ML20217C950
| ML20217C950 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 03/19/1998 |
| From: | FLORIDA POWER CORP. |
| To: | |
| References | |
| AR-801, NUDOCS 9803270255 | |
| Download: ML20217C950 (89) | |
Text
Document Transmittal #; 90883 Date: 3/23/98 Tc:
NRC (DC DESK)
MAC: N/A Destination:
==
Description:==
Copy Copy Totals Document:
Revision:
Comment:
INFO CNTL MSTR AR0801 11 24 1
0 0
instructions to the Addressee:
Please verify the document (s) received agrees with the above information.
Operations department must attach old document (s) or portions of document (s) superseded by the above g
to this transmittal.
II /
The signature indicates acknowledgment of receipt of the above document (s) and that documents have been updated. Rettm signed and dated transmittal to Document Control within 15 working days of transmittal date to mail code:
NA1C Florida Power Corporation h
Document Contr4 NA1C
.,,' O ()
Crystal RNor Energy complex
'~;gVJ4 15760 W, Power Line St.
Crystal RNor, FL 34426 6708 Signature of Addressee:
Date:
9903270255 990319 PDR-ADOCK 05000302
. P. -
PDRi
Rev. 11 U
Effective Date
~ 3" "INFORMATION ONLY m
ANNUNCIATOR RESPONSE AR-801 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 FSA ANNUNCIATOR RESPONSE i
)
APPROVED BY:
Interpretation Contact q x w / S W fg >, / [/t (SIGNATURE N FILE)
/
DATE:
E E
INTERPRETATION CONTACT:
Manager, Nuclear Plant Operations Support l.
-- =---------------J
TABLE OF CONTENTS qV SECTION PAGE 1.0 PURPOSE.................................................................
1
2.0 REFERENCES
.............................................................~. 1 2.1 IMPLEMENTING REFERENCES.............................................
1
~
2.2 DEVELOPMENTAL REFERENCES............................................
1 3.0 PERSONNEL INDOCTRINATION.................................................
4.O INSTRUCTIONS............................................................
1 5.0 FOLLOW-UP ACTIONS.......................................................
1 ENCLOSURE 1
An n u n c i at o r R e s po n s e................................................ 2 (t
. /m
./
\\%
AR-801-Rev. 11 Page i t:
1.0 PURPOSE
-[
\\s-1.1 Establish a reference document for each Annunciator Window on the FSA Lampbox.
1.2 Establish operator actions for valid Annunciator alarms on the FSA Lampbox.
1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the FSA Lampbox.
2.0 REFERENCES
2.1 IMPLEMENTING REFERENCES 2.1.1 AP-880, Fire Protection 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures
$s 2.2.2 Annunciator Window Engraving Drawing E-224-050 s,
l2.2.3 Calculation I-95-0007 R-0, EFW Source Volumes 3.0 PERSONNEL INDOCTRINATION 3.1 The Fire Service Annunciator System is powered from ACDP-40 Breaker 19.
4.0 INSTRUCTIONS 4.1 Respond to alarms on the FSA Lampbox as indicated on Enclosure 1, Annunciator Response.
5.0 FOLLOW-UP ACTIONS None y
g.
1
\\)
AR-801 Rev. 11 Page 1
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-01 FS-01-01 FIRE WTR TANK 3A LEVEL LOW I
]
INDICATED CONDITION: TANK LEVEL s35'7" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-47-LS
.{%
AR-801 Rev. 11 Page 2
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-02 FS-01-02 FIRE WTR TANK
' 38 LEVEL LOW INDICATED CONDITION: TANK LEVEL s35'7" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:. REFIl L TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-48-LS fb l
ye AR-801' Rev. 11 Page 3
i I
Q FIRE SYSTEM ANNUNCIATOR RESPONSE FS 04 FS-01-04 CO2 TANK PRESS Hl/LO INDICATED CONDITION: CARD 0X TANK PRESSURE RELAY RAR ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-1-2 ALARM
/N
- LOCAL PRESSURE INDICATOR CO-1-PI G
I OPERATOR ACTION FOR A VALID ALARM:
- WALK DOWN CO SYSTEM AND ENSURE NO LEAKS
- ENSURE PROPER OPERATION OF CARDOX UNIT DISCUSSION: CARD 0X TANK RELAY RAR IS ACTUATED WHEN CARD 0X TANK PRESSURE AS SEEN BY CO-1-PS1 IS 2325 PSIG OR s275 PSIG.
