Rev 26 to AR-305, Es E Annunciator Response
ML20216J169
Person / Time
Site: Crystal River 
Issue date: 04/14/1998
From:
FLORIDA POWER CORP.
To:
References
AR-305, AR-305-R26, NUDOCS 9804210319
Download: ML20216J169 (57)


Text

_

Document Transmittal #: 92954 Date: 4/14/98 To:

NRC (DC DESK)

MAC: N/A Destination:

==

Description:==

Copy Copy Totals Document:

Revision:

Comment:

INFO CNTL MSTR AR0305 26 24 1

0 0

Instructions to the Addressee:

Please verify the document (s) received agrees with the above information.

Operations department must attach old document (s) or portions of document (s) superseded by the above to this transmittal.

The signature indicates acknowledgment of receipt of the above document (s) and that documents have been updated. Retum signed and dated transmittal to Document Control within 15 working days of transmittaldate to mailcode:

,(){\\{

NA1C j

~n Florkia Power Corporation

' y v ()

Document Control, NA1C Crystal River Energy Complex 15760 W. Power Line st.

Crystal River, FL 34428-6708 Signature of Addressee:

Date:

9804210319 980409 PDR ADOCK 05000302 p

PDR f

l

r l

M O

2' Effective Date l

l l

INFORMATION ONLY ANNVNCIATOR RESPONSE AR-305 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 ES E ANNUNCIATOR RESPONSE APPROVED BY:

Interpretation Contact

& Nk blAF (SIGNAT RE ON FILE) /

k/.f, [ 9(~~

DATE:

INTERPRETATION CONTACT:

Manager, Nuclear Plant Operations Support

I i

i

/"

(

TABLE OF CQNTENTS s

I i

SECTION PAGE l

1.0 PURP0SE.................................................................

1

2.0 REFERENCES

1 2.1 IMPLEMENTING REFERENCES.............................................

1 2.2 DEVELOPMENTAL REFERENCES............................................

1 1

1 3.0 PERSONNEL INDOCTRINATION................................................

2 4.0 INSTRUCTIONS............................................................

2 5.0 FOLLOW-UP ACTI0NS.......................................................

2 ENCLOSURE 1

An n u n c i a to r Re s pon s e............................................... 3 b

's 1

t i

l l

l l

I i

1 t

i 1

l l 0

\\

~

l i

i AR-305 Rev. 26 Page i

1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the ES (B)-JH2 Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the i

ES (B)-JH2 Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the ES(8)-JH2 Lampbox.

1

2.0 REFERENCES

2.1 IMPLEMENTING REFERENCES 2.1.1 E0P - EMERGENCY OPERATING PROCEDURE 2.1.2 OP-703 - Plant Distribution System 2.1.3 OP-608 - OTSGs and Main Steam Systems 2.1.4 OP-402 - Makeup and Purification Systems l2.1.5 EM-308 - Containment Operating Procedure 2.1.6 AR-902 - DG 'B' Annunciator Response 2.1.7 OP-401 - Core Flood System 2.1.8 AP-770 - Emergency Diesel Generator Actuation 2.1.9 OP-707 - Operation of the ES Emergency Diesel Generator 2.2 DEVELOPMENTAL REFERENCES I

2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 l

2.2.3 MAR 94-07-07-01 CFT Level Setpoint l

l 2.2.4 REA #930926 regarding operation of the RB Main Fan Assemblies O

AR-305 Rev. 26 Page 1

3.0 PERSONNEL INDOCTRINATIQN 3.1 The Anr.unciator System is powered from VBDP-5 Breaker 28.

4.0 INSTRUCTIQN_5 4.1 Respond to alarms on the ES(B)-JH2 Lampbox as indicated on Enclosure.1, Annunciator Response.

t 5.0 FOLLOW-UP ACTIQNS None O

O AR-305 Rev. 26 Page 2

ENCLOSURE 1

/

(,/

(Page 1 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-01-01 E-01-01 l

l M

RB SPRAY i

ES B ACTUATION I

i EVENT POINT 0936

{

INDICATED CONDITION:

o 30 PSIG REACTOR BUILDING PRESSURE SETPOINT HAS BEEN EXCEEDED AS SENSED BY TWO OUT OF THREE RB PRESSURE SWITCHES (BS-21/22/23-PS)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES STATUS LIGHTS FOR RB SPRAY o BUILDING SPRAY PUMP IS RUNNING IF A RB SPRAY PERMISSIVE IS PRESENT o RB PRESSURE CONTROL BOARD INDICATOR BS-91-PI, BS-17-PI o COMPUTER POINT P-254 OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

