Forwards Safety Evaluation Approving Alternate Method for Complying w/10CFR50.55a for Main Steam Positive Leakage Control Sys Valve
ML20235N591
Person / Time
Site: River Bend 
Issue date: 02/21/1989
From: Calvo J
Office of Nuclear Reactor Regulation
To: Deddens J
GULF STATES UTILITIES CO.
Shared Package
ML20235N594 List:
References
TAC-64829, NUDOCS 8903010296
Download: ML20235N591 (4)


Text

-

February 21, 1989 Docket No. 50-458 1

Gulf States Utilities Company.

l ATTN: Mr. James C. Deddens Senior Vice President Post Office Box 220 St. Francisville, Louisiana. 70775

Dear Mr. Deddens:

SUBJECT:

ALTERNATIVE PETHOD OF COMPLYING WITH 10 CFR 50.55a FOR RIVER BEND STATION MAIN STEAM POSITIVE LEAKAGE CONTROL SYSTEM VALVE (TAC NO. 64829)

By letter dated October 6,1986, Gulf States Utilities Company requested relief from Section III of the American Society of Mechanical Engineers' Boiler and Pressure Vessel Code for River Bend Station, Unit 1.

The requested relief relates to a replacecr,ent disk in valve 1821*MOVF098C which does not meet the ASME Section III requirements for Authorized Nuclear' Inspector (ANI)/ Authorized Nuclear Inservice Inspector (ANII) involvement. Based on its review, the NRC staff finds that Gulf States Utilities Company has demonstrated that compliance with respect to ANI's review, in this case, would result in hardship or unusual difficulties without a compensating increase in quality and safety. The staff concludes, therefore, that the proposed alternative is acceptable and in accordance with 10 CFR 5s.55a(a)(3). The staff's Safety Evaluation is enclosed.

Sincerely,

/s/

Jose A. Calvo, Director Project Directorate - IV Division of Reactor Projects - III, IV, Y and Special Projects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure.:

See next page

, DISTRIBUTION.,

LDocket Fileu.i NRC PDR Local PDR PD4 Reading L. Rub'enstein J. Calvo P. Noonan W. Paulson I

0GC-Rockville E. Jordan B. Grimes ACRS (10)

PD4 Plant File PO4/D((c PD4/L PO 0

[

PNoon b

WP on:sr JCalvc 3

01#//89 01/ /89 0

3 /89 OA/#/89 8903010296 890221

! l 4

PDR ADOCK 05000458 l

P PDC

e February 21, 1989 Docket No. 50-458 Gulf States Utilities Company ATTN: Mr. James C. Deddens

)

Senior Vice President Post Office Box 220 St. Francisville, Louisiana 70775

Dear Mr. Deddens:

]

SUBJECT:

ALTERNATIVE PETHOD OF COMPLYING WITH 10 CFR 50.55a FOR RIVER BEND STATION MAIN STEAM POSITIVE LEAKAGE CONTROL SYSTEM VALVE (TAC NO. 64829)

By letter dated October 6,1986, Gulf States Utilities Company requested relief from Section III of the American Society of Mechanical Engineers' Boiler and l

Pressure Vessel Code for River Bend Station, Unit 1.

The requested relief relates to a replacement disk in valve IB21*MOVF098C which does not meet the ASME Section III requirements for Authorized Nuclear Inspector (ANI)/ Authorized Nuclear Inservice Inspector (ANII) involvement.

Based on its review, the NRC staff finds that Gulf States Utilities Company has demonstrated that compliance with respect to ANI's review, in this case, would result in hardship or unusual difficulties without a compensating increase in quality and safety. The staff concludes, therefore, that the proposed alternative is acceptable and in accordance with 10 CFR 50.55a(a)(3). The staff's Safety Evaluation is enclosed.

