Proposed Tech Specs,Removing Table 3.8-1, Containment Penetration Conductor Overcurrent Protective Device (Cpcop) & Controlling List of Cpcop Through Appropriate Plant Procedure
ML20235P878
Person / Time
Site: Wolf Creek 
Issue date: 07/08/1987
From:
WOLF CREEK NUCLEAR OPERATING CORP.
To:
Shared Package
ML20235P821 List:
References
NUDOCS 8707200656
Download: ML20235P878 (34)


Text

.

1 4

l ATTAONFRf I l

PROPOSED TECFINICAL SPECIFICATION Om I

1 8707DOO656 070/00 PDR ADDCK 0509049p PDR l

w-_________________-__-____________-__-__

. ~ to WM 87-0171 Page 1.of 31

- July 8,1987 ELECTRICAL POWER SYSTEMS 3/4.8.4 ELECTRICAL EOUIPMENT PROTECTIVE DEVICES l

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

LIMITING CONDITION FOR' OPERATION 4

3.8.4.1

"' ---"*----* ----+ -+#^- ---""c+--

^"---"----* ---+-~ 4"-

giver

  1. - T:ble 3.E-1 th:!' 5: C P E'" S LE.

INSERT A APPLICABILITY: MODES 1, 2, 3, and 4.

ACTION:

i With one or more of the above required containment penetration conductor overcurrent protective device (s) inoperable:

j Restore the protective device (s) to OPERABLE status or deenergi:e a.

the circuit (s) by tripping the associated backup circuit breaker or racking out or removing the inoperable circuit breaker within f

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, declare the affected system or component inoperable, l'

and verify the backup circuit breaker to be tripped or the inoperaole circuit breaker racked out, or remeved, at least once per 7 days thereafter; the provisions of Specification 3.0.4 are not ac 'icable

/

to overcurrent devices in circuits which have their backup circuit-breakers tripped, their inoperable circuit breakers racked out, or removed, or b.

Be in at least HOT STANCBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> ano in CCLO SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.4.1 m

-- tain e-t re~t-:e

ene;;ter ever:gr e-t :?:n-te.e

<re:_

gN:

s-i-hbi; 3.B-1 :h:!' t:

o d:

r,:tr:::: :r:,A n,

(

a.

At least once per 18 months:

1)

By verifying that the 13.8 kV circuit breakers are OPERABLE by selecting, on a rotating basis, at least 10.*.' of the circuit breakers, and performing the following:

a)

A CHANNEL CALIBRATION cf the associated prctective relays, b)

An integrated system functional test which incluces simulate:

autcmatic actuation of the system anc verifyihg ;na*. ea:n relay and associated circuit breakers anc~c0ntroi :ircui'.s C

function as designed and as specifiec in T3::le 3,3-1, 2nc l

WOLF CREEK - UNIT 1 3/4 S-M

)

i I

m_______._____________----------

- - - - - - - - - - - - - - - - - - - - - - - - ~ - - -

~

_____________-------_--J

_ Attachment 1 to' WM 87-0171 Page 2'of 31 July 8, 1987..

ELECTRfCAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) c)

For each circuit breaker found inoperable during these functional tests, an additional representative sample of at least 10% of all the circuit breakers of the inoperable type shall.also be functionally tested until no more failures are found or all circuit breakers.of-that type have been functionally tested.

'2)

.By selecting and functionally testing a representative sample of at least 30% of each type of lower voltage circuit breakers.

Circuit breakers selected for. functional testing shall be selected on a. rotating basis.

Testing of these circuit breakers shall consist of injecting a current in excess of the breakers nominal-Setpoint and measuring the response time.

The measured response tirae will be compared to the manufacturer's data to ensure that it is less than or equal to a value specified by the manufacturer.

Circuit breakers found inoperable curing functional testing shall be restored to OPERABLE status prior to resuming ope; ation.

For each circuit breaker found inoperable curing these functional tests, an additional representative sample of at least 10% of all the circuit breakers of the inoperable type shall also be functionally tested until no more failures are g

found or all circuit breakers of that type have been functionally q

tested.

k b.

At least once per 60 months by subjecting each. circuit breaker to an intpection and preventive maintenance in accordance with procedures prepared in conjunction with its manufacturer's recommendations.

i 1

enmen'No.

5 o

/

Att'achment I to WM 87-0171 ly 8,1987 TABLE 3.8-1 p'

CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVIC 5

(

PROT TIVE DEVICE g

POWERED NUMBER VND LOCATION EOUIPMENT

{

13.8-kVShitchcear P-252PA0107 Reactor Coolant Pum-B-252PA0110/25 A0101 OPBB01A P-252PA0108 B-252PA0110/252PA01 Reactor Coolant Pump 0P8801B P-252PA0205 B-252PA0211/252PA0202 Reactor Coo ant Pump DPSB01C P-252PA0204 B-252PA0211/252PA0202 Reactor Coolant Pump OPBB0 480-V Load Center P-125A Fuse at GS01A B-52NG0304 ydrogen Recombiner SGS01A P-125A Fuse at G501B 8-52NG0404 drogen Recombiner 5 018 P-52PG2102 Through 52PG2111 Press rizer Backup Heater B-250 A Fuse P-52PG2202 Pressurizer ackup Through 52PG2211 B-250 A Fuse Heaters l

P-52NG01TAF1 B-52NG0108 Containment-Coole 05GN01A P-52NG03TAFl B-52NG0305 Containment Cooler 05GN01C P-52NG02TAF B-52NG0208 Containment Cooler 05GN01B P-52NG04 AF1 B-52NGr,05 Contair. ment Cooler CSGN010 P-5^ G2007 FG2CP M :

i 5 '.'PG2001 h=JL 1

e.z :R554 car ;

3z s.;s 1

j

Attachment I to WM 87-0171 Page 4 of 31 July 8,1987

/

/

/

1 E'E 2.E-1 (Continued)

,/

/

.,.,... t.., T -.. t - -. -, c.,,

c.r...,,---

,i-2 r :i %i m

/

/

r o..r :.i.r. p. : NT P Rn. 'i ;r. ~.t Vt' n : V.i e. ".

t f

: /. :.-. 3.: a:.*.:

POW R:D

....*~..a

. e a.aI *=.,.e.

n, -

s, s

-..r}pt.*:".sT c Ce-ter :: ntinuedl

_-EIP0:40:

EEC2 Pressuri:er Heat.

e ruse

- : J u.,

t - 0, c:

.-5::::: 3 3t E Pressuri:er estar E-50:a Fuse at Et".

P-5203:404 at EE02 Pressuri er Heater E-500A Fuse at EE01

-E:PG::C5 at EEG2 Pre turi:er Hea er E-EO:i; Fuse at EE01 P-52PG24:5 at EEC2 Pressuri:er Heater E-500A Fuse at EE01 P-50 G2:07 at 6E02 Pressuri:er Heater E-500A Fuse at EE01 JSO-V 40t:- Control Center P:2N301EDF3 E-40A Fuse RHR Locp Inlet Iso Viv EJHVE7012 l

/

-5 f.30 EHR2

/

E ' from Ctet Air E-15A Fuse

/

f Coo rs Iso Viv EFHV46 P-52NG02EDF2

/

CCW to tmt Iso Viv E-30A ruse

/

EGHV60

/

P-52NG01EHF3

/

E-40A Fuse CCW Contain ent Isolation Valve f

EGHV132 P-50NG01EDF1 2-15A Fuse PRT to Containme-t Valve E5HV8037A F-E 2N301EER3 E-30A Fuse' Pressurizer Relief V ve BEHV8000A

/

" 52E2!I EF5 E-: Cf r Reactor Coolant Drain Tan Pumo use i

DPHE02A

?- EIDG'. 9N C R3 E/150A 'use at PG19NCR4 Lighting Transformer XQA26

/

/

/

y, * '

U

?*4 6

i4 4

s/M C. 7 0,

/

/

/'

Attachment I to WM 87-0171 Page 5 of 31 July 8, 1987 N

' 7

\\

N

/

\\

/

i

\\

,e TABLE 3.8-1 (Continued) x

/

\\

/

N CONTAINMENT PENETRATION CONDUCTOR N

OVERCURRENT PROTECTIVE DEVICES N

PROTECTIVE DEVICE NUMBER AND LOCATION POWERED EOUIPMENT

/

480-V Moto scontrol Center (Continued)