HPI ACTUATION THROUGH BLOCK 6 WILL GIVE A BUILDING SPRAY PERMIT l

ACTUAL SETPOINT IS 2 24.5 PSIG i 1.4 PSIG i

i

REFERENCES:

DRAWING 208-028 SHEET ESB-70

(~N SENSING ELEMENT: 63-Z1/RB-4,RB-5,RB-6 ES ACTUATION RELAYS, BS-21-PS,

(

BS-22-PS.AND BS-23-PS AR-305 Rev. 26 Page 3 i

l

]

1

/

\\

ENCLOSURE 1 lV (Page 2 of 52) l ESE ANNUNCIATOR RESPONSE ESB-3H2-01-02 E-01-02 l

l l

l RB SPRAY PP B TRIP EVENT POINT 0046 INDICATED CONDITION:

o BSP-1B BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION I

('

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

\\.'

o GREEN LIGHT ON WITH A RED FLAG ON BSP-1B CONTROL STATION o ES STATUS LIGHT OPERATOR ACTIONS FOR A VALID ALARM:

o HAVE BREAKER CUBICLE CHECKED FOR DROPPED RELAY TARGETS DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS

REFERENCES:

DRAWING 208-009 SHEET BS-02

('g SENSING ELEMENT: CS/SC, CS/0 (CONTROL SWITCH CONTACTS) 525, 52H U

AR-305 Rev. 26 Page 4

ENCLOSURE 1

(~

(Page 3 of 52)

(

ESE ANNUNCIATOR RESPONSE ESB-JH2-01-03 E-01-03 i

RB SPRAY PP B MOTOR OVERLOAD EVENT POINT 0060 INDICATED CONDITION:

o MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH BUILDING SPRAY FLOW AS SEEN ON BS-01-FI2 o HIGH MOTOR AMPS o BSP-1B TRIP OPERATOR ACTIONS FOR A VALID ALARM:

o THROTTLE BSV-4 TO REDUCE LOAD ON BSP-1B o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o IF LOAD REMAINS HIGH CONSIDER TRIPPING BSP-1B DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVER CURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

l

REFERENCES:

DRAWING 208-009 SHEET BS-02

(

SENSING ELEMENT: S1-IOC(INSTANTANEOUS) 51-TOC (TIMED) BREAKER CONTACTS i.,

AR-305 Rev. 26 Page 5

ENCLOSURE 1

"')

[V (Page 4 of 52)

ESE ANNUNCIATOR RESPONSE ESB-J H2-01-04 E-01-04 RB SPRAY PP B OOT OF SERVICE EVENT POINT 0045 INDICATED CONDITION:

o BSP-1B BREAKER IS RACKED OUT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

e-o NO INDICATING LIGHTS ON CONTROL STATION o NO ES STATUS INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS l

REFERENCES:

DRAWING 208-009 SHEET BS-02 p

SENSING ELEMENT: 52-H BREAKER CONTACT

(_)

AR-305 Rev. 26 Page 6

ENCLOSURE 1 f'

(Page 5 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-01-04 E-01-04 P

RB SPRAY PP B OUT OF SERVICE EVENT POINT 0062 INDICATFD CONDITION:

o BSP-1B BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON CONTROL STATION o ES STATUS LIGHTS INDICATE BREAKER POSITION i

l OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-5B SWITCH 10 o VERIFY DC KNIFE SWITCH FOR BSP-1B BREAKER CLOSED DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

l REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION. THIS IS AN l

EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-009 SHEET BS-02

,e SENSING ELEMENT: 27C BREAKER RELAY

(

l A.R-305 Rev. 26 Page 7

1 O

ENCLOSURE 1 b

(Page 6 of 52)

ESE ANNUNCIATOR RESPONSE ESB-3H2-01-05 E-01-05 RB SPRAY B FLOW HIGH/ LOW EVENT POINT 0048 INDICATED CONDITION:

o BUILDING SPRAY FLOW IS $1400 GPM AS MEASURED BY BS-1-FS2 FOR 30 SEC.

