May 22, 1989 Director of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Station Pl-137 Washington, DC 20555
Dear Sir:
Subject:
Oyster Creek Nuclear Generating Station Docket No. 50-219 Special Report Enclosed is Special Report 89-01 which is submitted in accordance with Technical' Specification 3.12.E.
If any questions or comments should arise, please contact Mr. George Busch, Oyster Creek Licensing Manager at (609) 971-4643.
Very truly yours, kDj60 8
890522 S
05000219 PNU D E. E. F t patrick Vice P esident and Director Oyster Creek EEF/GB/aa (0666A)
Enclosure cc: Mr. William T. Russell, Administrator l
Region I l
U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Mr. Alexander W. Dromerick, Project Manager U.S. Nuclear Regulatory Commission Division of Reactor Projects I/II i
Washington, DC 20555 NRC Resident Inspector Oyster Creek Nuclear Generating Station f,8 Forked River, NJ 08731 f
'fl GPU Nuclear Corporation is a subsidiary of General Public Utilities Corporation
v 0
~
'o'
.p I
SPECI AL" REPORT 89-01 o
Report'Date:
4 Occurrence Date:' Soril 22, 1989 Identification' of Occurrence:
A non-functional' fire barrier penetration was not repaired within seven-(7) days as required by Technical Specification 3.12.E..
Description of Occurrence-During a routine surveillance of fire penetration seals, one.(1). penetration into the A/B Battery Room was identified as not meeting the acceptance criteria. This seal was declared non-functional due to missing sealant material.
Analysis of Occurrence-p The Oyster Creek plant was in a refueling outage during which required L
mai'ntenance on: systems and components was being performed. Upon. discovering the.non-functional fire barrier seal,.a work. request was submitted to repair-t se fire barrier within.seven (7) days. Due to constraints imposed by r nt'possible to accomplish this repair within the 'seven (7) priority, it was 11 creased outage ~ related maintenance activities of a higher days.as r oecified.. -Since the required fire watches have been established, the safety s significance of this. event is minimal.
Corrective Action Upon discovering the non-functional fire seal, within one hour, a fire watch was established in accordance with the technical specification.
The non-functional fire barrier seal is planned to be restored to' operable status
~ by May 23,1989.