Sincerely,

/s/

Jose A. Calvo, Director Project Directorate - IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page DISTRIBUTION Docket file NRC PDR Local PDR PD4 Reading L. Rubenstein J. Calvo P. Noonan W. Paulson OGC-Rockville E. Jordan B. Grimes ACRS (10)

PD4 Plant File k,0b PD4/D((

PD4/L PD OGC PNoonth WPh on:sr JCalve 01N//89 01/ /89 3 /89 01/N/89, c

I,/

  • jg UNITED STATES

[

g NUCLEAR REGULATORY COMMISSION 7,,

~[

WASHINGTON, D. C. 20665

,/

February 21, 1989 Docket'No. 50-458 Gulf States Utilities Company ATTN: Mr. James C.. Deddens Senior Vice President Post Office Box 220 St. Francisville, Louisiana 70775

Dear Mr. Deddens:

SUBJECT:

ALTERNATIVE METHOD OF COMPLYING WITH 10 CFR 50.55a FOR RIVER BEND STATION MAIN STEAM POSITIVE LEAKAGE CONTROL' SYSTEM VALVE (TAC NO. 64829)

By letter dated October 6,1986, Gulf States Utilities Company requested relief from Section III of the American Society of Mechanical Engineers' Boiler and Pressure Vessel Code for River Bend Station, Unit 1.

The raquested relief relates to a replacement disk in valve 1821*M0VF098C which does not meet the ASME Section III requirements for Authorized Nuclear Inspector (ANI)/ Authorized NuclearInservice. Inspector (ANII)inycivement. Based cn its review, the NRC staff finds that Gulf States Utilities Company has demonstrated that compliance with respect to ANI's review, in this case, would result in hardship or unusual difficulties without a cor.pensating-increase in quality and safety. The staff concludes, therefore, that the proposed alternative is acceptable and in accordancewith10CFR50.55a(a)(3). The staff's Safety Evaluation is enclosed.

Sincerely, I

$A&

(m Jose A. Calvo, Director Project Directorate - IV Division of Reactor Projects - III, IV, Y and Special Projects Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page mm.

--____.____..________-___-___m

Mr. James C. Deddens Gulf States Utilities Company River Bend Nuclear Plant cc:

Troy B. Conner, Jr., Esq.

Mr. J. E. Booker Conner and Wetterhahn Manager-River Bend Oversight 1747 Pennsylvania Avenue, NW P. O. Box 2951 Washington, D.C.

20006 Beaumont, TX 77704 Mr. Les England Mr. William H. Spell, Administrator Director - Nuclear Licensing Nuclear Energy Division Gulf States Utilities Company Office of Environmental' Affairs P. O. Box 220 P. O. Box 14690 St. Francisville, LA 70775 Baton Rouge, Louisiana 70898 Richard M. Troy, Jr., Esq.

Assistant Attorney General in Charge Mr. J. David McNeill, III State of Louisiana Department of Justice William G. Davis, Esq.

234 Loyola Avenue Department of Justice New Orleans, Louisiana 70112 Atto.Pey General's Office 7434 Perkins Road Resident Inspector Baton Rouge, Louisiana 70808 P. O. Box.1051 St. Francisville, Louisiana 70775 H. Anne Plettinger 3456 Villa Rose Drive

, Gretchen R. Rothschild-Reinike Baton Rouge, Louisiana 70806 Louisianians for Safe Energy, Inc.

2108 Broadway Street New Orleans, Louisiana 70118-5462 President of West Feliciana Police Jury Regional Administrator, Region IV P. O. Box 1921 U.S. Nuclear Regulatory Commission St. Francisville, Louisiana 70775 Office of Executive Director for Operations Mr. Frank J. Uddo 611 Ryan Plaza Drive, Suite 1000 Uddo & Porter Arlington, Texas 76011 6305 Elysian Fields Avenue Suite 400 Philip G. Harris New Orleans, Louisiana 7012?

Cajun Electric Power Coop. Inc.

10719 Airline Highway P. O. Box 15540 Baton Rouge, LA 70895 i

f I

4 r