COINCIDENT WITH AN ES ACTUATION

!rs REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RB SPRAY FLOW INDICATOR BS-1-FI2 OR INDICATOR ON BSV-4 CONTROLLER OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER OPERATION OF BSV-4, OPEN BSV-4 AS REQUIRED o VERIFY BSP-1B NOT TRIPPED DISCUSSION:

THE NORMAL BUILDING SPRAY PUMP FLOW DURING AN ES ACTUATION IS 1500 GPM.

TAKING LOCAL / AUTO CONTROL OF BSV-4 WILL ALLOW THE OPERATOR TO USE THE THUMBWHEEL ON THE VALVE CONTROLLER TO SET THE FLOW RATE. IF THIS DOES NOT WORK THEN MANUAL CONTROL OF THE VALVE SHOULD BE ATTEMPTED FROM THE CONTROL BOARD STATION.

REFERENCES:

DRAWING 208-009 SHEET BS-11

,A SENSING ELEMENT: BS-1-FS2 1

AR-305 Rev. 26 Page 8

i C

ffCLOSURE 1 (P. age 7 of 52) j

{

ESE ANNUNCIATOR RESPONSE ESB-]H2-01-05 E-01-05 l

I i

RB SPRAY B FLOW

]

HIGH/ LOW q

EVENT POINT 0050 INDICATED CONDITION:

j o BUILDING SPRAY FLOW IS E1700 GPM AS MEASURED BY BS-1-FS2.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

' C.\\

b o RB SPRAY FLOW INDICATOR BS-1-FI2 OR INDICATOR ON BSV-4 CONTROLLER l

)

bPERATORACTIONSFORAVALIDALARM:

o VERIFY PROPER OPERATION OF BSV-4, THROTTLE BSV-4 AS REQUIRED TO REDUCE l

FLOW DISCUSSION:

THE NORMAL BUILDING SPRAY PUMP FLOW DURING AN ES ACTUATION IS 1500 GPM.

TAKING LOCAL / AUTO CONTROL OF BSV-4 WILL ALLOW THE OPERATOR TO USE THE j

THUMBWHEEL ON THE VALVE CONTROLLER TO SET THE FLOW RATE. IF THIS DOES j

NOT WORK THEN MANUAL CONTROL OF THE VALVE SHOULD BE ATTEMPTED FROM THE j

CONTROL BOARD STATION.

REFERENCES:

DRAWING 208-009 SHEET BS-11 I

SENSING ELEMENT: BS-1-FS2 gN AR-305 Rev. 26 Page 9 l

[

1 i

MCLOSURE 1

[\\

(Page 8 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-01-05 E-01-05 RB SPRAY B FLOW HIGH/ LOW l

EVENT POINT 0064 i

INDICATED CONDITION:

o BUILDING SPRAY FLOW IS 51100 GPM AS MEASURED BY BS-82-FIS WITH DHV-43 OPEN REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

c3U o RB SPRAY FLOW INDICATOR BS-1-FI2 OR INDICATOR ON BSV-4 CONTROLLER f

I OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER OPERATION OF BSV-4, OPEN BSV-4 AS REQUIRED, o VERIFY BSP-1B NOT TRIPPED DISCUSSION:

THE NORMAL BUILDING SPRAY PUMP FLOW WHILE TAKING A SUCTION FROM THE RB SUMP IS 1200 GPM, THIS IS TO INSURE ADEQUATE NET POSITIVE SUCTION HEAD FOR THE BUILDING SPRAY PUMP. OPERATION IN THIS MODE IS TAKING LOCAL / AUTO CONTROL OF BSV-4, THIS WILL ALLOW THE OPERATOR TO USE THE THUMBWHEEL ON l

THE VALVE CONTROLLER TO SET THE FLOW RATE. IF THIS DOES NOT WORK, THEN

)

MANUAL CONTROL OF THE VALVE SHOULD BE ATTEMPTED FROM THE CONTROL BOARD STATION.

