'o

}

i 4

APPENDIX B NOTICE OF DEVIATION Northeast Nuclear Energy Company Docket No. 50-336 Millstone Nuclear Power Station Unit 2 License No. DPR-65 i

During a routine resident inspection from August 21 - October 1, 1990, the following deviation was identified:

Licensee technical specification amendment submittals on June 24, 1985, and May 21, 1986, committed to provide direct dosimetry measurements of cumulative gamma exposure as part of the spent fuel pool boraflex coupon surveillance program. The proposed submittals were approved by the NRC staff as issued in technical specification amendments 109 (January 15, 1986) and 117 (June 2, 1987).

Contrary to the above, since the start of the boraflex surveillance program on May 6, 1987, per surveillance procedure SP 21026 " Spent Fuel Pool Poison Coupon Surveillance System," direct dosimetry measurements were not used to establish an accurate record of cumulative gamma exposure to the spent fuel pool boraflex coupons.

Northeast Nuclear Energy Company is hereby required to submit to this office, within thirty days of receipt of the letter which transmits this Deviation, a written reply, including:

(1) the corrective steps which have been taken and the results achieved; (2) corrective stepc which will be taken to avoid tsrther deviations; and, (3) the date when full compliance will be achieved. Whert good cause is shown, consideration will be gi en to extending this response time.

0011200182 901105 FDR ADOCK OS00j:lg36