REFERENCES:
DWG 208-031 FS-21, DWG FL-16996 4 SENSING ELEMENT: CARD 0X TANK RELAY RAR AR-801 Rev. 11 Page 4
FIRE. SYSTEM ANNUNCIATOR RESPONSE FS-01-05 FS-01-05 PUMP TEST RET WATER TO TANK 4
INDICATED CONDITION: FLOW IN FIRE SERVICE RECIRC LINE 2540GPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-12-FS
- n x >.
- AR-801'-
Rev. 11-Page 5
/
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-07 FS-01-07 FREON SYSTEM ACTIVATED s1 INDICATED CONDITION: FREON SYSTEM ACTIVATED IN CABLE SPREADING ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
A'd OPERATOR ACTION FOR A VALID ALARM: NOTIFY FIRE BRIGADE TO INSPECT CABLE SPREADING ROOM.
REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: KIB FREON SYSTEM INTERFACE FIRING UNIT
.AR-801~
Rev. 11 Page 6
FIRE' SYSTEM ANNUNCIATOR RESPONSE FS-01--08 FS-01-08 FDWTR PP & TUR8 DR 3A (HAZ 1)
INDICATED CONDITION: CARD 0X HAZARD ZONE 1 RELAY PE ACTUATED (FWP-2A)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-1-1 ALARM
- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2A
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-3-TS1 THROUGH CO-3-TS7.
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 1 RELAY PE g '
h i
1 i
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-09 FS-01-09 4
FDWTR PP & TURB DR 3B (HAZ-2)
INDICATED CONDITION: CARD 0X HAZARD ZONE 2 RELAY PE ACTUATED (FWP-28)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
. CARD 0X PANEL WINDOW CO-2-1 ALARM
- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2B
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARDOX SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-4-TS1 THROUGH CO-4-TS7
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 2 RELAY PE AR-801_'.
Rev. 11 Page 8
e FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-10 FS-01-10 TUR8 GEN BRGS 1-5 (HAZARD-3)
INDICATED CONDITION: CARD 0X HAZARD ZONE 3 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARDOX PANEL WINDOW CO-3-1 ALARM
- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 1 THROUGH 5
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED
- REFER TO AP-880 (FP).
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-5-TS1 THROUGH CO-5-T54
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 3 RELAY PE 1AR-801 Rev. 11 Page 9
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-11 FS-01-11 TURB GEN BRGS 6-9 (HAZARD-4)
INDICATED CONDITION: CARD 0X HAZARD ZONE 4 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
- CARD 0X PANEL WINDOW CO-4-1 ALARM
- 1OCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:
- LOCALLY VERIFY CARDOX SYSTEM ACTUATION ON TURBINE GENERATOR BEARINGS 6 THROUGH 9
- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW 15 REQUIRED
- REFER TO AP-880 (FP)
DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE DETECTORS CO-6-TS1 THROUGH CO-6-T54
REFERENCES:
DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 4 RELAY PE AR-801 Rev. 11 Page 10
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-13 FS-01-13 FIRE PUMP 3B RUNNING INDICATED CONDITION: POWER IS APPLIED TO FSP-1 MOTOR AND FSP-1 PUMP SHOULD BE RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/~
/
OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 0I-13.
REFERENCES:
DWG 208-031 FS-14, FS-03 SENSING ELEMENT: mal-1 I
l
?
1 AR-801-Rev. 11 Page 11
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-14 FS-01-14 FIRE PUMP 3B CONTR PWR OFF INDICATED CONDITION: CONTROL POWER TO FSP-1 IS OFF OR RELAY FAILURE (ACDP 7 BREAKER #9)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OO.
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION:
REFERENCES:
DWC 208-031 FS 14, FS-04 SENSING ELEMENT: mal-1 i
AR-801 Rev. 11' Page 12
q 4-t FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-15 FS-01-15 CABLE SPR ROOM AUTO FANS OFF INDICATED CONDITION: SELECTOR SWITCH PLACED IN THE "OFF" POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
\\.
OPERATOR ACTION FOR-A VALID ALARM: VERIFY SELECTOR SWITCH IS IN THE AUTO POSITION. INSTALL TEMPORARY FANS IF NECESSARY.
