Special Rept 87-08:on 871112,fire Diesel Pump 1-2 Not Restored to Functional Status within 7 Days.Caused by Constraints Imposed by Increased outage-related Maint Activities.Fire Diesel Pump Restored to Functional Status
ML20237C671
Person / Time
Site: Oyster Creek
Issue date: 12/11/1987
From: Fiedler P
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
87-08, 87-8, NUDOCS 8712220066
Download: ML20237C671 (2)


Text

- _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ __ ___ ._ ._

a s

  • GPU Nuclear Corporation Nuclear  ::::=r388 Forked River, New Jersey 08731-0388 609 971-4000 Writer's Direct Dial Number:

December 11, 1987 Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555

Dear Sir:

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 Special Report 87-08 Fire Diesel Pump 1-2 Enclosed is Special Report 87-08 which is submitted in accordance with Technical Specification 3.12.B.

If any questions or comments should arise, please contact Mr. George Busch, Oyster Creek Licensing Engineer at (609)971-4909.

Very truly yours,

"^& 2 'y Pe iedIe'r Vice President and Director Oyster Creek PBF/GB/dmd (0666A)

Enclosure cc: Mr. William T. Russell, Administrator Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 Mr. Alexander W. Dromerick, Project Manager U.S. Nuclear Regulatory Commission Division of Reactor Projects I/II 7920 Norfolk Avenue, Phillips Bldg.

Bethesda, MD 20014 l

NRC Resident Inspector Oyster Creek Nuclear Generating Station ,

Forked River, NJ 08731 i 1

8712220066 871211 PDR S

ADOCK 05000219 oration is a subsidiary of the General Pubhc Utilities Corporation Y j(

DCD l _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _

,. e 0YSTER CREEK. NUCLEAR GENERATING STATION r Forked River, A'ew Jersey 08731 Fire Diesel Pump 1-2 Special Report 87-08 Report Date December 11, 1987 Occurrence Date November 12, 1987 Identification of Occurrence Non-Functional Fire Diesel Pump 1-2 was not restored to a functional status within seven (7) days as required by Technical Specification 3.12.B.

Description of Occurrence During a functional test, Fire Diesel Pump 1-2 failed to meet the acceptance criteria. The fire diesel failed to start at the required pressure and failed to develop the required discharge pressure after starting.

Analysis of Occurrence The Oyster Creek plant was in a shutdown condition during which required maintenance activities on systems and components were being performed. Upon failing the functional test a work request was submitted to restore Fire Diesel Pump 1-2 to a functional status within seven (7) days. Due to the constraints imposed by increased outage related maintenance activities of a higher priority it was not possible to accomplish these repairs within the seven (7) days as specified. Since Fire Diesel Pump 1-1 was functional and the plant was in a shutdown condition the safety significance of this event was minimal.

Corrective Action Fire Diesel Pump 1-2 was restored to a functional status on November 14, 1987.

This was accomplished by recalibrating the pressure switch that initiates the automatic start function of the fire diesel pump and by rebuilding the fire diesel pump relief / control valve. The valve seat was degraded which prevented the development of proper discharge pressure.