0-CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS 4.6.3.1: Each. primary containment' isolation valve-specified in Table 3.6.3-1 shall be demonstrated OPERABLE prior to returning the valve to service after maintenance, repair, or replacement work is performed'on the valve or its associated actuator, control, or power circuit by performance of the cycling test and' verification of isolation time.
4.6.3.2 Each-isolation valve'specified in Table 3.6.3-1 shall be demonstrated L
OPERABLE'at least once per 18 months by verifying that on a containment l
isolation test signal each isolation valve actuates to its isolation position.
. 4.6.3.3 The isolation time of each power-operated or automatic valve specified in Table 3.6.3-1 shall be determined to be within its limit when-tested pursuant to Specification 4.0.5.
4.6.3.4 Each reactor instrumentation system isolation valve shall be i
demonstrated OPERABLE at least once per 18 months by cycling each valve through'at least one complete cycle of full travel.*
r.
- The end of the current surveillance period for the surveillance requirements below may be extended beyond the time limit specified by Technical Specification 4.0.2a.
After November 2, 1984, the plant shall not be operated in. Operational Conditions 1, 2, or 3 until the surveillance requirements listed below have been completed. Upon accomplishment of the surveillance, the provisions of Technical Specification 4.0.2a shall apply.
Technical Specification 4.6.3.4; as applicable to excess flow check valves B21-F047C, B21-F047D, B21-F049C, and B21-F049D.
BRUNSWICK - UNIT 1 3/4 6-13 Amendment No.