REFERENCES:

DRAWING 208-009 SHEET BS-11 SENSING ELEMENT: BS-82-FIS O,o AR-305 Rev. 26 Page 10

ENCLOSURE 1

[\\

(Page 9 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-01-05 E-01-05 RB SPRAY B FLOW HIGH/ LOW EVENT POINT 0066 INDICATED CONDITION:

o BUILDING SPRAY FLOW IS ;t 3G i GPM AS MEASURED BY BS-82-FIS WITH DHV-43 1

OPEN REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

7_

o RB SPRAY FLOW INDICATOR BS-1-FI2 OR INDICATOR ON BSV-4 CONTROLLER OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER OPERATION OF BSV-4, THROTTLE BSV-4 AS REQUIRED TO REDUCE FLOW DISCUSSION:

THE NORMAL BUILDING SPRAY PUMP FLOW WHILE TAKING A SUCTION FROM THE RB SUMP IS 1200 GPM, THIS IS TO INSURE ADEQUATE NET POSITIVE SUCTION HEAD FOR i

THE BUILDING SPRAY PUMP. OPERATION IN THIS MODE IS TAKING LOCAL / AUTO CONTROL OF BSV-4, THIS WILL ALLOW THE OPERATOR TO USE THE THUMBWHEEL ON f

THE VALVE CONTROLLER TO SET THE FLOW RATE. IF THIS DOES NOT WORK, THEN MANUAL CONTROL OF THE VALVE SHOULD BE ATTEMPTED FROM THE CONTROL BOARD STATION.

REFERENCES:

DRAWING 208-009 SHEET BS-11 SENSING ELEMENT: BS-82-FIS

(

AR-305 Rev. 26 Page 11

i ENCLOSURE 1 l[

(Page 10 of 52) x l

I ESE ANNUNCIATOR RESPONSE ESB-]H2-02-01 E-02-01 l

l RB FAN B HIGH SPEED TRIP EVENT POINT 0352 INDICATED CONDITION:

o AHF-1B CONTROL HANDLE PUSHED IN, IN NORMAL AFTER START, AND HIGH SPEED WINDINGS NOT ENERGIZED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN HIGH SPEED LIGHT WITH A RED FLAG ON CONTROL STATION, AND CONTROL HANDLE PUSHED IN.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF FAN TRIP j

l o ENSURE ONE OPERABLE FAN IS ES SELECTED PER OP-417 i

o MONITOR RB TEMPERATURE AND PRESSURE DISCUSSION:

THIS ALARM WILL OCCUR IF THE FAN IS RUNNING IN HIGH SPEED AND AN ES ACTUATION OCCURS. THIS WILL TRIP THE FAN IN HIGH SPEED AND START THE FAN IN SLOW SPEED.

SOME THINGS TO CHECK AFTER A FAN TRIP ARE: FAN AND MOTOR TEMPS AS READ ON AH-1003-TIR ON THE BACK OF THE CONTROL BOARD OR FAN VIBRATION ALARMS.

ENGINEERING CAN MONITOR FAN VIBRATION AT AN EXTERNAL PANEL IN THE IB 119' i

ELEVATION.

(

REFERENCES:

DRAWING 208-005 SHEET AH-29 SENSING ELEMENT: CS/IN, CS/SC, CS/0, 42/1F RELA l,m)

(

i V

i AR-305 Rev. 26 Page 12

l ENCLOSURE 1 lC (Page 11 of 52) l

(

ESE ANNUNCIATOR RESPONSE ESB-JH2-02-02 E-02-02 l

RB FAN B LOW SPEED TRIP EVENT POINT 0353 INDICATED CONDITION:

l o AHF-1B CONTROL HANDLE PULLED OUT, IN NORMAL AFTER START, AND SLOW SPEED WINDINGS NOT ENERGIZED.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LOW SPEED LIGHT WITH A RED FLAG ON CONTROL STATION, AND THE CONTROL HANDLE PULLED OUT.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF FAN TRIP.

l o ENSURE ONE OPERABLE FAN IS ES SELECTED PER OP-417 o MONITOR RB TEMPERATURE AND PRESSURE DISCUSSION:

SOME THINGS TO CHECK AFTER A FAN TRIP ARE: FAN AND MOTOR TEMPS AS READ ON AH-1003-TIR ON THE BACK OF THE CONTROL BOARD OR FAN VIBRATION ALARMS.

