'I BAILEY 862 I

S0 LID STATE LOGIC M 0 D U L-E BI- M 0.N T H L Y FAILURE R.E P 0 R T HOPE CREEK GE-NERATING ,.

STATION:

AUGUST 17,1987 i

8708280181 870820 PDR ADOCK 05000354 P PDR L___ -----_____________________x______________----_--. - _ _ _ , __ -- -_ _ _ _ _ _ _ _

HOPE CREEK GENERATING STATION BAILEY SOLID STATE LOGIC MODULE PAILURES FOR JUNE AND JULY, 1987

)

1 1

9 Modules Failures - There were 9 SSLM failures which I occurred in the two month period {

beginning June 1, 1987 through July j 31, 1987.

] 1 Projected Reliability 2.39% per year. failure rate 1). Based upon data from June and July, 1987, with 2 and 7 failures respectively, for a total population of 2258 modules.

2) The projected annual failure rate is i based upon bi-monthly data as presented in.a letter from C. A.

McNeill, Jr. to Dr. T. E. Murley, dated October 15, 1986 (NLR-N86148).

  • Correction to February data i - The failure data for February, 1987 is being revised from l two to three failures for the one month period. See attached failure record.. (

1

Record # 06-1 Assembly: SC652 Locations. 1 5 S/N 0151 Fail Dates 06/26/87 Werk Urder Number 8706260292 System 4.16 KV ELEC DIEiRIBUTION Classs- 1E Description of Failures OUTPUT BUFFERS 1 AND 2 FAILED TO THE HIGH STATE Affect on System FAILURE RESULTED IN LOSS OF " CLOSED" AND " TRIP" INDICATION ON 4.16 KV INFEED BREAKER 52-40201.

Time in LCOr.LCO NOT ENTERED Found During: NORMAL OPERATION-

==============================================================

Record #: 06-2 Assembly: BC653 Location: 12- 6-12 S/N 1429 Fail Date: 06/20/87 Work Order Number: 8706190324 System: DRYWELL HVAC Class: NON-1E Description of Failure:

BUFFER INPUT #8 FAILED TO ITS LOW STATE Affect on System FAILURE RESULTED IN SPURIOUS " LOW FLOW" INDICATION AND ALARM ON DRYWELL COOLER FAN H2V212 Time in LCO LCO NOT ENTERED Found During: NORMAL OPERATION

u m======n==================e===================c=====================

l l

l 1

l l 5 1

l l

l 1

i,

Record #: 07-1 Assembly .DC653 Location: 9- 6-13 S/Ni 1465 Fall Date: 07/07/87 Work Order Number: 8707060017 Systems AUX BLDG AND CONTROL AREA CHILLED WTR Class NON-1E Description of Failure:

OUTPUT BUFFER #4 FAILED TO ITS HIGH STATE.

Affect on System:

' FAILURE RESULTED IN FALSE CONTROL AREA CHILLED WATER SYSTEM "OUT OF SERVICE" COMPUTER POINT AND ALARM.

Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERATION au========================================================================

1 1

1 l

l l Record # 07-2 l Assembly: BC652 Location: 5 5 S/N 0666 l

Fail Date: 07/07/87 Work Order Number: 8707060025 i System: DEMIN WTR STORAGE AND TRANSFER Class: 1E Description of Failure:

OUTPUT BUFFER #1 FAILED TO THE HIGH STATE.

Affect on Systems FAILURE RESULTED IN FALSE "OPEN" INDICATION ON REACTOR BLDG SERVICE ISOLATION VALVE 1-AN-HV-2600.

l l

Time in LCO: LCO NOT ENTERED Found During NORMAL OPERATION

u=====================================================================

l Record #: 07-3 Assembly: BC653 Location: 1- 4-11 S/N: 0580 Fail Date: 07/16/87 Work Order Number: 8707130368 Systems SOLID RADWASTE Class: NON-1E Description of Failures L INPUT BUFFER #1 FAILED TO THE LOW STATE.

Affect on System FAILURE RESULTED IN FALSE "INOP" INDICATION AND ALARM ON 480 VOLT TIE DREAKER 52-30033.

Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERATION

==============================================================

Record # 07-4 Assembly: AC653 Location 8- 4-12 S/N: 1314' Fall Date: 07/25/87 Work Orcer Numbers- 8707202211 Systems REACTCR FEED PUMP TURBINE STEAM Class: NON-1E Description of Failure OUTPUT BUFFER #6 OPERATED INTERMITTENTLY.

Affect on System FAILURE RESULTED IN INTERMITTENT "A" REACTOR FEED PUMP TURBINE

. MODE INDICATION.

l Time in LCO: LCO'NOT ENTERED .Found During: NORMAL OPERATION

==============================================================

l l

l l

f I

f l

Record # 07-5 Assembly: AC652 Location: 5- 4-15 S/N 2330' Fail Date: 07/27/87 Work Order Number 8707202229 Systems SERVICE WATER Class: 1E j Description of Failure:

MEMORIES A AND B WOULD NOT SET.

Affect on Systems 1

, FAILURE RESULTED IN FALSE " PROTECTIVE INTERLOCK IN TEST" INDICATION ON THE l l STATION SERVICE WATER SYSTEM STRAINER'AF509. l Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERATION i =======================================================================e--

l \

i l

l b

1 I

l 1

'l' l

l )

i l  !

l Record #: 07-6 l l Assembly: CC652 Location: 8 7 S/N:'2273 <

l. Fail Date: 07/16/87 Work Order Number: 8707130013 l Systems SAFETY AUXILIARIES COOLIN8 SYSTEM. Class: '1E l Description of Failures OUTPUT BUFFER # 5 FAILED TO THE HIGH STATE.

Affect on System FAILURE RESULTED IN FALSE " LOW FLOW" INDICATION ON SACS PUMP CP210.

L i i

l i l

Time in LCO LCO NOT ENTERED Found During NORMAL OPERATION- J

===============e=========================================n====

l

l- 1 e i 1

Record-#3 07-7

! Assembly:. CC652' Location: 1 3 S/N 2051 ' '

l, Fail'Date: 07/31/87 Work Order Number: -870803151 j L' System: 4.16 KV ELEC DISTRIBUTION Class 1E i Description of Failures , ,

l l OUTPUT BUFFER #6 AND #8 FAILED TO THE HIGH STATE, MEMORY B FAILED.) ,

1

' ~

AHect on System FAILURE CAUSED IMPROPER OPERATION OF THE 4.16 KV CIRCUIT l BREAKER 52-4030BJ ,

(' . 1 l

l ,

l  !

l Time in LCOs LCO NOT ENTERED Found Durings NORMAL OPERATION

==============e=======================================================64=r 1 *

.i

( / , , +1 l .

q l

h

'}

c q 1

l l .i k

,' c ,

9 r k

s

\

a

.J N'

S u.

./

9

. ('f a'

-p .(

<!  ! > l

./

l - _. - _ - - _ _ -

~i

Record # 02-3 Assembly .AC652 Location: 1 9- O S/N 2314 Fail Date: 02/10/87 Work Order Number: 8702100011 Systems NUCLEAR BOILER AND REACTOR RECIRC Class: 1E Description of Failures INPUT DUFFER #1 FAILED TO THE HIGH STATE l

Affett on System FAILURE RESULTED IN FALSE "INOP" INDICATION ON REACTOR RECIRC PUMP MOTOR 1BN205.

1 Tima in LCO LCO NOT ENTERED Found During: NORMAL OPERATION

==============:=====================.::=========================

a l

l l

l l

1 I

1

3M 3 3

6 iU N

J 4 Y m iA 3 M 7 R E 7 8 3 iP T A Y

A L R U J

R E G 9

3 iA M

R N I

U D N

L I E A E G

3, B iE F A 4 F R

ME L V A

S G 3.

2 C ,A N

S N I

  • O L

2 L 6 O R

8 4 -

iE C

H 4 "

Y T

  • D E N O

L I M A 2 9

iO V

B 1 4

  • N 5 T 5

iC

  • O 4 P 5 iE
  • S 4

G U

- - - - -- E

- _ A 0 9 8 7 6 5 4 3 2 1 0 1

p co2 5c g >vo2 yF4E $3_d l

Il

j .. .

y g* o d g B;9 0

\

\

hf1 -

,b:Vq, 4

<b $ '

9' _

h.< I w

Yh I

l

)

7 d

- - - _ - - _-_-_ - _-_ _ _ _ _ _ _ - .. ..