/

P-52PG19NCR5N MachineRmExhbustFan

/

B-15A Fuse

'N OCGN04

/

P-5A Fuse - Total o'f 4 Fuses FluxMappIngMotorStarters x

B-52PG19GCF3

\\

SR05A,/

's i

P-5A Fuse - Total of 4 Fhses

/

Fiux Napping Motor Starters B-52PG19GDF5

\\

SROSB j

\\

/

P-52NG03CLF2

\\

RCP thermal barrier B-15A Fuse

'N f

f eturn isolation Vlv EEHV15 P-52NG01BHF4

/

x

/

1 B-40A Fuse CCW Containment Isolation Valve

)

/

EGHV130

/

P-52NG02SBFa B-250A Fuse Hydrogen Mixing Fan DCGN038 P-52NG02BCF3 H

N ydrogen Mixing Fan S-250A Fuse llCGN03D P-52NG01EBF4 B-250A Fuse Hydeggen Mixing Fan DCGN0*A P-52NG01BCF3 l

B-250A Fuse Hydrogen '4ixing Fan DCGNO3C P-52NG02BJF5 B-150A Fuse CRDM Cooling an DCGN013 P-52PG20 GAR 2 B-150A Fuse CRDM Cooling Fan OCGN01A P-52PG20NFR3 E-15A Fuse Pressurizer Cooling F3.

DCGN05 P-52PG20'tF5 Reactor Coolant B-100A use Drain Tank Pumo 2PHE023 P-5' G2CNEF1 E ' 0A Fuse at PG20:,Fil Ligntinq Trans f cr :er XOA2S

,e l

WCLF CRE5s - n!T '

3/4 S-20

1 Attachment I to WM 87-0171 Page 6 of 31 July 8, 1987 TAELE 3.E-1 (Continued)

NTAINMENT PENETRATION CONDUCTOR CVERCURRENT PROTECTIVE DEVICES
~E ~

P0k!ERED

'O L3 CATION EOUIPMENT htCentrolCenter(Centinued)

JED 5 "O

F-52N302EJF1 Standby Lightin i

E-20A Fuse

-52N3C2EJF2 Stancey Li.iting E-40A Fuse.
-52N002EHR3 PRT to ontainment Viv E-15A Fuse BBFVo 37B P-52NG02SDF1 Pr ssurizer Relief Valve 3-30A Fuse "aHV80003
-52N3DIEJF5 CRDM Cooling Fan 5-150A Fuse at NG01BKF3 DCGN01D P-52001EGER2 CRDM Cooling Fan B-150A Fuse at PG19GFR1 DCGN01C P-52NG02BDF3 Ctmt Iso Viv Ret from B-15A Fuse Thrm Barrier Cooling Coil EGHV62 P-52N302EEF2 S p to RHR Pump B-50A Fuse Viv CJHV8SilB P-52NGD2BEF3 Ctmt R irc Sump B-15A Fuse Iso Viv NHV7 P-52NG02BGF3 Accumulator 'so Viv B-60A Fuse EPHV88088 P-E2NG02BHF2 Accumulator Iso 'I v B-60A Fuse EPHV8808D P-52NGG2BFF H Control System 2

E-15A Fus Make up Air Viv KAHV30 P-52NG ABEF3 RC Pump Seal Water E-15' Fuse Iso Viv BGHV8112 P-2N301EFF3 Sump to RHR Pump j

~ 60A Fuse Viv EJHV8811A I

W3L ::,EEK - UNIT I 3/4 S-21 i

i a

1 At'tachment I to Wii 87-0171 Page 7 of 31 July 8, 1987

\\

I 1

_ TABLE 3.8-1 (Centinued's I

CONTAINMENT PENETRATION CCNDUCTCR I

OVERCURRENT PROTECTIVE CEVICES PR ECTIVE DEVICE NUMS R AND LOCATION POWERED EQUIPMENT l

480-V M +cr Control Center (Continued) 1 P-52NG01E B-15A Fuse Ctmt Recirc S'..p Iso Viv ENHV P-52NG01BGF3 B-60A Fuse Accumulat r Iso Vlv EPHVSS0c P-52dG01BGF2

\\

Accum lator Iso Viv B-5CA Fuse

\\

EPH" SOSC

\\

P-52NG01BFF2 mt Air to Aux Bldg B-1:iA Fuse

.3F Filter Iso Viv G5HV20 i

\\

P-52NG01EER2.

N 8-15A Fuse React Bldg Disenarce

\\

Iso Viv LFFV95 N

P-52NG02EEF3 N

B-40A Fuse RHR Loco Inlet Iso Viv ESPV87029

\\

P-52NG02BCF2 1

E-40A Fuse

\\

RHR Leco Inle i

i Iso Viv ESPV3702A N

P-52NG02EHF3 S-ISA Fuse

\\ES., ;o Ctat Air 1

C olers 15: Viv EFHV34 Q

P-52NG01BCF2 B-15A Fuse ES o Ctmt Air Coole' Iso Viv EF"V32 P-52NG01EDF2 B-15A Fuse ESW from "tmt Air Coolers is Viv E.:HV25 P-52NG01EEF2 B-4CA Fuse RHR Loco Inle Iso Vb EJHV8701A P-52NG02COF*

B-15A Fuse RCP Thermal Earr:e CCW !so Valve EEhVI.

P-52NGO'.HF1 RCP The

.1! E2 ~: e -

.:n. -use

,s.. i ::-.,,

i s

u. <,

P-5'-Gl?NAF E.50A Fuse Rea:::- C2,

n 2 C;.'..'J A

~23[i':C3

'.::: :: c :y: j.:.

c u-

.:e

jstem _. _.

\\

..: _ : :R5:s 3f: E:

/

]

At'tachment I to WM 87-0171 Page 8 of 31 July 8, 1987 TAELE 3.5-1 f:cr.tir.uec)

CNTAIN"ENT PENETRATION CCNDU TOR OVERCUERENT PDOTECTIVE DEVICE 5 1

l

-s_

..v:

.....r_,,1-.

P a,....t 3

<. t r

.. e. _:: :,n.. :. e. y

n.g pqgy; J.: : -.'
  • b t. r Control : enter (Cortinued)

P-52FG1ENGF2 RCP A Space Hester E-;D Fuse

-52DG19NGF3 RCP E Space H ater E ~0 Fuse D-52PG19NEF1 RCP A Oil Lift Pump E-::A Fuse i

?-52?G1 ENGR 3 RCP : Oil Lift Pumo E-40A Fuse P-52PG19NFFI

' mt Normal Sumo 5-15A Fuse Pump DPLF05A P-52PG19NFF2 Ct=t Normal Sump E-15A Fuse Pump DPLF05C D-52PG19NAF2 Instrument Tunnel E-25A Fuse Sump Pumo DPLF07A P-52NG03CEF4

,CP Thermal Barrier CCW 2-15A Fuse I o V1v BSHV15' P-52PG20NCR3 Reac r Cavity Cooling B-150A Fuse Fan Oc NO2B 4

P-E2PG20NFF4 1

Ctmt Atmo pheric Control l

E-60A Fuse System Fan CGR01B j

P-52PG20NSF1 RCP C Space H ter B-40A Fuse P-52PG20NCF1 RCP D Space Heater E-40A Fuse P-52PG20NF' RCP C Oil Lift Pump B-40A Fu a I

1EFROC-P-3A Fuse Accumulator Tank A Isol Viv RF12 E-3A Fuse EPHV8808A 1 DOED P-3A Fuse Accumulator Tank C Isol Viv

.P129 E-3A Fuse EPHVSSOSC l

l l

l l

WDLF CF,EEK - UNIT 1 3/4 6-23 l

N, N

Attachment I to WM 87-0171 Page 9 of 31 July 8, 1987 TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PR0i CTIVE DEVICE POWERED NUMBE. AND LOCATION EOUIPMENT 480-VMohqrControlCenter(Continued) 4EPR08A P Fuse Accumulator Ta B Isol Viv RP140 B-3A se EPHV8S088 1

4EPR088 P-3A Fus Accumulato Tank D Isol V1v RP140 B-3A Fuse EPHV8808D 1EPK09B P-3A Fuse RLO18 B-3A Fuse Accumu ator Tank B Vent Viv EPHV 508 IEPK090 P-3A Fuse RLO18 B-3A Fuse Ac umulator Tank C Vent V1v HV89500 1EPK09F P-3A Fuse Accumulator Tank 0 Vent viv RL018 B-3A Fuse EPHVS950F 4EPK09A P-3A Fuse RLO18 B-3A Fuse Accumulator Tank A Vent v1v f

EPHV8950A

\\-

4EPK09C P-3A Fuse Accumulator Tank E Vent.is RLO18 B-3A Fuse EPHVS950C 4EPK09E P-3A Fuse RLO18 B-3A Fuse cumulator Tank C Vent.:/

Er V8950E P-52PG20NFF2 B-40A Fuse RCP O il Lift Pur.o P-52PG20NER2 B-15A Fuse Ctmt Norma Sump Pump DPLF05 P-52PG20NGFJ B-15A Fuse Ctmt Normal Sc..