ENGINEERING CAN MONITOR FAN VIBRATION AT AN EXTERNAL PANEL IN THE IB 119' ELEVATION.

REFERENCES:

DRAWING 208-005 SHEET AH-29 SENSING ELEMENT: CS/0UT, CS/SC, CS/0, CONTROL SWITCH CONTACTS 42/15 AR-305 Rev. 26 Page 13

i i

ENCLOSURE 1

['

\\

(Page 12 of 52) l ESE ANNUNCIATOR RESPONSE ESB-]H2-02-03 E-02-03 i

I RB FAN B AIR FLOW LOW i

EVENT POINT 0354 INDICATED CONDITION:

o AHF-1B CONTROL HANDLE PUSHED IN AND IN NORMAL AFTER START AND LOW AIR

)

FLOW IS SENSED BY AH-19-DPS.

i f

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR BUILDING TEMPS ARE INCREASING AS SEEN ON AH-536-TIR I

OPERATOR ACTIONS FOR A VALIO ALARM:

o IF CONDITION CANNOT BE CORRECTED THEN CONSIDERATION SHOULD BE MADE TO SECURE THE FAN l

o ENSURE ONE OPERABLE FAN IS ES SELECTED PER OP-417 o MONITOR RB TEMPERATURE AND PRESSURE DISCUSSION:

THIS ALARM MAY BE PRESENT WHEN AN ES ACTUATION HAS STARTED A PREVIOUSLY RUNNING FAN IN SLOW SPEED. PLACING THE CONTROL HANDLE IN THE PULL OUT NORMAL AFTER START POSITION SHOULD CLEAR THE ALARM. ALSO IF THE FAN TRIPS 1

THIS ALARM SHOULD ACTUATE.

l

(

REFERENCES:

DRAWING 208-005 SHEET AH-29 SENSING ELEMENT: AH-19-DPS l

AR-305 Rev. 26 Page 14

O EN QQSURE 1

\\d (Page 13 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-02-04 E-02-04 i

RB FAN B VIBRATION HIGH EVENT POINT 0355 INDICATED CONDITION:

o AHF-1B HIGH VIBRATION CONDITION AS SENSED BY AH-20-ME1/2.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[(/

o FAN AND MOTOR TEMPS INCREASING ON AH-1003-TIR ON BACK OF CONTROL BOARD o IF FAN IS RUNNING IN SLOW SPEED THEN CURRENT ON THE FAN MAY BE OSCILLATING.

OPERATOR ACTIONS FOR A VALID ALARM:

o ATTEMPT TO RESET ALARM BY DEPRESSING RESET PUSHBUTTON ON CONTROL BOARD.

o IF CONDITION CANNOT BE CORRECTED THEN CONSIDERATION SHOULD BE MADE TO SECURE THE FAN.

l o ENSURE ONE OPERABLE FAN IS ES SELECTED PER OP-417 e

DISCUSSION:

ENGINEERING CAN MONITOR FAN VIBRATION AT AN EXTERNAL PANEL IN THE IB 119' ELEVATION.

REFERENCES:

DRAWING 208-005 SHEET AH-137 SENSING ELEMENT: AH-20-MEl, AH-20-ME AR-305 Rev. 26 Page 15

r l

l

[~ ~

ENCLOSURE 1

\\

(Page 14 of 52)

ESE ANNUNCIATOR RESPONSE ESB-)H2-02-05 E-02-05 i

l RB FAN B l

i CONDENSATE l

HIGH EVENT POINT 1698 i

INDICATED CONDITION:

l o AHF-1B CONDENSATE FLOW IS ;t1133 CC PER MINUTE AS SENSED BY AH-657-FIS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR BUILDING SUMP RATE OF RISE IS INCREASING AS SEEN ON BS-93-PIR.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE SOURCE OF CONDENSATE.

