Jump to navigation Jump to search
Forwards Insp Rept 50-263/98-14 on 980810-14.No Violations Noted.Insp Consisted of Selective Exam of Procedures & Representative Records,Walkdowns Throughout Plant,Interviews W/Personnel & Observations of Activities in Progress
ML20239A235
Person / Time
Site: Monticello Xcel Energy icon.png
Issue date: 09/04/1998
From: Grobe J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Wadley M
NORTHERN STATES POWER CO.
Shared Package
ML20239A238 List:
References
50-263-98-14, NUDOCS 9809080331
Download: ML20239A235 (2)


See also: IR 05000263/1998014

Text

=

.

3

1

Septernber 4, - 1998

'

' Mr. M. Wadley

President, Nuclear Generation

L Northem States Power Company ,

- 414 Nicollet Mall

minneapolis, MN 55401

Dear Mr. Wadley:.

SUBJECT: NRC RADIATION PROTECTION INSPECTION REPORT 50-263/98014(DRS)

Dear Mr. Wadley:

'

. On August 14,1998, the NRC completed an inspection at your Monticello Nuclear Generating

Plant. The enclosed report presents the results of that inspection. The inspection examined

activities conducted under your license related to radiation safety and to compliance with the

Commission's rules and regulations and with the conditions of your license.

Specifically, this inspection reviewed the calibration and functional checks of the process and

area radiation monitors, the methodology to quantify the gaseous radioactive effluents from the -

plant, semi-annual effluent reports submitted to the Commission, and the surveys for the free

release of equipment and material from the Radiologically Controlled Area. Within these areas,

the inspection consisted of selective examinations of procedures and representative records,

walkdowns throughout the plant, interviews with personnel, and observations of activities in

progress. No violations of NRC requirements were identified during this inspection.

Overall, the gaseous effluents program was well implemented as evidenced by the Semi-

' Annual Effluents Reports, and the materiel condition and calibrations of the process radiation

monitors (PRMs). In addition, the safety control functions of the PRMs were successfully

tested, the meteorological tower calibrations were properly conducted, and the area radiation

monitor calibrations were appropriate for their indication functions.

- However, your staff's demonstration of a self-checking, questioning attitude was inconsistent.

' Evidence of your staff's effective questioning attitude included their identification of an

incorrect, non-conservative main steam line radiation monitor alarm set point and the

miscalibration of a control room PRM. However, the fact that the alarm set point exceeded the

correct value for several months (though the data was reviewed daily), and the initial incorrect

calibration of the control room PRM demonstrated the lack of a self-checking, questioning

attitude by other plant personnel. ]

In accordance with 10 CFR 2.790 of the NRC's " Rules and Practice," a copy of this letter and its

enclosure will be placed in the NRC Public Document Room (PDR).

9809080331 980804 '

POR ADOCK 05000263 +

8 PDR 3

.

J

. __ -

._- _______-_ ___ __ --___ ____ -__ ____ ___ - _____-_ - _ _ - _- ._ _ - - __ - - _ _

..

l

1

M. Wadley 2

We will gladly discuss any questions you have conceming this inspection.

Sincerely,

Original /s/ J. A. Grobe

John A. Grobe, Director

Division of Reactor Safety

Docket No.: 50-263

l

License No.: DPR-22

Enclosure: Inspection Report 50-263/98014(DRS)

cc w/enci: Plant Manager, Monticello

State Liaison Officer, State

of Minnesota

Distribution:

CAC (E-Mail)

Project Mgr., NRR w/enci

J. Caldwell, Rill w/ encl

C, Pederson, Rill w/enci .

B. Clayton, Rlll w/ encl

SRI Monticello w/enci

DRP w/enci

TSS w/enci

l DRS (2) w/enci

'

BL C /e 2.B

' Docket File w/ encl"

GREENS

LEO (E-Mail)

DOCDESK (E-Mail)

\

'

080001 ,

I

DOCUMENT NAME: G:DRS\ MON 98014.DRS

To recePo a copy of thee document, Indicato in the box: *C" = Copy atthout attachment /encloswe *E's Copy with attachment / enclosure "N" * No copy

OFFICE Rlli l6 Rlli l/! Rlli lr Rlli ~,/ J J

NAME RGlinski:jp R6-- GShear (d/(o MKunowski m g JGroW

DATE 09// /98 09/a/98 09/? /98 09/.j5/94

OFFICIAL RECORD COPY

'

l