Proposed Tech Spec Page 3/4 7-22,changing Snubber Visual Insp Interval Until Sept 1989
ML20235U903
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/27/1989
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20235U896 List:
References
NUDOCS 8903090425
Download: ML20235U903 (1)


Text

-__

b' es 7

PLANT SYSTEMS 1

3/4.7.8 HYORAULIC SHOCK SUPPRESSORS (SNUBBERS)

LIMITING CONDITION FOR OPERATION

)

d 3.7.8 All snubbers shall be OPERABLE.

The only snubbers excluded from this requirement are those installed on nonsafety-related. systems and then only if their failure or failure of the system on which they are installed, would have no adverse effect on any safety-related system.

APPLICABILITY:

MODES 1, 2, 3 and 4.

MODES 5 and 6 for snubbers located

)

on systems required 0PERABLE in those MODES.

3 ACTION:

With one or more applicable snubbers inoperable,'within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> replace.

or restore the inoperable snubber (s) to OPERABLE status and perform an engineering evaluation per Specification 4.7.8.f on the attached component, or declare the attached system inoperable and follow the appropriate ACTION statement for that system.

SURVEILLANCE REQUIREMENTS 4.7.8 Each applicable snubber shall be demonstrated OPERABLE.by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.

a.

Inspection Types As used in this specification, type of snubber shall mean snubbers of the same design and manufacturer, irrespective of capacity.

Snubbers are categorized as inaccessible or accessible during reactor operation.

b.

Visual Inspections Visual inspections shall be performed in accordance with the following schedule:

No. Inoperable Snubbers Subsequent Visual per Inspection Period Inspection Period 0

18 months i 25%

1 12 month 1 25%*

2 6 months i 25%

3, 4 124 days i 25%

5,6,7 62 days i 25%

8 or more 31 days i 25%

The snubbers may be categorized into groups based on type and accessibility.

Each group may be inspected independently in accordance with the above schedule.

  • For inaccessible snubbers, the inspection due April 27, 1989, (12 months 125% from April 27, 1988) may be extended until the 1989 refueling outage.

ARKANSAS - UNIT 2 3/4 7-22 Amendment No. 72 P