DISCUSSION:

SOME SOURCES OF HIGH CONDENSATION ARE:

RCS LEAK IN CONTAINMENT - CHECK PZR LEVEL AND MAKE UP TANK LEVEL TRENDS; FEEDWATER/ MAIN STEAM LEAK IN CONTAINMENT - CHECK FEEDWATER FLOWRATES; RB FAN COOLER SW LEAKS - CHECK SW SURGE TANK LEVEL IF ON SW, OR CI SURGE TANK LEVELS IF ON CI.

i 1

REFERENCES:

DRAWING 208-005 SHEET AH-131 SENSING ELEMENT:AH-657-FIS I

AR-305 Rev. 26 Page 16 l

)

p ENCLOSURE 1 (j

(Page 15 of 52)

ESB ANNUNCIATOR RESPONSE ESB-JH2-02-05 E-02-05 THIS AR IS ONLY USED W11EN COLD LJLG N0ZZLE DAMS ARE INSTALLED PER MP-110C l

RCSG 1B NOZZLE DAM PROBLEM j

l l

l EVENT POINT 1698 INDICATED CONDITION:

o "B" SIDE N0ZZLE DAM CONTROL CONSOLE IS IN ALARM i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

k o N0ZZLE DAM PRESSURE 29 PSIG ON EITHER SEAL o N0ZZLE DAM PRESSURE $6.5 PSIG ON EITHER SEAL o N0ZZLE DAM AIR FLOW 19 SCFH o LOSS OF POWER TO THE CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:

o IMMEDIATELY INVESTIGATE SOURCE OF ALARM o REFER TO E0P-11 DISCUSSION:

THIS ALARM INDICATES POSSIBLE N0ZZLE DAM SEAL DEGRADATION. IF THE SEAL FAILS, A REACTOR COOLANT LEAK WOULD DEVELOP, FLOODING THE PRIMARY SIDE OF i

THE STEAM GENERATORS WHERE PERSONNEL MAY BE AT WORK.

l i

THIS EVENT POINT IS ONLY IN USE ON A TEMPORARY BASIS WHEN N0ZZLE DAMS ARE INSTALLED. THE WINDOW "RB FAN B CONDENSATE HIGH" IS REMOVED FROM THE ANNUNCIATOR PANEL WHEN THIS EVENT POINT IS IN EFFECT.

l

REFERENCES:

MP-110C SENSING ELEMENT: INTERNAL ALARM CIRCUITS INSIDE N0ZZLE DAM CONTROL CONSOLE AR-305 Rev. 26 Page 17

i ENCLOSURE 1 (Page 16 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-02-06 E-02-06 l

l l

ES B ACTUATION TROUBLE i

EVENT POINT 1231 l

INDICATED CONDITION:

o "B" ES ACTUATION SIGNAL ON ONE OR MORE ES CHANNELS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ES STATUS LIGHTS o ES BISTABLE TRIP INDICATORS OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO E0P DISCUSSION:

THIS ALARM INDICATES THAT AT LEAST ONE OF THREE CHANNELS OF "B" ES HAS ACTUATED. ANY HPI OR LPI BISTABLE TRIPPED WITH ES NOT BYPASSED, OR ANY 4 PSIG ES PRESSURE SWITCH ACTUATED WILL GIVE THIS ALARM. PLACING THE RC PRESSURE TEST MODULE IN " TEST" DEFEATS THIS ALARM FROM LPI OR HPI. WHEN THE 4 PSIG TEST SWITCHES ARE IN THE " TEST" POSITION THIS ALARM IS DEFEATED FROM A 4 PSIG ACTUATION.