Pumo OPLF05D P-52PG20NOR2 S-25A Fuse Instrument Tunnel Sump Pump DPLF075 P-52PG190*

5-600A F se Polar Crane HKE13 CRCM Control Red Drive Power P 10A Fuse

-30A Fuse Gripper Cci s (104 fusea

(**

circuits) k

'a0LF CREEK - UNIT '.

3/4 3-24 1

\\

Attachment I to WM 87-0171 age 10 of M

'N July 8,1987 s

\\

TABLE 3.E-1 (Continued)

N CONTAINMENT PENETRATION C0t:DUCTCR

\\

N

\\

JVERCURRENT PROTECTIVE DEVICEE

\\(CTE:T:".E DEVICE POWERED 6'E E D l'!: LCCATION ECUIPMENT N

ED:'.\\ c, ol Red Drive Power (Continued)

C F-EDA F e 5-150A Fu'te Lif t Coils (52 f sed circuits)

_ Low ic' tace. wer and Control 5ES3C2AP-2AFu\\

RCP Oil

'ft PG19NEF1 B-1A Fu Pump Co rol 4GTK023 P-3A Fuse Cont Mini Purge Isel Ca per RL:20 3-3A Fuse GTH'11 437C3D P-3A Fuse cont. Purge Isol Camper RLC^0 E-3A. Fuse.

GTHZ8 5EEA01A P-15A Fuse RCP Breaker PA0107 B-15A Fuse Control 5EEA01B P-15A Fuse RCP Breaker PA0105 5-15A Fuse Control EEEADIC P-15A Fuse RCP Breaker FA0205 E-15A Fuse Control 4

6ESA01D P-15A Fuse CP Breaker FA020A B-15A Fuse C \\ ol tr 6HBK0AB P-3A Fuse RCDT HB115 B-3A Fuse eat Exchanger return to RCDT Viv HBHV71 4 1

6HBK05A F-3A Fuse 1

HS115 B-3A Fuse

_RCDT Disc arge Viv HBHV7143 1HEK19A P-3A F e

Containment Is lation Viv RLO21 B-3A use HBHV7176 4KAGDaA P-A Fuse Hydrogen Purge Make'o Air N302BFF3

'-1A Fuse Supply Viv KAHV30 5*:C:'.5 P-3A Fuse l

<C2 4A 5-3A Fuse Fire Protection Discharce

'1 v KCXV261 r,C01ES P-3A Fuse C274A E-3A Fuse Fire Protection Distnarge Viv KCXV262

  • 0LF CREEK - UNIT I 3/4 8-25

1

\\.

Attachment I to WM 87-0171 Page 11 of 31

{

\\

July 8, 1987

(

I

\\

i

{

s TABLE 3.8-1 (Continuec)

)

l CONTAINMENT PENETRATION CONDUCTCR OVERCURRENT PROTECTIVE DEVICES PROTECTIVE DEVICE NUMBER AND LOCATION POWERED EQUIPMENT LowVolta\\

ceNPower and Control (Continued)

SKCQ19X P-3A se Fire Protection tector KC274A 8-3A Ful KCHPS261-002 6KC019Y P-3A Fuse Fire Protectjon Detector KC274A B-3A Fuse KCHPS262-002 Fuel Tra /

6KE501A P-5A Fuse sfer Panel KE124 B-ISA Fuse KE124 6KE501A P-5A Fuse Fuel Transfer Panel KE125 B-15A Fuse KEld5 SLFG06A P-2A Fuse PG19NFF1 B-1A fuse ontainment Normal Sumo :. o A OPLF05A SLFG06C P-2A Fuse PG19NFF2 8-1A Fuse Containment Normai 5 o ;uro C OPLF05C 6LFG06B P-2A Fuse PG20NER2 B-1A Fuse Containment Normal 5urs :

i CPLFC58 6LFG060 P-2A Fuse PG20NGF4 6-1A Fuse Co.tainment Normal 5 ro :_:o :

DPLr'50 SGNG03A P-5A Fuse NG01BJF5 B-3A Fuse CRCM Co ling Fan D Dis: se;E Isolatio. Damoer GNHZ44 SGNG03C P-EA Fuse PG19GBR2 6-3A Fuse CROM Cooling nC Discharge Isola ion 23 :e-CNHZ43 1EMK048 P-3A Fus SIS Test Lir.e V!.

RLO17 S-3A Fu e EMHv8224 1EMK040 P-3A ruse SIS Test Line viv RLO17 B 's Fuse EMH71521 lEMK04C -2A Fuse EIT Test Line '.'.

RLD17 B-3A Fuse EMHVE243 JEMF>4E P-2A Fuse SI Test.i e.'

RL-7 3-3A Fuse f.HVI2 71 g

/

^

WCL: CREE ; - LNIT 1 3/4 2-25 I

Attachment I to WM 87-0171 P ge 12 of 31 July 8, 1987 TLELE 3. 5-1 (:entinuec)

C.n,....,.,...,,, -

.,,tirmi.v.

..,,,r---

  1. m

...a:

a u.

.,...r DVERCUR:ENTROTECTIVE DEVICES 1.,-:

rm.

v n n. n.-.,
r:L

,....c..., -. n. -, r..,

i. a i

t.v.-.,,,,e,..,,-

.n i

L :.. '. n i, : e : e r. + - cn: Control (Continuec)

EE"K0EA P.' Fuse SI Test Line Viv RLD17 E-3A Fuse EMHVSSS9A EE!XO50 ;-3A Fu e Si Test Line iv RLC17 E-3A Fus EMHVEES9C EEMK05'E P-3A Fuse BIT Test ine Viv RLC17 S-3A Fuse EMHVEEE2 I

/

6Eur,933 p-3A Fuse SI st Line V1v R.017 E-3A Fuse EMS BES9D EEMKCED P-3A Fuse I Test Line Viv RLO17 E-3A Fuse EMHVSS895 1ENGC2A P-2A Fuse Containment Spray Sumo Isoi ' liv N201EEF3 E-1A Fuse ENHV1 LENGC2E P-2A Fuse f4G02EEF3 E-1A Fuse Containment Soray Sump Isol Viv ENHV7 i

l 1EPGD2A P-2A Fuse N30155F3 E-1A Fuse Accumulator Tank Isolation vahe HVSSOSA 1EPG025 P-2A Fuse NG01EGF2 E-1A Fuse Act T.ulator Tank Isolation Valve

{

EPHV OSC i

1EPK02C P-3A Fuse Accumula or Tank Isolation Valve RLO1E S-3A Fuse EPHV88088 ndication 1EMK04A P-3A Fuse i

SI Test Line lv RLO17 B-3A Fuse EMHV8823 4EJG04E P-2A 'use N202AFR3 E-l' Fuse RHR to charging /S pump suctions EJHV8804B IEJGC5A P 2A Fuse NGC1EEF2 -1A Fuse RHR Shutdown Suction L e Isol Valve EJHVS701A 1EJG :B P-2A Fuse N3".SDC3 E-1A Fuse RHR Shutdown Suction Line Iso ation Valve

\\\\

EJHV87018

(

<!C L : REEK - UNIT 1 3/4 E-27

.)

