Notice of Violation from Insp on 870601-05.Violation Noted:Failure to Follow ASME Section XI Code Requirement, Specifically Iwp 4111,during Testing of Emergency Svc Water Sys
ML20235L970
Person / Time
Site: Oyster Creek
Issue date: 07/08/1987
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20235L953 List:
References
50-219-87-20, NUDOCS 8707170008
Download: ML20235L970 (1)


Text

)

6 1

APPENDIX A NOTICE OF VIOLATION General Public Vtilities Docket No. 50-219 Oyster Creek Nuclear Generating Station

' License No. DPR-16 i

As a result of the inspection conducted on June 1-5, 1987, and in accordance with the' " General Statement of Policy and Procedure for NRC Enforcement Actions,"'10 CFR Part 2, Appendix C (Enforcement Policy) (1986), the following j

violation was identified:

I A.

10 CFR 50.55a(g)(4) requires pumps and valves classified as ASME Code I

Class 1 to be tested for operational readiness in accordance with Section i

XI of the ASME Boiler and Pressure Vessel Code. Technical Specifications 4.3C requires conformance with 10 CFR 50.55a(g), except where relief has been granted by the Commission The Emergency Service Water pumps are included as part of the licensee's Inservice Test Program and are thus subject to ASME Section XI, article IWP-4000, " Methods of Measurement." Subarticle IWP-4111. states that "the full range of each instrument shall not be greater than four times the reference value."

Contrary to the above, on June 2, 1987, a flow measurement test was performed on System II of the ESW System utilizing a gage (ESW-1) with j

a range'of greater than four times the established reference value.

i This is a Severity Level V Violation.

Pursuant to the provisions of 10 CFR 2.201, General Public Utilities is hereby required to submit to this office within thirty days of the date of the letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further violations;

)

and (3) the date when full compliance will be achieved.