DISCUSSION:
REFERENCES:
SENSING ELEMENT: FSE-592 j
I (J
R AR'-801 Rev. 11 Page 13
5 i
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-16 FS-01-16 F.S. TANK INSTR HEAT. TRACE Fall INDICATED CONDITION: OUTSIDE AIR TEMP 534 DEG F; HEAT TRACE FAIL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: DETERMINE IF TEMP REQUIRES A CHANGE IN THE FIRE SERVICE SYSTEM LINEUP. CHECK HEAT TRACE LINES.
DISCUSSION: CHECK METEOROLOGICAL STATION INDICATION l
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-49-TS l
- O.Q AR-801':
Rev 11 Page 14 a :-
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-01 FS-02-01
m.===
l FIRE PUMP 3A OVERSPEED INDICATED CONDITION: FSP-2A OVERSPEED 22100 RPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
J f~'
I,q OPERATOR ACTION FOR A VALID ALARM:
i DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH i
l
[\\J l
AR-801' Rev. 11 Page 15
FIRE SYSTEM-ANNUNCIATOR RESPONSE FS-02-02 FS-02-02 FIRE PUMP 3A HI WATER TEMP INDICATED CONDITION: HI WER TEMP ON COOLING WTR 2190 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM; OPERATOR ACTION FOR A VALID ALARM: CHECK WATER LEVEL IN DIESEL COOLING SYSTEM.
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-2-7, FS-01 i
SENSING ELEMENT: FS-15-TS l
9 AR-801' Rev. 11.
Page 16
,J
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-03 FS-02-03 FIRE PP 3A LO LUBE OIL PRESS J
INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: REFILL WITH OIL IF NECESSARY.
DISCUSSION:
REFERENCES:
-DWG 208-031 FS-2-7. FS-01 SENSING ELEMENT: FS-40-PS 9
AR-801-Rev. 11 Page 17
FIRE SYSTEM ANNUNCIATOR RESPONSE' FS-02-04 FS-02-04 FIRE PUMP 3A NOT IN AUTO INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: RETURN SWITCH TO AUTO DISCUSSION:
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: C5
.-w AR-801' Rev. 11-Page 18
(. _, /
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-05 FS-02-05 FIRE PUMP 3A Fall TO START INDICATED CONDITION: PUMP NOT RUNNING UP TO SPEED 90 SECONDS AFTER DIESEL RECEIVES AN AUTO START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
,-_s
)
' ^ '
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO RESET ALARM
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 7R i
AR-801 Rev. 11 Page 19
FIRE ~ SYSTEM ANNUNCIATOR RESPONSE FS-02-06 FS-02-06 FIRE PUMP 3A RUNNING INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i(
OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
FIRE PUMP HOUSE FANS (AHF-33A & AHF-338) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 01-13.
REFERENCES:
DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 15R
\\J AR-80'1 Rev. 11' Page 20
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-07 FS-02-07
.u.
FIRE PUMP 3A FUEL LEVEL LO INDICATED CONDITION: FUEL TANK LEVEL s66.5% FULL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID. ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-13-LS f t]
(/ '
- AR-801 ~
Rev. 11 Page 21
(d l
\\
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-09 FS-02-09 FIRE PUMP 3C OVERSPEED INDICATED CONDITION: FSP-2B OVERSPEED 22100 RPM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWC 208-031 FS-8-13, FS-02 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH I
f AR-801 Rev. 11 Page 22 A
)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-10 FS-02-10 FsRE PUMP 3C HI WATER TEMP INDICATED CONDITION: HI WATER TEMP ON COOLING WTR 2190 DEG F
) ~
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK WATER LEVEL IN DIESEL COOLING SYSTEM.
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: FS-16-TS AR-801 Rev. 11 Page 23
c.-
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-11 FS-02-11
.x.....-
FIRE PP 3C LO LUBE OIL PRES INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O Qi OPERATOR ACTION FOR A VALID ALARM: REFILL WITH OIL IF NECESSARY DISCUSSION:
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: FS-41-PS r
4 i
((')
- . ( /
AR-801 Rev, 11 Page 24
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-12 FS-02-12 FIRE PUMP 3C NOT IN AUTO INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
OPERATOR ACTION FOR A VALID ALARM: RETURN TO AUTO DISCUSSION:
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: CS
}
'\\
)
.AR-801L Rev. 11 Page 25
)
FIRE' SYSTEM ANNUNCIATOR RESPONSE FS-02-13 FS-02-13 1
)
FIRE PUMP 3C FAIL TO START INDICATED CONDITION: DIESEL NOT UP TO SPEED AND RUNNING 90 SECONDS AFTER RECEIVING AN AUTO START SIGNAL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:
DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: RELAY 7R V
.AR-801'-
Rev. 11 Page 26
Ds Q!