Attachment I to WM 87-0171 Page 13 of 31 1

July 8, 1987

{

i

{

TABLE 3.8-1(Continued}

l i

. CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PROTEC 'VE DEVICE NUMBER AND LOCATION POWERED E0UIPMENT

_Lcw Voltac ower and Control (Continued) 1EJG06A P-2A se NG01BFF3 B-1A Fu Cont Recirc Sump 'solatien Valve EJHV8811A 4EJG068 P-3A Fuse NG02BEF2 B-2A Fuse Cont Recirc 5 mp Isolation Valve EJHVSS113 1EJK07A P-3A Fuse RLO17 B-3A Fuse Test Line Isol Viv Hot Leg [nj k

Line 50 noid EJHCVS^t5 1EJK07C P-3A Fuse RL017 B-3A Fuse RHR est Line Vlv EJ' V3S90A

{

4EJK07B P-3A Fuse RLO17 B-3A Fuse

.HR Test Line Viv EJHCVB890B l

P-1EJY13A 3A Fuse RLO11 Ctmt Sump Sample Isolation.!/

B-1RLYO1G 15A Breaker EJHV21 NG01ACR119 P-4EJY13B 3A Fuse

}

\\

RLO11 Ctat ump Sample Isolation k

B-4RLYO1G 15A Breaker EJHV2&

..v NG02ACR140 l

P-4BMY01D 3A Fuse

\\

RLO24 S.G.C Cnt to Nuc Sample 5 5 3

I v 6-4RLYO1H 15A Breaker BMHV22 NG02ACR127 P-4BMYO2A 3A Fuse RLO24 S.G. A Tube Sheet Sa ' Ole VI.

B-4RLY01H 15A Bre.ke BMHV35 NG02ACR127 P-4BMYO2B 3A use RLO24 S.G. B Tuce sheet Sa-ole. '

B-aRLYO1H :A Breaker BMHV35 NG02AC R 1,

P-4EMY 20 3A Fuse RLO2'

5. G. C 7.re snee; $2 c ' e B-4 mV01H '5A areu er EWV37 (C

(

  • s2A2R127

'.CLF CREE - N ' 1 3/4 B-2B i

j

July 8,1987

_ : L O n t i n u eC,,

C

.--..,r.s,...,..e

, :.. T.. y r... -..,..-- :

...,. t

.. r....... s.

L, \\5 : : -.. * -

.... u r I

  • e, : t ? : /.* *, '6.f-r *.Ii.. e**

i

.r.

n. 'n : :. : n

.o

...-a:-- -.,

.. j ; ; t.. : y -

..s,,..

.]

i..+...*.....

3. c. i

% *.E":::: 'A :use

; r,. - -

5.G.D Tube Shee Sar:'e viv

.t.. m.. 4..:

E ~ E '.l-1 E - E ** ii t e r

n. m a-. n..... -

J

. r. a. s

Da;u;m r ru u..,-.,

..'. s.

.,..q pumD og..out.lon..,jVe

. I o

hn

.J

..ss?

L* ruse D a n tf o.e,L n..

w n

IEN2225 0

Fuse

^HR uma RW5T Iut icn.'alve 0.

.a s.

r

...:=

pp oc.1.$:

e

.:rutt r.,.... se

n.coler,sc,.ation.alve r.

,a..:.r.

- use
r e.,:s "Er3C9:

-1 cse Cont Cooler Isolation talve a s...:. :.-

..n-

...e

q. vat

-:rrer:.,., r.

..use Cont Cooler.tso. tien i..alve ia

.aecerr: : ;s ruse

..t r H.,,s, *,

ZEFG3iC :-:A Fuse Cont Cooler Isolation Valve

...~ :

p,

..s,

.a

.n

.. n tr o-

-:uater r

.n ruse Puno CC., Return Con: Isol Viv n

N302ECF2 E-1A Fuse a

EG', '60 4 EGG 1CA P-2A Fuse Cont ol Vlv CCW Return from NGC2EDF3 E-1A Fuse RC pumo her Barr Viv EGHV62 1EG317A P-2A Fuse N301EHF; B-1A Fue EGHV-60 Bypa Valve Cent Isol Viv e

EGHV130 2:aate:

e, n, use

-_,V-o2 Bypass Va ve Cont Isol viv tud NG31EH3 E-1/ fuse EGHV132

.' E.'G32 A. - 2 A F u se RHR to Charging /SI Pu.

Suction Viv

.ss

.r
n ruse

.y t o dt, o BO.,.s.

1EEi.2~, P-2A ~use R. 00 E-3A Fuse Excess Letcown Dath to FRT ' sol V?v BBHVE157A

v.2EE P-3A ;use Excess Letcown Patn to DRT Isc1 v1

.. r. w d

.:M :.., e

,ca eo.o=,r/o w nv s4J o.,'*

1./ a*. :.*-

4 s A

. - +

l Attachment I to WM 87-0171 Page 15 of 31 N

July 8,1987

\\\\

\\

'N\\

TABLE 3.8-1 (Continued)

'\\\\

CONTAINMENT PENETRATION CONOUCTCR

's OVERCURRENT PROTECTIVE DEVICES N

PROTECIIVEDEVICE NUMBER AND LOCATION POWERED EOUIPMENT

\\

Low Voltace' Power and Control (Continued)

\\

1BBK37A P-3A Fuse Pressurizer Safer / Vlv RLO21 B-3AFuss'N BEHV8010A 1BBK37B P-3A Fuse 3

Pressurizer fety Viv RLO21 8-3A Fuse N

BBHV80108 4BBK37C P-3A Fuse-RLO21 8-3A Fuse Pressuri er Safety Viv BBHV801,C IBBG39A P-2A Fuse

\\

l NG01BBR3 B-1A Fuse

'N BB 8000A Pres urizer PORV Isolation talve

\\

5GRK02A P-3A Fuse N

iltration Unit Dam:er RLO20 B-3A Fuse

\\

GRP0Z5 6GRK028 P-3A Fuse

\\

RLO20 B-3A Fuse Filtration Unit Damper i

N GRPDZ15 s

1GTK03A P-3A Fuse

\\

RLO20 B-3A Fuse

\\CtatMinipurgeIsolVaise G HZ5 P-1G5Y010 3A Fuse RLO11 Hyd gen Analy:er Ctet Isci.iv G5HV1 B-1RLYO1G 15A breaker NG01ACR119 P-1G5Y01E 3A Fuse RLO11 Hydrogen An y:er Ctet'Isol ?!/

6-1RLYO1G 15A Breaker GSHV14 NG01ACR119 P-1G5Y10A 3A Fuse kt220 Ctat Atmosphere Mon,*:r 15;' V *,,

B-1RLY01.1 15A B eaker G5HV31 NG01ACR123 l

P-1G5Y108 's Fuse RLO20 Contai. en 4.m "anite:.:0 G5HV3a B-1RLY01 15A Breaker NG01AC" 23 3-6'ir'01A ISA Breaker OG sGBR233 tac t e :::r.s 5 ' :I n c-(C 2 650Y01A 20A Fuse

(

C CCER1 bCLF CREE 5, - cN:7 1

2. 4 i-30

Attachment I to WM 87-0171 Page 16 of 31 July 8, 1987 T4 LE L E-1 (Cr-tinuec) 02'TAIN"ENT PENETRATION CONDUCTCR CVERCURRENT PROTECTIVE DEY!CES

....... - - c.4c:

1

..;.: L:
3. c,,<. -.,
ntu t

E? ' 3 L::'~ICN EDU: Ff.'E NT L:*.

tsce De,er end Control (Ccntinued)

I

{

P-5EEY164 iEA Ereaker s

.v.,,-

Reactor Coolan+ Sys Le.el Alarm r

ro e:n. :

E-5EEY16A 30. :use

G2DGERI 3-60';YO 9: IEA Ere ker CROM Co ing Fan Space Heater PG20NER225 E-63NYO9F 30A Fuse PGODNER1 P-6GNYO9H 15A Ereaker 20:0NER226 DM Ccoling Fan Soate Heater E-5GNYO9H 30A Fuse PG20NER1 i

P-fGNYC9K 15A Ereaker l

SG 0NER223 Reactor Cavity Cooling Fan I

Space Heater E-65Nv09K 30A Fuse PG20NBR1 I

i D-4EFYO:: 15A Ereaker N3:2 EAR 114 Accumulator Isolation valve Space Heater E-4E:v02C 30A Fuse NGO EGR4 1

P-4EPY020 ISA Ereaker Act mulator Isolation Valve NG02 EAR 115 Spac Heater E-4EFYO2D 30A Fuse NG02BGR4 P-4GNYO93 15A Bre er NG02BAR110 Containment Cooler Fan Space Heater E-4GNYO9B 30A se NG02EGR4 P-4GNYO9D oA Breaker NG02BAR1'.