REFERENCES:

DRAWING 208-028 SHEET ES-AB-05 SENSING ELEMENT: VARIOUS ES ACTUATION CONTACTS g

N,.]

l AR-305 Rev. 26 Page 18 l

J

I E_NCLOSURE 1 1

O (Page 17 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-03-01 E-03-01 REACTOR BLDG PRESS HIGH (2 PSIG)

EVENT POINT 0067 I

l INDICATED CONDITION:

o REACTOR BUILDING PRESSURE IS 12 PSIG AS SENSED BY BS-93-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o CONTROL BOARD RB PRESSURE INDICATORS, BS-17-PI, BS-93-PIR o RB TEMP INDICATION AH-536-TIR j

j o COMPUTER POINT P254 OPERATOR ACTIONS FOR A VALID ALARM:

I PROMPTLY TAKE ACTION TO REDUCE REACTOR BUILDING PRESSURE AND PREVENT A 4 l

PSIG ES ACTUATION. CONSIDER ONE OR MORE OF THE FOLLOWING ACTIONS:

START SWP-1A AND/OR SWP-1B A_ND PLACE RB FAN ON SW COOLING.

l o

o START RWP-2A AND/0R RWP-2B ENSURE ONLY ONE RB FAN IS RUNNING DURING AN ES ACTUATION.

l o

DISCUSSION:

PCSSIBLE SOURCES OF HIGH RB PRESSURE ARE:

o LOSS OF RB FAN AND/OR COOLING WATER o STEAM AND/0R FEEDWATER LEAK INSIDE CONTAINMENT j

o RCS LEAK INSIDE CONTAINMENT o COMPRESSED AIR SYSTEM LEAKS INSIDE CONTAINMENT o INCREASED RB TEMP DUE TO RCS HEATUP, OR HIGH OUTDOOR TEMPS o HIGH RB FLOOD LEVEL IT IS RECOMMENDED TO RUN FAN IN SLOW SPEED 50 AS TO PRECLUDE MOTOR l

OVERLOAD IN A DENSE STEAM ATMOSPHERE AND RENDERING IT UNAVAILABLE. RUNNING SWP-1A AND SWP-1B SIMULTANE0USLY FOR INCREASED SW FLOW TO FAN IS ACCEPTABLE AND WILL YIELD THE BEST RB COOLING PERFORMANCE.

REFERENCES:

DRAWING 208-009 SHEET BS-11 SENSING ELEMENT: BS-93-PS AR-305 Rev. 26 Page 19 l

['/')

ENCLOSURf;_1 L

(Page 18 of 52) 4 ESE ANNUNCIATOR RESPONSE ESB-]H2-03-02 E-03-02 REACTOR BLDG TEMP HIGH EVENT POINT 1700 INDICATED CONDITION:

1 o REACTOR BUILDING TEMPERATURE IS 2123.6*F AS SENSED BY AH-536-TY4 REDUNDAffT INDICATION WHICH WILL VERIFY ALARM:

(%

o RB TEMP INDICATION AH-536-TIR V

o THE AVERAGE OF COMPUTER POINTS: 5358, 5359, 5382, 5383 o COMPUTER POINT 5837 OPERATOR ACTIONS FOR A VALID ALARM:

TO REDUCE THE REACTOR BUILDING TEMPERATURE CONSIDER ONE OF THE FOLLOWING ACTIONS:

i i

l o START SWP-1A AND/OR SWP-1B A,_ND PLACE RB FAN ON SW COOLING o START RWP-2A AND/OR RWP-2B l

o ENSURE ONLY ONE RB FAN IS RUNNING DURING AN ES ACTUATION DISCUSSION:

POSSIBLE SOURCES OF HIGH RB TEMPERATURE ARE:

o LOSS OF RB FAN AND/OR COOLING WATER o STEAM AND/OR FEEDWATER LEAK INSIDE CONTAINMENT o RCS LEAK INSIDE CONTAINMENT o RCS HEATUP OR HIGH OUTDOOR TEMPS l

RUNNING SWP-1A AND SWP-1B SIMULTANEOUSLY FOR INCREASED SW FLOW TO FAN IS ACCEPTABLE AND WILL YIELD THE BEST RB COOLING PERFORMANCE.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

l('

REFERENCES:

DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-536-TY4 AR-305 Rev. 26 Page 20

ENCLOSURE 1

(

(Page 19 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-04-01 E-04-01 MAKEUP PP C TRIP

~'