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-14 FS-02.
FIRE PUMP 3C RUNNING INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OQ OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:
FIRE PUMP HOUSE FANS (AHF-33A & AHF-338) ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD WEATHER OPERATIONS PER 01-13
REFERENCES:
DWG 208-031 FS-8-13, FS-02 SENSING ELEMENT: RELAY 15R l
4
. []
' (,/ -
)
AR-801E Rev. 11 Page 27 r..
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-15 FS-02-15 FIRE PUMP 3C FUEL LEVEL LO h
INDICATED CONDITION: FUEL TANK LEVEL s50% FULL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:
REFERENCES:
DwG 208-031 FS-21 SENSING ELEMENT: FS-14-L5 i
)
J
.g).
L
^ AR-801.-
Rev. lle Page 28
]
l i
l
)
i f')
V.
' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-01 FS-03-01 MN TRANSF 3-1 FIRE SYS TRBL INDICATED CONDITION: MAIN TRANSFORMER #3-1 DELUCE VALVE (FSV-69) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-68), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-5,'FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 1
%s AR-801~
Rev. 11' Page 29
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-02 FS-03-02 MN TRANSF 3-2 FIRE SYS TRBL INDICATED CONDITION: MAIN TRANSFORMER #3-2 DELUGE VALVE (FSV-66) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-65), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-6, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5
'AR-801 Rev. 11 Page 30
p(,)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-03 FS-03-03 MN TRANSF 3-3 FIRE SYS TRBL INDICATED CONDITION: MAIN TRANSFORMER #3-3 DELUGE VALVE (FSV-64) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-63), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-07, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5
.l0' AR-801-Rev. 11 Page 31
(
FIRE' SYSTEM ANNUNCIATOR RESPONSE FS-03-04 FS-03-04 UNIT TRANSF 3 FIRE.SYS TR8L INDICATED CONDITION: UNIT AUX TRANSFORMER DELUGE VALVE (FSV-72), LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-71), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
1
REFERENCES:
DWG 208-031 FS-08, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 1
AR-801 Rev. 11 Page 32
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-05 FS-03-05 STRT-UP TRAN 3 FIRE SYS TRBL INDICATED CONDITION: START UP TRANSFORMER DELUCE VALVE (FSV-61) LOSS OF POWER TO CIRCUIT ISOLATION VALVE NOT OPEN (FSV-60), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-09, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 f
AR-801 Rev. 11 Page 33
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-06 FS-03-06 WATER CURTAIN TROUBLE I
INDICATED CONDITION: TURBINE BUILDING WATER CURTAIN DELUGE VALVE (F5V-239)
LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-238), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWC 208-031 FS-22, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 i
Il if
)
AR-801 Rev. 11 Page 34
4 9
FIRE SYSTEM ANNUNCIATOR RESPONSE F5-03-07 FS-03-07 TURB LUBE CHL RRE SYS TRBL INDICATED CONDITION: TURBINE LUBE OIL DELUGE VALVE (FSV-10) LOSS OF POWER TO CIRCUIT ISOLATION VALVE NOT OPEN (FSV-108), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-10, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 O
' AR-801 Rev. 11 Page 35
i I
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-08 FS-03-08 FEEDWTR PUMP FIRE SYS TRBL INDICATED CONDITION: FEEDWATER PUMP CONSOLES DELUGE VALVE (FSV-67) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-62), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-10, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5 J-AR-801 Rev. 11-Page 36
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-09 FS-03-09 H2 SEAL OIL FIRE SYS TRBL INDICATED CONDITION: HYDROGEN SEAL OIL DELUGE VALVE (FSV-82) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-83), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-12, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: K-2, K-5
' \\.J AR-801' Rev. 11 Page 37
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-10 FS-03-10 8/U ES XFAAR
.TR8L INDICATED CONDITION: BACKUP ES TRANSFORMER DELUGE VALVE (FSV-832) LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN (FSV-831), OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-22, FD-302-231 SHT 01 0F 05 SENSING ELEMENT: FSCP-4
(
i AR-801:
Rev. 11 Page 38
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-11 FS-03-11
/
j FIRE PUMP HSE SPRINKLER ACT i
INDICATED CONDITION: FIRE PUMP HOUSE SPRINKLER SYSTEM ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALAw..