Containment Cooler ~an Space Heater E-4GNYD"s 30A Fuse NG02EG,4 P-4.'Y09M 15A Breaker N'.2BAR120 Hydrogen Mixing Fan Space Heater

' 4GNYO9M 30A Fuse k'

NG02EGD4 s

WOLF : REEK - UNIT 1-3/4 E-31

_ _ _- _ __ - =

Attachment to WM 87-0171 09" July 8,1987 I

TABLE 3.8-1 (Continued) 1 3

l CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PROTECT VE DEVICE POWERED NUMBER At LCCATION EOUIPMENT LowVoltace\\owerandControl(Continued)

P-4GNYO9P 15A E.eaker NG028AR121 Hydrogen Mixing an 5:: ace Heater B-AGNYO9P 30A Fuse NG02BGR4 P-1GNYO9A 15A Breaker Containm t Cooler Fan E; ace NG018AR119 Heater B-1GNYO9A 30A Fuse NG01BER3 P-1GNYO9C 15A Breaker C tainment Cooler Fan 5: ace NG01BAR120

. eater B-1GNYO9C 30A Fuse NG013ER3 P-1GNYO9L 15A Breaker NG01BAR122 Hydrogen Mixing Fan scace Heater B-1GNYO9L 30A Fuse NG018ER3 l

P-1GNYO9N 15A Brea<er H'

rogen Mixing Fr i::a:c NG01BAR123 Hea er S-1GNYO9N 20A Fuse NG01BER3 P-5GNYO9E 15A Breaker PG19NHF228 CRDM Cool og Fan Space -eater B-5GNYO9E 30A Fuse PG19NHF1 P-1EPYO2A 15A Brea er NG01 EAR 115 Accumulated Iso i

E-1EPYO2A 20A F'se Valve Space Hester l

NG01EER3 l

P-1EPYC2B 1 A Erea'.er NG01 EAR 117 Accumulator ISO B - 1 E P Y C.' 3CA Fuse valve space He3ter NG01EEP

?-EC'IICC 3A Fuse O L 10 Ctat Atn Manit;..

Gihy:5 e % CIA 1E; E ea..

h. ~.

i GC: ACE 2;

'iCLF C EE,

,,,,;7 ;

2/4 S-2;

_____a

Attachment I to WM 87-0171 Page 18 of 31 July 8, 1987 T AELE 3.5-1 JContinued)

CONTAINMENT PENETRATION CCNDUCT:R OVERCURRENT PROTECT!YE DEVICEE

^ 'TE:~ ti CEVICE POWERED

' / _ :: R:: _0:AT :N EDUIN4ENT r- '. \\ tare Power s": Control (Continued)

?-235Y10D 'A Fuse RLO20 Ctat Atm Moniter Isol Viv GSHV39 E-IELYO1A '5 Breaker N302ACR130

-5;NYO93 15A Bre.;er CEDM Coo ng Fan Space Heater
G19NHF229 E-5GNYC9G 30A Fuse
Gl?N"
1

-5 Nt09J 15A Breater

~R actor Cavity Cooling Fan Space

=3: Et.HF225 ester 5-5GNYO9J 30A Fuse

G19NHF1 55FY11AA P-30A Fuse N7'1 E-60A Fuse Rod Position Panel 5F109A 55Fi'1AB P-30A Fuse PN0710 B-60A Fuse Rod Position Tanel SF109B ILFGCEA P-2A Fuse N30.'EER2 E-1A Fuse Normal sump Ctmt 1s01 Viv LFFV95 5LFG15A P-2A Fuse PG19NAF2 B-1A Fuse In trument Tunnel Sump Pump DPL 7A 6LFG15B P-2A Fuse PG20NDR2 B-1A Fuse Instru... nt Tunnel Sump Pump DPLF07B 1GSG03A P-2A Fus NGDIFFF2 B-1A Fu e Hydrogen Pu e Ctmt Isolation Viv G5HV20
EEG39B P-2A' use Pressurizer PORT Isol Viv N302B0F1 E '

Fuse BBHVB0008 ISBK;0A.P ISA Fuse PZR PORV NK510E

-15A Fuse BSPCV455A 4EEK's3 P-15A Fuse PZR PORV NK; 1 E-15A Fuse BBPCV456A

'dGK04B P-3A Fuse ELOC1 E-3A Fuse Alternate Charging Path Isol V IV BGHVB147 s_

<!: L: CREEK - UNIT 1 3/4 8-33

s Attachment I to WM 87-0171 Page 19 of 31 July 8,1987 TABLE 3.3-1 (Continuec)

CONTAINMENT PENETRATION CCNDUCTOR OVERCURRENT PROTECTIVE DEVICES PROTEC VE DEVICE POWERED NUMEER 340 LOCATION ECUIPMENT Low Voltace Dower and Control (Continued) 6BGK04A P-3A

'se Normal Charging ath Isol Valv RL001 E-3A Fu BGHV8146 P-5LFY10A 3A Fuse Containment coler Orain Valve RLO23 LFLV97 B-5RLYO1H ISA Breaker PG19GCR217 i

P-5LFY10C 3A Fuse Cont nment Cooler Drain Valve RLO23 LFL':9 B-SRLYO1H 15A Breaker PG19GCR217 P-6LFv10E 3A Fuse Containment Cooler Crain.*!ve RLO23 LFLV9B i

S-6RLYO1G 15A Breaker PG20GBR-

D-6LFY100 3A Fuse Containment C00ier ursin.ai.e RLO23 LFLV100 S-6RLYO1G 15A Breaker PG200ER217 P-6LFY17A 3A Fuse Refue ing Pool 5;anc Pi ce RLO23 Discha e Vaive B-6RLY01G 15A Ereaker LFLV122 1

PG20GER217 P-5LFY20A 15A Breaker

-I n s't rume n t T u nel sume ve'3:are PG19NHF224 Sensor S-5LFY20A 30A Fuse TLVF01 OG19NHF1 P-6LFY20B ISA reaker Instrument Tunnel iu., veisture PG:0NER216 Sensor S-6LFY2CSJA Fuse TVLF02 PG20NER1 P;5{

ru.o{i 5C '5 A E res ser Lccal rac i a. : ;r en :.

-2.,

sucplies E-5~.YO6C 3CA E;5e 3DRl439-J

-.:,_,.rr.

(

,. C. : ::.

-, a:.,

Attachment I to WM 87-0171 Page 20 of 31 l

July 8,1987 i

i 1

i IAELE 3.5-1 (Contiruedi l

CONTAIN"ENT PENETRATION CCN UCTOR l

OVERCURRENT PROTECTIVE DEVICEE

~ ~C E:~:.'E :E'. ::E POWEPED I

' "E : ~ 21: LO:AT:N EDU!P"ENT I

.. hq r e s wer sna Control (Continued) c

_t.

F-15)v01D. r use Press. Ctat Isol iv l

RLO11 SJHV12S E-1RLv01G 15A 'reater N331ACR119 F-45)YDIA 3A Fuse Press. Li HL 113 Sample Clr Viv l

C.011 SJHV5 E-4RLY01G 15A Ereaker N30:A R140 l

1;Th03: P-3A Fuse Ct.

