I ATTACliMENT 1 PROPOSED TECIINICA1. SPECIFICATIONS CliANGES Virginia Electric and Power Company l

890P290435 896223 PDR ADOCK 05000339' P

PNV :

l TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

Nominal Nominal I

Device Number Trip

Response

System and Location Setpoint Time Powered (Breaker No.)

(Amneres)

(Seconds)

(Mark No.)

1.

4160 VAC 25A3 Variabic 0.030*

2-RC-P-01A 25B3 Variabic 0.030*

2-RC-P-01B l

25C3 Variabic 0.030*

2-RC-P-01C

(

2 5111 4 Variable 0.030*

2 -Ril-P - 01 A i

25J14 Variabic 0.030*

2 - Ril-P- 01B i

2.

480 VAC from load centers i

I 24Al-2 9000 0.12 PRZR litrs, j

deleted j

1 24B1-2 5250 0.10 PRZR litrs.

deleted l

l 24C1-2 5250 0.055 PRZR litra.

24C2-16 3000 0.075 Refuel. & Maint. Power 24111-2 7500 0.06 2-RS-P-01A 24111-5 5250 0.057 2-IIV-F-01A I

2 4111 - 6 5250 0.10 PRZR IItrs.

24ti-7 5250 0.10 2 -IIV-F- 010

?4J1-2 7500 0.06 2-RS-P-01B 24J1-5 5250 0.057 2 -IIV-F-01B 24J1-6 5250 0.10 PRER litrs.

3.

480 VAC from MCC 2Al-1 AIL 800 0.060 Loop 1 Pwr Recepts.

2'l-102 250 0.060 MOV-CC-200A 1 a-1C3 250 0.060 MOV-IIV-200A 2Al-104 250 0.060 MOV-l[V-200C 2Al-1D3L 500 0.060 Incore Inst. Drive A 2Al-1E3 250 0.060 2 -IIV-F- 03 A 2Al-1F1 250 0.060 3-RC-P-01A1 l

2Al-1F3 500 0.060 2-RC-P-01A2 2Al-lF5 250 0.060 2-DA-P-04A 2B1-1A2 500 0.060 2-IIV-F-92C i

2B1-1B4L 250 0.060 Manip. Crane 2B1-1B4R 500 0.060 Fuel Transfer Cab.,

2B1-101 500 0.060 2-IIV-F-92B 2B1-1C2R 250 0.060 RCC Channe Fixture 2B1-103 500 0.060 2-IIV-F-92A

  • circuit dreaker Opening Time NORTil ANNA - UNIT 2 3/4 8-18 A

TABLE 3.8-1 (Continued) l CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES j

i Nominal Nominal Device Number Trip

Response

System and Location Setpoint Time Powered (Breaker No. )

(Amperes)

LSeconds)

IMark No.)

2B1-2 AIL 800 0.060 RllR Cub. Pwr. Recepts.

2B1-2A2R 800 0.060 Loop 2 Pwr. Recepts.

2B1-2A2L 500 0.060 Incore Inst. Drive B 2B1-2A3 2000 0.060 React. Cont. Crano 2B1-2C2 250 0.060 MOV-CC-200B 2B1-2E3 250 0.060 2-IIV-F-03B 2B1-2E4 250 0.060 3-RC-P-01B1 2B1-2E5 250 0.060 2-DA-P-04B 2B1-2F2 500 0.060 2-RC-P-01B2 2B1-2F4 250 0.060 2-DG-P-OLA 2Cl-1A3L 800 0.060 Cont. Elevator 2Cl-1B3R 500 0.060 Incore Inst. Drive C 2Cl-1B3L 500 0.060 Monorail Feeder 2C1-1C2 500 0.060 2-RC-P-01C2 2Cl-1D3 250 0.060 2-RC-P-01C1 2Cl-1E3 250 0.060 2-DA-P-05 2Cl-1E4 250 0.060 2-DG-P-01B l

2Cl-1A2L 800 0.060 Loop 3 Pwr. Recepts.

2Cl-4A1 250 0.060 2-NS-P-01A deleted l

2C2-1A2R 800 0.060 Port Crano Recepts, deleted deleted 2C2-1C1 250 0.060 2-NS-P-01B 2111-2NA1 2000 0.060 2 -IIV-F- 37A 2H1-2NA3 500 0.060 2-IA-C-02A 2ill-2NB1 2000 0.060 2-flV-F-37B 2H1-2NC4 2000 0.060 2-l[V-F-37C 2111-2 Nil 4 500 0.060 MOV-2665B 2111-2NK1 500 0.060 2-IA-C-02A 2H1-2NL3 500 0.060 MOV-2865A l

2111-2SB4 250 0.060 MOV-2536 2111-2SC1 500 0.060 MOV-2720A 2111-2SD1 250 0.060 MOV-2700 l

NORTil ANNA - UNIT 2 3/4 8-19 I

rysi t

ATTACllMENT 2 SAFETY EVALUATION i

)

'1 i

j i

1 Virginia Electric and Power Company j

1 i

l

- _ _ _ _.. - - - -. _ _ - - - - _ - - -. - - - _ - _ - _. - - - - - - - - - - - - - - - _ - _ _ - - _ - - - - - - - - - _ -. -. - - - - - - - - - -. - - - - - - - - - - - - - - - - - - - _ - - - - - - - - - - - - - - - - - - - - - - - - - _ - - - - - -. - - - - - - - - - - - - ~ - - - - - = - - - - - -

s.

DISCUSSION Technical. Specifications Section 3.8.2.$,

Table 3,8-1, specifies the trip point for the Containment Penetration Conductor Overcurrent Protective Devices. Included in this list are the Steam Generator Support Haaters which were removed in June 07, 1984, by Amendment 40 to the Technical Specification.

This change will remove the support heatars from the list.

In addition, the " System Pcwered (Mark No.)" for "Devico Number and Location (Breaker No.)",

2Cl-1A2L, is shown as ' " 2 -DA-P- 01B" whereas it should be "2-DG-P-01B". This is a typographical error.

BASIS FOR NO SIGNIFICANT llAZARDS DETERM1 NATION The proposed to correct the typographical error does not involve a significant

' hazards consideration because it is only a correction of an error and therefore is similar to 48FR14870, " Examples of Amendments That Are Not Likely To Involve Significant Hazards Considerations Are Listed Below", Example (1)

"A purely administrative change to technical sp3cifications: for example, a change to achieve consistency throughout the technical specifications, correction of an error, or a change in nomenclature."

The proposed deletion of the Steam Generator Support Heaters does not involve a significant hazarde consideration because operation of North Anna Unit 2 in accordance with this change would not:

(1) involve a significant increase in the probability or consequence of an accident previously evaluated, or (2) create the possibility of a new or different kind of accident from any accident previously identified, or (3) involve a significant reduction in a margin of safety because, this change only deletes the Overcurrent Protective Device Settings for the Steam Generator Support Heaters which were previously removed. This removal was approved by the NRC via license amendment 40, dated June 07, 1984.

Therefore, pursuant to 10 CFR 50.92, based on the above consideration, it has been determined that this change does not involve a significant hazards consideration.