Special Rept 87-06:on 870928-30,fire Barrier Penetration Seals Identified as Not Meeting Acceptance Criteria.Cause Not Stated.Fire Watch Established Immediately.Fire Barrier Seals Will Be Restored to Functional Status by 871030
ML20236L371
Person / Time
Site: Oyster Creek
Issue date: 10/29/1987
From: Fiedler P
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8711100292
Download: ML20236L371 (2)


Text

.. -

4 GPU Nuclear Corporation Nuclear

==:;388

- Forked River, New Jersey 08731-0388 609 971-4000 3

Writer's Difect Dial Number:

October 29, 1987 Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555

Dear Sir:

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 l

Special Report 87-06 Non-Functional Fire Barrier Penetrations Enclosed is Special Report 87-06 which is submitted in accordance with Technical Specification 6.9.3.

If any questions or comments should arise, please' contact Mr. George Busch, Oyster Creek Licensing Engineer at (609)971-4909.

Very truly yours, 1

W

-A A

tof M r wa rer - - &

L Vice President and Director

}

Oyster Creek 1

PBF/GB/dmd (0666A)

Enclosure cc: Mr. William T. Russell, Administrator 1

Region I U.S. Nuclear Regulatory Commission l

631 Park Avenue King of Prussia, PA 19406 Mr. Alexander W. Dromerick, Project Manager U.S. Nuclear Regulatory Commission Division of Reactor Projects I/II 7920 Norfolk Avenue, Phillips Bldg.

Bethesda, MD 20014 NRC Resident Inspector Oyster Creek Nuclear Generating Station h<

Forked River, NJ 08731-3~

8711100292 871029 PDR ADOCK 05000219

\\

S PDR-

.\\

GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation

/-

b 0YSTER CREEK NUCLEAR GENERATING STATION l

Forked River, New Jersey 08731 Special. Report 87-06 ~

Report Date October-29, 1987 l

Occurrence Date

'i September 28-30, 1987 i

Identification of Occurrence Non-functional fire barrier penetrations 'were not repaired within seven (7) days i

)

as required by Technical Specification 3.12.E.

q

'l l

Description of Occurrence l

During routine surveillance of fire-barrier penetration seals, four (4)

)

penetrations were identified as not meeting the' acceptance criteria.. These j

seals-were declared non-functional due to missing or degraded sealant material.

J within the penetration.

Analysis of Occurrence The Oyster Creek plant is currently in' a shutdown condition during which.

required maintenance on systems and components is being performed.

Upon discovering the non-functional fire barrier seals, repair. work was scheduled within the existing maintenance schedule for overall plant' maintenance.. 'Since degraded fire seals are required to assure the plant capability.to shutdown, the' work was scheduled such that repairs would be accomplished prior to plant startup within the normal constraints imposed by increased maintenance activities.

Therefore, it was not possible to accomplish these repairs within; the seven (7) days as specified. 'Since the required fire watches had been-established and the plant was in a shutdown condition, the ~ safety -significance -

of this event is minimal.

Corrective Action Upon discovering the non-functional fire seals, within one hour, a fire watch was established in accordance with the Technical Specification.

The l

non-functional fire barrier seals will be restored to a functional. status by -

E October 30, 1987.

l.

_ _ _ _ _ _ _ _ _. _ _. _ - _. _ - _