Discusses 870807 Telcon Between Bj Youngblood & M Mcintosh Re Per Nuclear Svc Water Sys Design at Plant. Util Requested to Notify Incident Response Ctr within 1 H of Any Situation When One of Four Diesels Out of Svc
ML20237J898
Person / Time
Site: Catawba  
Issue date: 08/11/1987
From: Jabbour K
Office of Nuclear Reactor Regulation
To:
Office of Nuclear Reactor Regulation
References
NUDOCS 8708180398
Download: ML20237J898 (2)


Text

.

m Docket Nos.: ~

50-413 and 50-414 MEMORANDUM FOR:

File

)

FROM:

Kahtan M. Jabbour, Project Manager Project Directorate II-3 Division of Reactor Projects I/II

SUBJECT:

TELECON WITH DUKE POWER COMPANY'S MANAGEMENT REGARDING THE NUCLEAR SERVICE. WATER DESIGN - CATAWBA NUCLEAR STATION, UNITS 1 AND 2 At about 4:30 pm on August 7, 1987, B.J. Youngblood (NRC) called _M. McIntosh (Duke Power Company) to inform him that: (1) the staff has issued a letter dated August 7,1987, pursuant.to.10 CFR'50.54(f), to Duke Power Company regarding the Nuclear Service _ Water System Design at Catawba Units 1 and 2; the staff's concern was related to the application of GDC 5 and 44 and the potential single failure of an NSWS valve; furthermore, the staff'is requesting that Duke provide, within 10 days from the date.of the letter, a justification for continued operation; M. McIntosh was also informed that the letter is being immediately telecopied to Duke; and (2) B.J. Youngblood requested that Duke Power Company notify the NRC Incidence Response Center, within one hour, of any situation when out of the four diesels is out-of service because this occurrence would put the Catawba plant in an analyzed condi tion, i 6\\

q Kahtan N. Jabbour, Project Manager l

Project Directorate 11-3 Division of Reactor Projects I/II-cc:

S. Varga Distribute:

J. Partlow

Docket Filef

' Local' PDR' ' 'y*

G. Lainas*

J. Craig*

NRC PDR J. Smith

  • PD#23 Reading W. LeFave*.

MDuncan D. Hood

  • KJabbour K. Jabbour*

I L. Reyes T. Peebles

.s' l

Present during telecon PDII-DRPI/II PDIL PI/II KJabbour/ rad -

BJYo gblood 08/l)/87 08/l4/87

^*

8708180398 870811 PDR ADOCK 05000413 P

PDR 4

3 5.

/

.)-

i UL

...is _z___ __

J m_i

L gaRt3p

/

'o UNITED STATES

["

k NUCLEAR REGULATORY COMMISSION g

y WASHINGTON, D. C. 20555 AUG 111987 l

Docket Nos.:

50-413 and 50-414 MEMORANDUMFOR:}M$5@

l FROM:

Kahtan M. Jabbour, Project Manager l

l Project Directorate 11-3 Division of Reactor Projects I/II l'

SUBJECT:

TELECON WITH DUKE POWER COMPANY'S MANAGEMENT REGARDING THE NUCLEAR SERVICE WATER DESIGN - CATAWBA NUCLEAR STATION, UNITS 1 AND 2

-l At about 4:30 pm'on August 7, 1987, B.J. Youngblood (NRC) called M. McIntosh (Duke Power Company) to inform him that: (1) the staff has issued a letter dated August 7, 1987, pursuant to 10 CFR 50.54(f), to Duke Power Company regarding the Nuclear Service Water System Design at Catawba Units I and 2; the staff's concern was related to the application of GDC 5 and 44 and the i

i potential single failure of an NSWS valve; furthermore, the staff is l

requesting that Duke provide, within 10 days from the date of the letter, a justification for continued operation; M. McIntosh was also informed that the letter is being immediately telecopied to Duke; and (2) B.J. Youngblood requested that Duke Power Company notify the NRC Incident Response Center, I

within one hour, of any situation when one out of the four diesels is out of i

service because this occurrence would put the Catawba plant in an unanalyzed condition and that it appears they should be in Technical Specification 3.0.3.

'f0la~

1 Kahtan N. Jabbour, Project Manager Project Directorate II-3 Division of Reactor Projects I/II cc:

S. Varga J. Partlow G. Lainas*

J. Craig*

J. Smith

  • W. LeFave*

D. Hood

  • K. Jabbour*

L. Reyes T. Peebles Present during telecon