Forwards Safety Evaluation of NRC 881205-08 Audit of Util Response to IE Bulletin 79-27.Expresses Concern That Util Had No Procedures for Testing Nonnuclear Instrumentation/Ics Power Supply Automatic Bus Transfer Switches
ML20246J518
Person / Time
Site: Arkansas Nuclear 
Issue date: 07/07/1989
From: Craig Harbuck
Office of Nuclear Reactor Regulation
To: Tison Campbell
ARKANSAS POWER & LIGHT CO.
Shared Package
ML20246J521 List:
References
IEB-79-27, TAC-68199, NUDOCS 8907170391
Download: ML20246J518 (3)


Text

-

Dp et.No. 50-313-Mr. T. Gene Campbell

.Vice President, Nuclear Arkansas Power and Light Company Post Office Box 551

~

Little Rock, Arkansas '72203

Dear Mr. Campbell:

SUBJECT:

ARKANSAS NUCLEAR ONE, UNIT 1 AUDIT FOR VERIFICATION OF RESOLUTIONOFIEBULLETIN79-27 CONCERNS (TACNO.68199)

Enclosed is the Safety Evaluation (SE) of the staff's December 5-8, 1988, audit i

of your response to IE Bulletin 79-27, for Arkansas Nuclear One, Unit 1 (ANO-1).

Based on the SE, the staff concludes that Arkansas Power and Light Company has adequately resolved the concerns of the bulletin for ANO-1 in design and procedure.

However, during the audit, the staff was concerned that you had no procedures for testing the non-nuclear instrumentation /ICS power supply automatic bus transfer switches and the inverter static transfer switches. As discussed in the exit meeting you comuitted to evaluate our position that periodic testing of the switches using an approved procedure is necessary to demonstrate their reliability.

We. request that you provide in writing the results of your evaluation and your plans for testing of these switches within 60 days of the receipt of this letter.

The audit team appreciated the outstanding support your staff provided during the conduct of the audit. Those members of your staff who assisted in' that effort are to be commended.

Please note that TAC No. 68199 will remain open until the entire series of audits of the Babcock and Wilcox Safety and Performance Improvement Program for ANO-1 is completed. The reporting and/or recordkeeping requirements contained.in the letter affect fewer than ten respondents; therefore, ONB clearance is not required under P.L.96-511.

Sincerely,

/s/

C. Craig Harbuck, Project Manager Project Directorate - IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page DISTRIBUTION

' Docket File" NRC PDR Local PDR PD4 Reading G. Holahan L. Rubenstein F. Hebdon P. Noonan C. Harbuck OGC-Rockville E. Jordan-B. Grimes I. Ahmed ACRS (10)

PD4 Plant File DOCUMENTLNAME: ANO LTR/ TAC 68199 PD4/L h b PD4/?

P 4/D

'go/

PNoonaV I Chad uck:b FHebdon 07/b/89 07/f/89 07/o')/89 i

8907170391 890707 ADOCK0500g3 DR

g 1

t

+

j

,, u,

'o UNITED STATES l

g

[.

g NUCLEAR REGULATORY COMMISSION

E WASHINGTON, D. C. 20555

(

,f July 7 1989

....+

'Do'cket No. 50-313

)

1 Mr. T. Gene Campbell l

i Vice President, Nuclear d

Arkansas Power and Light Company Post Office Box 551 Little Rock, Arkansas 72203

Dear Mr. Campbell:

SUBJECT:

ARKANSAS NUCLEAR ONE, UNIT 1 AUDIT FOR VERIFICATION OF RESOLUTION OF lE BULLETIN 79-27 CONCERNS (TAC NO. 68199)

EnclosedistheSafetyEvaluation(SE)ofthestaff'sDecember 5-8, 1988, audit of your response to IE Eulletin 79-27, for Arkansas Nuclear One, Unit 1- (ANO-1).

Based on the SE, the staff concludes that Arkansat Power and Light Company has adequately resolved the concerns of the bulletin for ANO-1 in design and procedure.

However, during'the audit, the staff was concerned that you had no procedures for testing the non-nuclear instrumentation /ICS power supply automatic bus transfer switches'and the inverter static transfer switches.' As discussed in the exit meeting you contaitted to evaluate our position that periodic testing of the switches using an approved procedure is necessary to demonstrate their reliability.

We request that you provide in writing the results of your evaluation and your plans for testing of these switches within 60 days of the receipt of this letter.

The audit team appreciated the outstanding support your staff provided during the conduct of the audit. Those members of your staff who assisted in that effort are to be commended.

Please note that TAC No. 68199 will remain open until the entire series of audits of-the Babcock and Wilcox Safety and Performance Improvement Program for ANO-1 is completed. The reporting ard/or recordkeeping requirements contained in the letter affect fewer than ten respondents; therefore, OMB

. clearance is not required under P.L.96-511.

Sincerely,

%0Dn In.

C. Craig Ha ub,ProjectManager Project Directorate - IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation Encloture:

As. stated cc w/ enclosure:

See next page

.f,jY '....

1

%w H

Mr. T. Gene Campbell L"

. Arkansas Power & Light Company Arkansas Nuclear One, Unit 1-

.cc:

Mr. Early Ewing, General Manager Technical Support and Assessment Arkansas Nuclear One P. O. Box 608' Russe 11ville, Arkansas 72801 Mr. Niel Carns, Director Nuclear 0perations Arkansas Nuclear One

P. O. Box 608

~ Russellville, Arkansas 72801 Mr.. Nicholas S. Reynolds-Bishop, Cook, Purcell & Reynolds 1400 L Street, N.W.

. Washington, D.C.. 20005-3502 Mr.' Robert B.-Bor. sum Babcock & Wilcox' Nuclear Power. Generation Division 1700.Rockville Pike, Suite 525 Rockville, Maryland 20852-Senior Resident Inspector U.S. Nuclear. Regulatory Commission 1 Nuclear Plant Road Russellville, Arkansas 72801 Regional Administrator, Region IV' U.S. Nuclear. Regulatory Commission Office'of Executive Director-

-for Operations

'611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 a

Honorable Joe W. Phillips County Judge of Pope County 1

Pope County Courthouse i

Russellville, Arkansas 72203 Ms. Greta Dicus, Director Division of Environmental Health Protection Arkansas Department of Health 4815 West Markam Street 1

Little Rock,' Arkansas 72201

__1.___.__.________.___;_____.___._

.