OPERATOR ACTION FOR_ A VALID ALARM: CHECK INDICATED AREA FOR FIRE DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-17-PS
'AR-801 Rev. 11 Page 39
(
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-12 FS-03-12 RB MAINT BLD SPRINKLER ACT INDICATED CONDITION: FIRE SPRINKLER SYSTEM HAS ACTUATED IN THE.RB MAINTENANCE SUPPORT BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM: SPRINKLER SYSTEM PRESSURIZED
/^)
TO >30 PSIG OPERATOR ACTION FOR A VALID ALARM: CHECK RBMSB FOR FIRE DISCUSSION:
]
)
REFERENCES:
55 211-031 FS-02 I
SENSING ELEMENT: FS-508-PS2 i
,t
\\u -
AR-801 Rev. 11 Page 40 i
4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-13 FS-03-13 TURB BLDG BEL 119' SPR ACT INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION ACTUATED 210 PSIG
,q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
"Q OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-24-PS
,,1f AR-801 Rev. 11-Page 41
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-14 FS-03-14 TURB BLDG BEL 119' SPR ACT INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATION ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 l
SENSING ELEMENT: FS-25-PS D.()-
AR-801 Rev. 11-Page 42
i
'_i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-15 FS-03-15 x
-l OUTAGE SUPP BLDG FIRE I
l i
INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN OUTAGE SUPPORT BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
r'^s
)
)
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA FOR FIRE. REFER TO
~'
AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 211-031 FS-076 SENSING ELEMENT: FS-472-F5
)
/
AR-801 Rev. 11 Page 43
n
(
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-01 FS-04-01 MAIN TRANSF 3-1 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
p.
(
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-05 SENSING ELEMENT: K-4 i
l
- f~'
'l AR-801 Rev.-11 Page 44-
f3 k/
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-02 FS-04-02 s
MAIN TRANSF 3-2 FHRE INDICATED CONDITION: DELUGd VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O.-
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-06 SENSING ELEMENT: K-4
.l'
./~
AR-8011 Rev. 11 Page 45
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-03 FS-04-03 MAIN TRANSF 3-3 FIRE -
INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-07 SENSING ELEMENT: K-4
'AR-801 Rev. 11 Page 46
i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-04 FS-04-04 UNIT TRANSF 3 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-08 SENSING ELEMENT: K-4
'n t
IAR-80i' Rev. 11-Page 47
Q)
./
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-05 FS-04-05 STARTUP TRANSF 3 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA, REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-09 SENSING ELEMENT: K-4 ge k,-
AR-801 Rev. 11 Page 48
FIRE. SYSTEM ANNUNCIATOR RESPONSE FS-04-06 FS-04-06 WATER CURTAIN FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-22 SENSING ELEMENT: K-4
}']
%J:
AR-801 Rev. 11 Page 49
lg
~~
.,u Y_
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-07 FS-04-07 TURB LUBE OIL SYSTEM FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO
__,j AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-10 SENSING ELEMENT: K-4 AR-801 Rev. 11 Page 50
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-08 FS-04-08 FEEDWTR PUMP CONSOLE FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-11 SENSING ELEMENT: K-4
' If()
AR-801'-
Rev-, 11~
Page 51
~
(j FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-09 FS-04-09 H2 SEAL OIL UNIT FIRE INDICATED CONDITICN: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS SENSING ELEMENT.: K-4
- /~j A__f 1
IAR-801' Rev. 11 Page 52
(%.
s,,)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-10 FS-04-10.
B/U ES XFMR FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH HELL VERIFY ALARM:
()
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-040 MT-140 SENSING ELEMENT: FSCP-4
- f '.).
-i.\\.4 AR-801 Rev. 11 Page 53
FIRE SYSTEM ANNUNCIATOR RESPONSE-FS-04-11 FS-04-11 TURB BLDG BEL 145' SPR ACT INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
AV OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-26-FS O
L)
-AR-801[
Rev. 11 Page 54
Ch
\\,_)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-12 FS-04-12 TURB BLDG BEL 145' SPR ACT INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SEN5ING ELEMENT: FS-27-FS ur~
, k.