Purge Isol Viv

02D E-3A Fuse G HZ7
-1G5YC1F 3A Fuse Hydrocen Anal Samp Return to Ct t Viv RLO11 G5HV1B E-1RLYO1G 15A Breaker NG01ACR119

)

1 i

P-4G5Y01A 3A Fuse l

Hydrogen Anal Ctmt Sample Viv RLO11 C5HV4 E-4RLYO1G N302ACR140 15A Breaker 1

P-4G5YO15 3A Fuse H; rogen Anal Ctet Sample Viv RLO11 G5 5 B-4RLY01G 15A Breaker l

NG02ACR140 P-4G5Y01C 3A Fuse Hydrogen nd Samp Return to Ctmt Viv RLO11 G5HV9 B-4RLYO1G 15A Brea er NG02ACR140 5B30028 P-2A F se RCP Oil Lift PG19NGR3 B-1# Fuse Pump Control 6BSGC2C P A Fuse RCP Oil Lift PG20NFF3 -1A Fuse Pump Control 6BBGC's P-2A Fuse RCP Oil Lift PG2 FF2 B-1A Fuse Pump Control

' sG03A P-2A Fuse RCP Thermal Barrier Cooler Isol Viv JG03CDF4 8 1A Fuse BEHV13 i

/

WOLF CREEN - UNIT 1 3/4 B-35

Attachment I to WM 87-0171 9

July 8, 1987 TA8LE 3.8-1 (Continued)

CONTAINMENT PENETRATION CCNDUCTOR OVERCURRENT PROTECTIVE DEVICES PROT: TIVE CEVICE NUMBER 'ND LOCATICN POWERED EOUIPMENT LcwVoltahePowerandControl(Continued) 1BSG033 P-2A 'use NG03CHF1 B-1A RCP Thermal Barri.r Cooler Isol Viv

=se BBHV14 182G03C P-2A Fuse NG03CBF4 B-1A Fuse RCP Thermal c rrier Ccoler Isol Viv BBHV15 185G030 P-2A Fuse NG03CLF2 E-1A Fuse

~

RCP Ther.al Barrier Cooler Isol V'v BEHV16 EBBK05A P-3A Fuse RCP aal Water Return Viv RLOO1 B-3A Fuse i

BB.8141A 5SEK053 P-3A Fuse RL001 E-3A Fuse CP Seal Water Return viv BEHVS1413 6BBK05C P-3A Fuse RL001 B-3A Fuse RCP Seal Water Return Viv BBHV8141C l

l 6EBK05D P-3A Fuse RL001 B-3A Fuse RCP Seal Water Return vb BBHv8141D 62EK07A P-3A Fuse P.

Discharge to RC;T '..

i RLO21 5-3A Fuse BB 8031 6EEK073 P-3A Fuse RLO21 B-3A Fuse Reacto Makeup Water to PRT Viv 1

BEHV804s 6EEKOSA P-3A Fuse 1

i HS115 3-3A Fuse RCDT Ht. Ex h.

to PRT Viv BBHV7141 6BBK09A P-3A Fuse RLO21 E-2A Fuse RV Flange Leakor Lir.e ta :. COT 'ils BBHV8032 1BEK30C P-3A Fi e RLO21 6-3A Fu e Reactor Vessel Hesa. nt viv BBHVEOCCA 4EEK200 P t Fuse e

RLO21 E-2 Fuse Rx vessel Hes Vent

',1.

EBHVE0023 1EEG31 P-2A Fuse NG01.F1 E-1A Fuse PRT Emergency crain t.:ne EEHV3037A 4E C313 P-2A ~use

EhE2 E-la Fuse FRT Emercency Crain _ic

'*""1 EEHt.3037N

~

e s--

..C L ; C.; E E - ;N I T ;

2/4 3-25

Attachment I to WM 87-0171 Page 22 of 31 July 8, 1987 TABLE 3.8-1 (Continued)

/

/

CONTAINENT PENETRATION CONDUCTOR

/

p DVERCURRENT PROTECTIVE DEVICES

,/

'R:TE:~IJE DEVICE

/

POWERED

/

':. E E A';D LOCATION EOUIPMENT

/

Lr.

c'ta 2 Oc.er and Control (Continued)

/

1EFK0:C P-3A Fuse

/

Accumulator "ank D isol Viv RLO15 E :' Fuse EPHVS5080 Indicati6n IEDK02E P-3 Fuse Accumulator Tank A Isol Viv RLO1E E-3A Fu =

EPHVS803A Ind'6ation-1EPK0:F P-3A Fus RLC1E E-3A Fuse Accumulator' Tank'C Isol Viv EPHV880SC/ Indication

EFGD
C P-2A Fuse Accumu) or Tank B Isol Viv N30253F3 E-1A Fuse EPHVp808 Vindication

/

E
G 20 P-2A Fuse Accumulator Tank 0 Isol Viv N00ZEHF2 B-1A Fuse 4 HV8S08D Indication

/

1,

EPK02A P-3A Fuse Accumulator Tank A Isol Viv l.

RLO15 E-3A Fuse EPHV8808A Indication 4EPK02B P-3A Fuse Accumulator Tank C Isol Viv RLO18 B-3A Fuse i.

EPHV8808C Indication j

4EPK02G F-3A Fuse Accumulator Tank B Isol Viv RLO1E E-3A Fuse EPHV880SB Indication 4EPK02H P-3A Fuse Accumulator Tank D Isol Viv RLO13 E-3A Fuse 3

. HV880BD Indication l

EEPK03A P-3A Fuse

\\

RL018 E-3A Fuse Acc mulator Nitrogen Supply Viv EPHV 75A i

EEPK035 P-3A Fuse l

RL018 B-3A Fuse Accumula or Nitrogen Supply Viv EPHV8875C 5EPK03C P-3A Fus Accumulator st Line Viv RLOIE E-3A Fuse EFHV8877A AEEK303 P-3A use Reactor Vessel He d Vent Viv RLO21 E-3A ~use BBHV8001B EEPKC2D

-3A Fuse Accumulator Test line

'I v RLO12 E 3A Fuse EPHV8877C EEPK 3E P-3A Fuse Accumulator Water Fill Lin Viv RLr g 3 3A Fuse EPHV8878A

('

e!0LF CDEEK - UNIT 1 3/4 8-37 1

i l

l

__________m_

Attachment I to WM 87-0171 Page 23 of 31

~~

\\g July 8, 1987 i

N

\\

TABLE 3.3-1 (Continued)

{

CONTAINMENT PENETRATION CONDUCTOR l

s i

OVERCURRENT PROTECTIVE DEVICES 1

PROTECbVEDEVICE POWERED NUM3ER AND, LOCATION EOUIPMENT j

\\

Low Voltace Power and Control (Continued)

SEPK04A P-3A Fu'se Accumulator Water ill Line Viv 1

RLois B-3A Fuse N EPHV8878C l

{

5EPK04B P-3A Fuse Accumulator T-t Line liv RL018 B-3A Fuse EPHV8879A SEPK04C P-3A Fuse Accumulat r Test Line

','Iv

{

RL013 B-3A Fuse

.N EPHV887c 6EPK040 P-3A Fuse RL018 B-3A Fuse Accen lator Test Line V1v EPH' 8793 i

I l

6EPK04E P-3A Fuse f

' cumulator Tes: Line.':s RL018 B-3A Fuse cPHV88790 GEPK05A P-3A Fuse RLO18 B-3A ruse Accumulator Nitrogen :ucpi;.

N

PHV88755 N

l 6EPKC53 P-3A Fuse RL013 6-3A Fuse Accumulator Mitrogen 5;:::...

E4EVSS750

{

s j

6EPK05C P-3A Fuse AcchulatorTest Line i:.

I i

RLO18 S-3A Fuse EPHVEB 73 6EPK05D P-3A Fuse Accumula r Test Lire VI-RL018 B-3A Fuse EPHV8877D 6EPK05E P-3A Fuse RL01U B-3A Fuse - -

Accumulator W ter rill.' 1 "

EPHV827ES i

6EDK05F P-3A Fuse Ac:umulator Water 'il'.'

4 RLO18 B-3A Fuse EPbvES75D P-4SJY013 3A Fu Press. Vapor. Cont. !sc 5: ace 'elv RLO11 SJHV12 3-4RLY01G 15; Breaker NGD2ACR140

?-45JYC1" 3A Fuse Ac:ums :3mple Crt ::;l.'.

