May 2022 Pre-Submittal Meeting 2: TSTF-51, TSTF-471, TSTF-490, and Alternative Source Term License Amendment Request - May 10, 2022 (EPID L-2022-LRM-0033)(slides) ML22126A0012022-05-0606 May 2022 SNC Slides - Pre-Submittal Meeting on May 11, 2022 - Vogtle ATF LTAs LAR and Exemptions ML22110A1702022-04-20020 April 2022 4 2022 Annual Assessment Meeting.Final ML22060A0062022-02-28028 February 2022 4Q 2021 Performance Summary U3 ML22021B6472022-01-27027 January 2022 Pre-Submittal for Westinghouse Increased Enrichment Accident Tolerant Fuel Lead Test Assemblies (EPID L-2022-LRM-0003) (Slides) ML22026A0582022-01-26026 January 2022 Dashboard Report 1-26-2022 ML21306A0242021-11-30030 November 2021 SNC Pre-Submittal Meeting for LAR to Relocate Augmented Piping Inspection Program Details from TSs to a Licensee Controlled Document for Farley Nuclear Plant, Units 1 & 2; and Vogtle Electric Generating Plant, Units 1 & 2 (EPID L-2021-LRM-0 ML21333A2172021-11-29029 November 2021 Readiness Group Presentation During 12-2-21 Public Meeting ML21230A2842021-08-18018 August 2021 SNC Slides - Vogtle MSIV Elimination LAR - Pre-submittal Meeting Part 2 - 08-25-2021 ML21197A0032021-08-0606 August 2021 Slides - SNC Slides - Pre-Submittal Meeting on August 13, 2021 - Vogtle TS 3.3.1 and 3.3.2 LAR ML21193A0762021-07-0808 July 2021 ITAAC Related to Incore Instrument Thimble Assembly (Iita) ML21187A0972021-07-0808 July 2021 Late Filed Allegations (Lfa) Process ML21188A3612021-07-0606 July 2021 1Q 2021 Performance Summary U4 ML21188A3592021-07-0606 July 2021 1Q 2021 Performance Summary U3 ML21188A3622021-07-0606 July 2021 Archives ML21193A0772021-06-24024 June 2021 Exemption from Operator Written Examination and Operating Test for Unit 4 Licenses, 6-24-21 Pre-submittal Meeting ML21124A2522021-05-31031 May 2021 Request for Alternative to ASME Section XI and Section III Requirements for Repair of Reactor Vessel Head Penetrations - NRC Pre-submittal Meeting May 10, 2021 (EPID L-2021-LRM-0047) (Slides) ML21085A4902021-05-19019 May 2021 Risk-informed Resolution of Generic Letter 2004-02 ML21113A2272021-04-23023 April 2021 Readiness Group Public Meeting Presentation Slides - April 28, 2021 2024-01-08 |
Text
SNC Vogtle 1&2 Pre-Submittal Meeting Technical Specification Revision to Modify Acceptance Criteria for Charcoal Filter Testing, TS 5.5.11.c November 30, 2022
Meeting Purpose and Agenda
- The purpose for this meeting is to discuss proposed amendment request to revise the charcoal adsorber penetration acceptance criteria for the Control Room Emergency Filtration System (CREFS) for Vogtle Technical Specification (TS) 5.5.11.c
- This meeting will cover the following topics:
- Background
- Proposed License Amendment Request
- Evaluation
- Precedent
- Schedule 2
=
Background===
Background
- TS 5.5.11, Ventilation Filter Testing Program (VFTP), item c. identifies the test method and acceptance criteria for the laboratory test of the charcoal adsorber for the CREFS and Piping Penetration Area Filtration and Exhaust (PPAFES) systems
- The proposed change would revise the TS 5.5.11.c CREFS filter penetration criteria to improve the ability to monitor the performance of the charcoal. This would improve:
- margin for trending of results for better prediction of charcoal filter service life, and
- proactive planning for filter replacement
- Regulatory basis for our requested change based on GL 99-02, Laboratory Testing Of Nuclear- Grade Activated Charcoal 4
Proposed License Amendment Request
Technical Specification 5.5.11 5.5.11 Ventilation Filter Testing Program (VFTP)
A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in accordance with Regulatory Guide 1.52, Revision 2, and ASME N510-1980:
Proposed revision to TS 5.5.11.c 6
Evaluation Evaluations Performed
- The revision to the acceptance criteria does not change the test methodology
- GL 99-02, Laboratory Testing Of Nuclear- Grade Activated Charcoal, allows the use of a safety factor of 2, which maintains the credited carbon efficiency of 99% in the dose calculations.
- The proposed change to revise CREFS charcoal adsorber methyl iodide penetration acceptance criteria in TS 5.5.11.c from 0.2% to 0.5% is consistent with GL 99-02.
8
Precedent Precedent Entergy submittal on June 12, 2003 (ML031670927) for Indian Point 3, which was NRC approved on October 30, 2003 (ML033070330)
Revised the Control Room Ventilation System (CRVS) charcoal adsorber testing protocol and acceptance criteria to be consistent with GL 99-02.
Florida Power & Light submittal on November 17, 1999 (ML993270236) for Saint Lucie, which was NRC approved on December 7, 2000 (ML003776207).
10
Schedule Schedule
- Submit LAR - 1st Quarter 2023
- Request approval - 1 year from acceptance 12
Questions?