1

)

6

[q I

Florida

{

Power i

CORPORATION l

March 17, 1989 l

3F0389-15

)

Document. Control Desk U.

S.

Nuclear Regulatory Commission i

Washington, D.C.

20555 l

Subject:

Crystal River Unit 3 Docket No. 50-302 Operating License No. DPR-72 l

NUREG 0737,. Supplement 1 l

Detailed Control Room Design Review (DCRDR)

Dear Sir:

t t

Florida Power Corporation (FPC) is submitting this letter to correct response number 4 in our letter dated October 18, 1988.

FPC performed a review of all indicating lights on the main control board which are normally off.

Eight safety-related indicating lights with single filament bulbs without test capability and normally off were found.

We stated that these indicating lights also had associated annunciator j

points.

FPC has subsequently identified that two of the eight indicating lights do not have associated annunciator points; namely Diesel Generator A Parallel Block and Diesel Generator B Parallel Block indicating lights.

The tabulation of lights versus associated annunciator description is as follows:

Indicatina Licht Annunciator Description DG A Block Close Actuated-3205 4KV ESA Cross - Tio Blocked

)

(Window SSF-A2-3-4)

N DG A Block Close Actuated-3207 l

800 y@a DG A Block Close Actuated-3211

\\

0 So DG B Block Close Actuated-3206 4KV ESB Cross - Tie Blocked gg (Window SSF-A2-7-4) i.

Os o o8 DG B Block Close Actuated-3208 l

@Gg DG B Block Close Actuated-3212 P@}

oc

  • 11 DG A Parallel Block None DG B-Parallel Block None

. GENERAL OFFICE: 3201 Thirty fourth Street South a

P.O. Box 14042

  • St. Petersburg, Florida 33733 (813) 866 5151 A Florida Progress Company

]

l g.

~ March.17,.1989-l

3F0389-15 l

Page 2

'l l

.)

I

^

In f order..'to correct this deficiency FPC plans to add' two indicating lights, one for Diesel Generator A Parallel Allowed and one'for Diesel Generator B Parallel Allowed.

The Parallel' Block.or Parallel-Allowed indicating. light for each Diesel Generator.would remain lit'at all'-

times.

The schedule'for the' installation.'of.these'two new lights is Refuel-7.

Should there be any questions, please contact this office.

Sincerely, q

l l

Rolf C. Widell, Director Nuclear Operations Site Support l

RCW/EMG/sdr-

)

i xc:

Region Administrator, Region II Senior Resident Inspector l

l

_ _ = _ - - _ _ -.

_ _ - - -