.AR-801 Rev. 11 Page 55
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-13 FS-04-13 CONT COMP BEL 108' SPR ACT INDICATED CONDITION: CONTROL COMPLEX BELOW 108' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
^r)
OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: FS-33-FS 4
%J
'-AR-801' Rev. 11 Page 56-
- =
=
7~
'g' '.
FIRE SYSTEV ANNUNCIATOR RESPONSE FS-05-01 FS-05-01 CHARCOAL FLTR AHFL-1 TRBL INDICATED CONDITION: PURGE EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f}s.
i,'
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-24, FS-13 SENSING ELEMENT: K-2, K-5 4
,'Q -
- AR-801 Rev. 11 Page 57
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-02 FS-05-02
.s...
CHARCOAL FLTR AHFL 2A TRBL INDICATED CONDITION: AUX BLDG MAIN EXHAUST GIARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:
l
)
REFERENCES:
DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-2, K-5 t
.{%
AR-801 Rev. 11 Page 58 l
1
A-h
. FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-03 FS-05-03 CHARCOAL FLTR
- AHFL-2B TRBL INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
p i
1 V
OPERATOR ACTION-FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-15 SENSING ELEMENT: K-2, K-5
\\
i
/%, '
AR-801' Rev. 11 Page 59
A(,,)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-04 FS-05-04 CHARCOAL FLTR AHFL-2C TRBL INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARC0AL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH HELL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-16 SENSING ELEMENT: K-2, K-5 f)
,.__j.
AR-801 Rev. 11 Page 60
- p..
<b FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-05 FS-05-05 CHARCOAL FLTR AHFL-2D TRBL INDICATEF CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
gU OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-17 SENSING ELEMENT: K-2, K-5 s
AR-801 Rev. 11 Page 61
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-06 FS-05-06 CHARCOAL FLTR AHFL-4A TRBL -
INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARC0AL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-18
.5ENSING ELEMENT: K-2, K-5 D.
\\
AR-801 Rev. 11 Page 62
rh k,,)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-07 FS-05-07 CHARCOAL FLTR Au1FL-4B TRBL INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-19 SENSING ELEMENT: K-2, K-5 AR-80I Rev. 11 Page 63
O V
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-08 FS-05-08 CHARCOAL FLTR AHFL 15 TRBL INDICATED CONDITION: NUCLEAR SAMPLE ROOM CHARC0AL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:
REFERENCES:
DWG 208-031 FS-20 SENSING ELEMENT: K-2, K-5 l
u
\\
i nU l
AR-801
'Rev. 11' Page 64
R Ed FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-09 FS-05-09 ADMIN BLDG WAREHOUSE FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN WAREHOUSE OR ADMIN BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
)
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
SENSING ELEMENT:
v AR-801 Rev. 11 Page 65
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-10 FS-05-10 OFFICE BLDG TROUBLE / FIRE INDICATED CONDITION: RUSTY BUILDING FIRE OR INSTRUMENT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR'A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 1-3 ALARM
[\\.y AR-801.
Rev. 11 Page 66
(n)
FIRE SYSTEM ANNUNCIATOR RESPONSE' FS-05-11 FS-05-11 CONTROL BLDG TROUBLE / FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN CONTROL BLDG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
[(h)
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 4-11 ALARM i
1
)
AR-801 Rev. 11 Page 67
4 I
O)
\\,
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-12 FS-05-12
~
SWITCH GEAR RM TROUBLE / FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: ZONE 12-13 ALARM A
N_]
'AR-801 Rev. 11 Page 68
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-13 FS-05-13 FIRE PROT TROUBLE INDICATED CONDITION: FIRE PROTECTION TROUBLE PLANT OR OFFICE AREA CAB REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ALARM PANELS LOCATED ON 124' ELEV. CONTROL COMPLEX AND 1st FLOOR OF RUSTY BLDG IN TELEPHONE TERMINATION OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION: THIS ALARM MAY COME IN WHEN THE HALON PROTECTION SYSTEM IS PLACED IN " TEST"
REFERENCES:
DWG 208-031 FS-21 SENSING ELEMENT: PLANT AREA CAB, OFFICE AREA CAB I
~
l
)
v AR-801 Rev. 11 Page 69
l l
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-14 FS-05-14 EMER DSL GEN ROOM TROUBLE INDICATED CONDITION: LOSS OF POWER OR CIRCUIT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
DWG 208-031 FS-23 SENSING ELEMENT: OR, RSR, TSR
.,rh ks} '
AR-801-~
Rev.'11 Page 70
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-15 FS-05-15 EMER DSL GEN ROOM FIRE INDICATED CONDITION: ONE OF TWENTY SENSORS HAS ACTUATED. FSV-101 SHOULD BE OPEN.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:
REFERENCES:
DWG 208-031 FS-23 SENSING ELEMENT: OR
[)\\
AR-801.