RLO11 5JHV13 3-;RL'J1G 15A Brea<er i

N200 CR140

,g l

s..:a CnE.- m 1

<4 s-3

\\

---d

1 Attachment I to WM 87-0171 Page 24 of 31 July 8, 1987 TAELE 3.E-1 (Continued)

CONTAINMENT PEi:ETRATION CONDUCTO^

DVEPCURRENT DROTECTIVE DEVICE 5 D FiSE :~I,'E DEVI C E POWERED et"E N :.*:0 LO::TI:';

EOL'I PMENT Lh '.' c ce %er and Contrcl (Continuec)

D-SSJYO3B c' Fuse Accumulator Samp/.

i Line Viv RF211 SJHV16

/

E-5DDYO9D 15A 'reaker

^G19NHF236 P-5SJYO3C 3A Fuse Accumulat Sample Line Viv RP211 SJHV17 E-5RFYO90 15A Breaker PG19NHF236 P-55)YC4B 3A Fuse Ac umulater Sample Line Viv RF211 HV14 E-5EPYO9D 15A Erecker PGliNHF236 P-53JYOaC 3A Fuse Accumulator Sample Line Viv RD211 SJHV15 E-5RFYO9D 15A Ereaker PG19NHF236 i

P-15JY06B 3A Fuse HL Sample 3 Viv

(

RP332 SJHV4 E-1RPYCEF 15A Ereaker J

NG01BAR140 F-4SJYO6A 3A Fuse HL 5.ple 1 Viv RP333 SJHV3 E-4RPYO9F 15A Breaker NG02SAR140 l

\\

P-5SJYO6C 3A Fuse Press Liquid pace Samp Isol Viv RP211 SJHV20 E-5RPYO90 15A B eaker PG19NHF236 i

P-4BMY01A ' Fuse S.G. A Out to Nuc Sa.nie Sys Viv RLO24 BMHV19 E-4RLYO 15A Ereaker NG02AC 227 P-4^AYO18 3A Fuse 5.G. B Out to Nuc Sample Sys Viv R' 24 BMHV20

  • 4RLY01H 15A Breaker NG02ACR127 WOLF CREEK - UNIT 1 3/4 E-39

/

1 N.

i Attachment I to WM 87-0171 Page 25 of 31 i

July 8,1987 i

i l

TABLE 3.8-1 (Continuec) l CONTAINMENT PENETRATION CCNDUCT:

OVERCURRENT PDOTECTIVE CEVICE3 l

N i

PROTECTtyE DEVICE POWERED NUMBER Ard LOCATION 1

EOUIPMENT x

{

Low Voltace Aower and Control (Continued) 1

\\

{

P-4BMYO1C 3A Fuse S.G, C Cut to Nu Sam. ole Sys Viv

{

RLO24

\\

I EMHV21 B-4RLY01H ISA Breaher 1

NG02ACR127 P-5GMY08A 3A Fuse RLO20 CROM Cool rg Disenarge Cze:er GNHZ71 B-5RLYO1L 15A Breaker PG19GCR230 P-5GNY08C 3A Fuse RLO20 CF M Cooling Disenarge :a er

^iHZ73 B-5RLY01L 15A Breaker PG19GCR230 j

i P-5GNY08C 3A Fuse RLO20 CROM Cooling Disenarge :2 :er GNHZ72 S-6RLY01J 15A Breaker PG20GBR222 j

P-6GNYOSA 3A Fuse Cn M Cooling Distnar;e Car:er RL020 GNH 4 B-6RLY01) 15A Breaker PG20GBR222 55GK10A P-3A Fuse RL001 B-3A Fuse Nor. mal La Own Isolstica.'.

BGLCV459 1

5BGK10B P-3A Fuse-RLOO1 B-3A Fuse Normal Letdown Isolatier.'

EG LC'/460 i

l SEGK19A P-3A Fus RLOO1 6-3A Fuse Pressuri:.er I:r3y.'v EGH'!E;;5 l

6BGK20A P-3A ruse Excess Let

..n RL001 B-3A use

- :ne !se.stice viv SGHV5143 EEGK35A -3A Fuse Leta:.n O' * :n :..~at RL001 : 3A Fuse E GH'. S la H EEGF;5B P-3A Fuse Le:::,.n :ri*':e

'1 n EL01 B-2A fuse E CH'. 312 33

/M

.EGx:5: =-:A suse

.e:::_n :,. :e

L201 5-3A ;use IGW.5.li

CLF lREE: - UNIT ;

3/4 E-4:

Attachment I to WM 87-0171 Page 26 of 31 July 8, 1987

  1. f i

TABLE 3.E-1 (Centinued)

\\'

CONTAINMENT PENETRATION CCNDUCTO:

OVERCUREENT PROTECTIVE CEVICE3

.n....

p,w.

gn n..

<..,.,,.,. 7 c..

L:s. ' :.

Dr.<er 2 c Control (Continueci

' E 3 r.3 f : :-3A 'use Letdown Contain.ent Is:iation Vh J.I;' E-3; :us BGHVS160

'.E 2 3 21 :- A Fuse Seal Water

Isolation V1v N3.".ES:3 E-1A Fuse SGHVS112

'.E;s E: 0-3A Fuse Excess etdown/ECS Isolation V!v

J.CC; E-3A :use BGHVE 53A
E G-JE
0-3A Fuse Ex ess Letcown/F.CS Isolit :n /1v E.001 E-3A fuse
HV235A ECKEA ?-3A Fuse Excess Letcown/ P.CS Isolation Vl e 0.L::.* E-3A Fuse BGHVS;533 033h EE F-3A Fuse Excess Letcown/RCS Isoistion Viv R.00 3-3A Fuse BGHVS15AB IEE312A P-2A Fuse RHR Pump Suction Isolaticn '.alve NGC2BCF2 E-1A Fuse BBPV8702A EE2'2E P-2 A Fuse

!R Loop 2 Inlet N302EEF3 E-1A Fuse I

lation Valve EEPVS702B IEEK13A P-3A Fuse Ctmt sol Nitrogen Supply to PRT viv RLO21 5-3A Fuse BBHV80.

ESEK1AC P-3A Fuse RCP Stand 'pe Maieup Viv RLC21 2-3A Fuse BBLCV180 EEEK1:D P-3A Fus RCP Standpipe. keep Viv RLO21 E-3A Fuse BBLCV181 6EEK;;A P-3A use RCP Stanapipe Makeu viv.

RLO21 2-3A use BBLCV178 EEER!aE ^-3A Fuse RLO21 E 3A Fuse RCP Standpipe Makeup Viv BBLCV179 EEEC iB D-3A Fuse e

Reactor Coolant Loops n, r 1-.. : :' ruse

] instrumentation

.::y,.

p*

- ruse MLL

as,.

Reactor Coolant Loops ruse Instrumentation v!OL: C:.EEK - UNIT 3/4 E-Al 1

\\

\\s Attachiaent I to WM 87-0171 Page 27 of 31 July 8, 1987 s

\\

g TABLE 3.8-1 (Continued)

\\

\\\\

CONTAINMENT PENETRATION CONOUCTOR

~

\\\\

\\

CVERCURRENT PROTECTIVE DEVICES PR0iESTIVECEVICE NUMBEFNAND LOCATION POWERED EOUIPMENT

\\

l Low Voltace Power and Control (Continued)

\\

l 6BBK150 P-34\\ Fuse RLO21 B-3A Fuse Reactor Coolant cops Instrumentati

\\

6BBK15E P-3A Fuse RLO21 8-3A Fuse Reactor Co ant Loops Instrumen ation 5BBK19A P-3A Fuse Pressu zer Spray Valve RLOO2 B-3A Fuse BBPCV 55B SEEK 19B P-3A Fuse RLOO2 E-3A Fuse Pr ssurizer Spray Valve

  • PCV455C 15BK30A P-3A Fuse RLO21 B-3A Fuse Reactor Vessel Head Vent Viv EBHV8001A 6GNG03B P-5A Fuse NG02BJF5 6-3A Fuse CRDM Cooling Fan B Discharge Isolation Dam;er GNHZ42 6GNG030 P-5A Fuse PG20 GAR 2 6-3A Fuse CRCM Cooling Fan A Discnarge Isolation Cam:er

.NHZ41 1HSK03A P-3A Fuse RCD Vaoer Space CTMT 1s01 Viv RLO21 8-3A Fuse HBHV7.76 6HEK04A P-3A Fuse HB115 B-3A Fuse RCDT Vap Scace CTMT Isci v1v HBHV7127 SEPY078 P-3A Fuse RPO43 B-15A CB-1 Accumulator T ok Discnarge Valve Position 'witen EPHYS8080A EPHVSSCSBA 6EPYO7A P ^n Fuse RPO44 E-' A CB-1 Accumulator Tank Disc.' ;e Valve Position Swit:.

EPHVSSOSAA EPHVESOSCA EGT'12A P-15A Breaker

" CGER234 B-20A Fuse CTMT Minipurge Esnaust Isolation 03mper G T HZ 4 '.

' h_

a:LF CREE' cNIT 1 3/4 3-42

_ _ _ _ _ _ _ - _ _ - - - ~

Attachment I to WM 87-0171 Page 28 of 31 July 8, 1987

[

\\

>TAE:_E t.5-1 (Continvec}

lk CbMTAIN".ENT PENETRATION CCNDU: TOR CVERCURRENT PROTECTIVE CEVICEI

' T: ~E :.E E'.'

