-Docket No. 50-333 Power Authority of the State of Ucw York J5, 2A. 3 ' / (
NITN:
Mr. Asa George 10 Columbus Circle New York, Ucw York 10019 Centioment
' At a aceting held on September 24, 1970 concerning the status of certain matters to be resolved during the construction of the FitzPatrick Nucicar Power Plant, we discussed the design criteria under consideration with regt,rd to pipe whip protection and the proposed on-site cacrgency power system.
,' o ft.
fyar#(
You indicated that ycur criteria for pice whip protection were ctated in 2
(fL#
_ Supplement 13 to your application and include a statencnt that the mini-Eus acEcyttrble core cooling uould consist of either a single core spray 1
We systen or two of four low pressure coolant injection (LPCI) pumps.
noted that the adecuacy of the core coolinn provided by only two LPCI
~s pu:aps has uat haua deususLtated Lv uut nutisfaction. U ud'upin infut-h mation that we have considered in previous reviews, we conclude that the combination of a partial LPCI system (consisting of two pumps) and 1 core spray system is acceptable, but that two LPCI pumps alone would not be adequate.
Unless the results of a rigorous analysis, including appropriate experi-
.i mental justification, can be provided to support your statement, Lour; proposed criteria for pipe whip protection for engineered safety. features i
s2Tould be revised with regard to the emergency core cooling systems whicli; 7
are ' to'be protected from the. effects of pipe whip.
l You indicated at the meeting that you had completed a study of the advan-tages and disadvantages of the two diesel singic bus system and the one To complete our evaluation of the acceptability t
diesel single bus systen.
of the parallel-two-diesel single bus system, we need the results of your Your diccussion should include considera-study comparing the two systems.
tion of the need for synchauule.ution. Fu t Lhe t-um uuted lu ihe leitet f a u,,,
the Advisory Conmittee on Reactor Safegua:ds, dated January 27, 1970, regarding testing, describe your picns to demonstrate "... rigorous, realirric i
8910050211 890921
' ~
PDR ADDCK 05000333 y
O PDR
g-
,,,I*.
54 Power Authority of the State of Of.'T 19 B/0 New York '
-g:
preoperational and inservice trsting program [to] be undertaken on the t
l diesel system which is adopted." A discussion of suitabic alternatives j
should bo deceribed that may have to be considered in the event the system selected does not meet design requirements.
a i
Picase contact us should you wish to set up a meeting to discuss the fore-going matters further.