Rev. 11 Page 71
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-01 FS-06-01 CHARCOAL FLTR AHFL-1 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-24, FS-13 SENSING ELEMENT: K-4 1
i
/^
(_.%.
/
AR-801.
Rev.-11 Page.72
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-02 FS-06-02 CHARCOAL FLTR.
AHFL-2A FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWC 208-031 FS-25, FS-14 SENSING ELEMENT: K-4 4
AR-801 Rev. 11 Page 73
()
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-03 FS-06-03 CHARCOAL FLTR AHFL-2B FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(V OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-15 SENSING ELEMENT: K-4 4p
'()
j AR-801 Rev. 11 Page 74 i
]
I FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06 FS-06-04 CHARCOAL FLTR AHFL-2C FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/~N,
'V OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-16 SENSING ELEMENT: K-4 I
I A..
h.
AR-801 Rev. 11 Page 75
O
- b. _
e FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-05 FS-06-05 CHARCOAL FLTR AHFL-2D FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM:. INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWC 208-031 FS-17 SENSING ELEMENT: K-4 N,,
-.AR-801 Rev. 11 Page 76
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-06 FS-06-06 CHARCOAL FLTR AHFL-4A FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA, REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-18 SENSING ELEMENT: K-4
- (")
V
~AR-801 Rev. 11 Page 77
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-07 FS-06-07 m.. -
CHARCOAL FLTR AHFL-48 FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-19 SENSING ELEMENT: K-4 O
( /:
AR-801.
Rev. 11 Page 78
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-08 FS-06-08 CHARCOAL FLTR AHFL-15 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DWG 208-031 FS-20 SENSING ELEMENT: K-4
-[N.)
AR-801 Rev. 11 Page 79
)
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-09 FS-06-09 TSC TROUBLE INDICATED CONDITION: ALARM AT PYROTRONICS PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
)
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FIRE SYSTEM DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL AR-801-Rev. 11 Page 80 L-
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-10 FS-06-10 TSC FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN TSC REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OQ OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC AREA DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL
'\\ )
AR-801 Rev. 11 Page 81
4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-11 FS-06-11 TSC FILTER AHFL-20 TROUBLE INDICATED CONDITION: ALARM AT LOCAL PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:
REFERENCES:
DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL y
NJ l
AR-801 Rev. 11 Page 82
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-12 FS-06-12 TSC FILTER AHFL-20 FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN AHFL-20 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
.O
^
ig OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:
REFERENCES:
209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL ex i
AR-801 Rev. 11 Page 83
-[v.
FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-13 FS-06-13 RECORD STORE VAULT FIRE INDICATED CONDITION: WATER FLOW INTO RECORD VAULT SPRINKLER SYSTEM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA FOR FIRE.
NOTIFY ADMINISTRATIVE SUPERVISOR.
DISCUSSION:
1
REFERENCES:
DWG 208-031 FS-21
]
SENSING ELEMENT: FS-70-FI l
()s..
l AR-801 Rev. 11 Page 84 1
a
' FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-14 FS-06-14 CONT COMPLEX FIRE INDICATED CONDITION: DELUCE VALVE SHOULO BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
)
OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 (FP)
DISCUSSION:
REFERENCES:
DwG 208-031 FS-24 SENSING ELEMENT: K-4
.Q
'sY AR-801 Rev. 11 Page 85
t FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-15 FS-06-15 l
CONT COMPLEX FIRE SYS TRBL l
l l
INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE I
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O 1
OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING.
INVESTIGATE LOSS OF CONTINUITY IN HALON SYSTEM FIRING CIRCUIT.
DISCUSSION:
REFERENCES:
DWG 208-031 FS-24 SENSING ELEMENT: K-5, K-2 O
'AR-801' Rev. 11 Page 86 (LAST PAGE)