E

.P0klERED

'"E

-: ;C:tTION ECUIPMENT ir. k;{ : = ? Pe.e and Centrol (Continuec)

E37Y12' :-ISA Breaker CTMT Minipurge xnaust

? 200ER20' B-20A Fuse Isolation.Dar. r GTH:42

-55Ri;2A 5A eater CE-1 SR057 In Core N utron Monitoring 6 Path ansfer Motor.A C-55RYO9A 20A-Fu.

SR02A FG'950R1

-55FY12A 5A Ereaker

-2 I Core Neutron Monitoring SR057 Path Transfer Motor A 5-EERYO9A EGA Fuse dR03A r a. :a u r..

-55RY12A SA Sreaker CB-3 SR057 In Core Neutron Monitoring E-554YO9A 20A Fuse 6 Path Transfer Motor B SR02B j

PG;9GCRI L

P-55RY12A 5A Breaker CB-4 SR057 In Core Neutron Monitoring E-55Rf09A 20A Fuse 15 Path Transfer Motor B SR03B PG193'R1 P-55RY12A 5A Breaker CE-5 SR057 n Core Neutron Monitoring 6 ath Transfer Motor C S-55RYO9A 20A Fuse SR 'C PG193CR1 1

P-55RY12A 5A Ereak CB-6 SR057 In Core Jeutron Monitoring 15 Path ansfer Motor C i

E-55RYO9A 20A F e 5R03C PG19GCR1 P-55RY12A 5 Breeker CB-B SR057 In Core Neutron ionitoring 5-55RYO9' 20A Fuse 6 Path Transfer, ter D SR02D PG19G:R P-55 12A SA Breaker CB-9 1

SR's7 In Core Neutron Monitor g

E,5RYO9A 20A Fuse 15 Path Transfer Votor D SRO10 G15 GOR 1 v0Lr CREgg. UNIT 1 3/4 8-43

Attachment I to WM 87-0171 Page 29 of 31 July 8,1987 TABLE 3.8-1 (Continuec)

CONTAINMENT PENETRATION CONDUCTCR OVERCURRENT PROTECTIVE DEVICES r$0TECTIVE DEVICE i

POWERED NUM ER AND LCCATICN EOUIPMENT Low (tace Power anc Centrol (Centinued)

P-55RY0 SA Breaker CS-10 SR057 In Core Neutron M nitoring Drive Unit Heat s B-55RYO9A 2 Fuse SR01C & D i

PG19GCR1

{

P-55RYO9A SA Bre er CB-11 In Core N tren Monitoring i

SR057 i

S-55RYO9A 20A Fuse Drive Un '. ' Heaters SR01A PGICGCR1 1

P-CB95 CKT 12 20A Breake CS-12 l

0295 Es pe Lock and 5 ir Lignting B-0595 CKT 12 20A Fuse QB95 I

P-5KFG02V 6A Fuse Reacter Building KF07

~

Elevator E-5KFG02V 15A Fuse KF07 KF07

~

l P-Loco #9 15A Fuse FU9A QF076 P.A. Lecp #9 QF076 E-Leop #9 15A Fuse FUES QF076 P-Loca #10 ISA Fuse FU10A 0F076 P. A.

Lcep #10 B-Leop #10 15A Fuse FUlr QF07e QF076 WEECPI P-20A Breake PG2CNER2 E-30A Fur Steam Gener ter Instrument it t system WEECP3 P-20A Breaker Steam Generator PG2CNER2 B-30 Fuse Instrument Test 5; tem WEECP2 P-2 Breaker PG2CNBR2 -30A Fuse Steam Generator Instrument Test System

-5GRYuA 15A Breaker PG';N5124 CAC5 Char
cal Filter S-5,Y02A 2CA Fuse Temperature Transmitter GISNHF1 GRTT9 6_

..u :m,- x 1 m e-=

Attachment I to WM 87-0171 age 30 of 31 July 8,1987 1 ELE 2.E-: ftent'nue:1 C';TA : ?:":NT E;;E 04T 0, :CJ:T:R CVEr.:U: ENT CE:TECT:'JE :VI:53

- ~..~ ~; ; '-

  • 4. \\-iL

' ; a. w ;

. b

/

P.'s. 0 7.; d

/

3 E EN) LO2$75CN

[ * *J ! O M E ' I

'.. V 01:2re

  • .rer sno Centrol (Continued)
.'RYO33 15A Breaker CAC5 Charcoal Filter Pu CNER242

' Temperature Transmitter 3-EGR) 33 30A fuse GRTT19

320h El F-5 3RYO4 A A Breaker i

PG19NHF21-Noter Space Heater S-53RYO4A 30A 'use 66r DCGR01A PG19NHF1

,/

/

F-52RYO B 15A Brea 'er

/'

Motor Space Heater

G20N3R212

/

Fcr DCGRO10 5-53RYO4B 30A Fuse

/

PG20NER1

/

f F-6 KEG 02A 15A Breaker r'

PG20GBR224 Fuel Hancling L

S-6 KEG 02A 30A Fuse

/

Manipulator Crane HKE01 k-PG20GBR1 j/

s P-1EE517A 10A Fuse 5B029C RHR Loop 1 Inlet Isolation 5-1ESA17A 20A Fuse Valve Limit Switch BBZ55702AB NN0112 P-4EE517B 10A Fuse SB032C RHR Loop 2 Inlet Isolation Valve 5-453517B 20A F e BPVB702B NN0412 P-6KFYO2A 2 Fuse Pers nel Access Hatch TVKF03 3

Lock. chanism and Lights 5-6KFYO2p3DBreaker TVKF03 TYKF0

}

r."LF : REEK - UNIT 1.

3/4 S-45

.~

1 Attachment I to W. 87-0171 Page 31 of 31 l

July 8, 1987 l

1 1

l Inserts J

1 J

Insert A For each containment penetration provided with a penetration conductor overcurrent protective device (s), each device shall be OPERABLE Insert B Protective devices required to be OPERABLE as containment penetration conductor overcurrent protective devices shall be danonstrated OPERABLE.

i l

i l

l i

i i

e

__._m_

9 l

l l

1 l

ATTAOMFMr II DESCRIPTION N OTANGES t

i i

I l

i

]

Attachment II to WM 87-0171 Page 1 of 1 July 8, 1987 DESCRIPTION OF CHANGES Concurrent with the issue of Amendment No.

5 to Facility Operating License NPF-42, the Nuclear Regulatory Cor: mission (NRC) Staff concluded that since the removal of Table 3.8-1, and References to that Table, was being generic basis, approval or disapproval of the Wolf Creek considered on a Generating Station (WCGS) subnittal would be deferred until a generic resolution of the issue.

Subsequently, WCGS was informed by the NRC Staff that this issue had been resolved.

This attachment describes the changes to the proposed Technical Specification 3/4.8.4,

" Containment Penetration Conductor Overcurrent Protective Devices", originally transmitted by letter dated August 25, 1986 (IMLNRC 86-153).

These changes are considered minor in nature and are consistent with the conclusions of the Safety Evaluation and Significant Hazards Consideration transmitted by the aforementioned letter.

Limiting Condition for Operation (LCO) 3.8.4.1 LCO 3.8.4.1 presently reads as follows:

All Containment Penetration Conductor Overcurrent Protection Devices given in Table 3.8-1 shall be OPERABLE.

This ECO is being revised to read as follows:

For each containment penetration provided with a Penetration Conductor Overcurrent Protective Device (s), each device shall be OPERABLE.

This change is a minor revision to the wording originally proposed for LCO 3.8. 4.1 to remove the Reference to Table 3.8-1.

Surveillance Requirement 4.8.4.1 Surveillance Requirement 4.8.4.1 presently reads as follows:

l All Containment Penetration Conductor Overcurrent Protective Devices

)

given in Table 3.8-1 shall be demonstrated OPERABLE:

The Surveillance Requirement is being revised to read as follows:

I Protective Devices required to be operable as Containment Penetration Conductor Overcurrent Protective Devices shall be demonstrated 1

OPERABLE.

i This change is a minor revision to the wording originally proposed for Surveillance Requirement 4.8.4.1 to remove the Reference to Table 3.8-1.

)

_ _ _ _ _ _ _ _ _ _