PRELIMINARY NOTIFICATION

-4

/

Fsbru p p 8, 1977 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-77-25

(

This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance. The information

. presented is as initially received with6ut verifica. tion or evaluation and is basically all that is known by IE staff on this date.

Facility: Peach Bottom Unit No. 3 (DN 50-278)

Subject:

CORE SPRAY LINE CRACK INDICATIONS During this refueling outage inservice inspections have identified the

~ following pipe cracks in the primary coolant boundary. These cracks have caused a delay in the scheduled date for plant startup from February

- 23 to March 5,1977:

" - ~

1.

One crack on the "A" core spray line to 5/8 inches long and

.070 inches deep - 10% of wall thickness.

(PNO-77-13) 2.

.One crack on the "B" core spray line 7/8 inches long and.025 inches deep - 5% of wall thickness.

3.

One crack on the "B" Recirculatory Loop four-inch bypass line h to 3/4 inches long and.015 inches deep - 10% of wall thickness.

s._

The four-inch bypass line has been, repaired by replacement of

(

a 12-inch section of line.

Media interest is not expected. The Commonwealth of Pennsylvania has been informed. A press release is not planned.

NRC, Region I, (Philadelphia) received notification of the latest status on these occurrences by telephone from the Philadelphia Electric Inservice 4'

! nspection Coordinator at 10:00 a.m., February 8, 1977. NRC inspectors

/'

I have also been on site following investigations and repairs.

Contact:

FADreher, IE x27261 GWRoy, IE x27261 DThompson, IE x27541 d

Distribution:

Chairman Rowden Commissioner Kennedy S. J. Chilk, SE'CY Commissioner Gilinsky C. C. Kammerer, CA G. F. Murphy, JCAE O

L. V. Gossick, EDO K. R. Chapman, NMSS R. G. Ryan, OSP k

S. H. Hanauer, EDO E. Volgenau, OIE J. A. Harris, PA B. C. Rdiche, NRR H. K. Shapar, ELD T. J. McTiernan, OIA

- H St. /.'3d ; MN33/.') C, ;

Transmitted: PBldg/.'##;

Luge l

I (m __

PRELIMI Z Y NOTIFICATICM f

/

w 9807130035 770200 J