EVENT POINT 1047 INDICATED CONDITION:

o MUP-1C BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON MVP-1C CONTROL STATION o ES STATUS LIGHT OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-402 FOR RESTORATION OF RCP SERVICES PRIOR TO STARTING ANOTHER MVP o CONSIDER MINIMIZING LETDOWN FLOW o INVESTIGATE MVP-1C BREAKER FOR DROPPED RELAY TARGETS o START AN0THER MAKE-UP PUMP PER OP-402 IF CAUSE OF THIS TRIP WILL NOT TRIP ANOTHER PUMP j

DISCUSSION:

EXERCISE CARE WHEN STARTING ALTERNATE MU PUMPS. ENSURE ANY FAILURES SUCH AS IMPROPER FLOWPATH, WHICH MAY HAVE DIRECTLY OR INDIRECTLY HAVE CAUSED THIS PUMP TO TRIP 00 NOT CAUSE ALTERNATE PUMPS TO TRIP AFTER THEY ARE STARTED.

I REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-04

(

SENSING ELEMENT: CS/SC, CS/0, 52H/A, 525/B AR-305 Rev. 26 Page 21 i

i O)

ENCLOSURE 1 (Page 20 of 52)

ESE ANNUNCIATOR RESPONSE ESA-]H2-04-02 E-04-02 MAKEUP PP C GEAR OIL PRESS LOW EVENT POINT 1059 1

INDICATED CONDITION:

o MVP-1C BREAKER CLOSED ;t2 SECONDS WITH GEAR OIL PRESS 57 PSIG AS SENSED BY MU-90-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MVP-5C BACK UP GEAR OIL PUMP AUTO STARTS o COMPUTER POINT X069 OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY MVP-SC DC BACK UP GEAR OIL PUMP STARTED o MONITOR MVP-1C VIA COMPUTER GROUP 72

)

I l

DISCUSSION:

CONSIDERATION SHOULD BE GIVEN TO SWAPPING MAKE UP PUMPS PER OP-402 l

i l

REFERENCES:

DRAWING 208-041 SHEET MU-51 SENSING ELEMENT: 2MVP-5C, MU-90-PS, 525/A l

AR-305 Rev. 26 Page 22

/~

EN_ CLOSURE 1

(

(Page 21 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-04-03 E-04-03 MAKEUP PP C MOTOR OVERLOAD EVENT POINT 1045 INDICATED CONDITION:

o MVP-1C MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS o MVP-1C TRIP o HIGH FLOWRATES THROUGH MVP-1C OPERATOR ACTIONS FOR A VALID ALARM:

o TRIP MUP-1C o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS i

OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED, INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-041 SHEET MU-49 SENSING ELEMENT: 51 RELAY INSIDE BREAKER CUBICLE L

AR-305 Rev. 26 Page 23

ENCLOSURE 1 (Page 22 of 52) y ESE ANNUNCIATOR RESPONSE ESB-JH2-04-04 E-04-04 MAKEUP PP C LUBE OIL PUMP TRIP j

EVENT POINT 1050 INDICATED CONDITION:

o MVP-2C, CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE, MOTOR NOT ENERGIZED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION f

o LOW LUBE OIL PRESSURE ALARM o MVP-3C, BACK-UP LUBE OIL PUMP, AUTO START OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MVP-3C, BACK-UP LUBE OIL PUMP, STARTED i

DISCUSSION:

THIS ALARM IS AN INDICATION OF INADEQUATE LUBRICATION TO THE MAKE-UP PUMP.

MONITOR THE MAKE-UP PUMP VIA COMPUTER GROUP 72. CONSIDERATION SHOULD BE GIVEN TO SWAPPING MAKE-UP PUMPS.

(

REFERENCES:

DRAWING 208-041 SHEET MU-07 SENSING ELEMENT: CS/SC, CS/0, 42B AR-305 Rev. 26 Page 24

ENCLOSURE 1 l(/m (Page 23 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-04-04 E-04-04 l

I MAKEUP PP C l

LUBE OIL PUMP TFilP EVENT POINT 1056 I

INDICATED CONDITION:

o MVP-3C CONTROL HANDLE IN THE NORMAL AFTER START POSITION WITH THE MOTOR l

NOT ENERGIZED.

l

/]

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

%J o GREEN LIGHT WITH A RED FLAG ON CONTROL STATION o MAKEUP PUMP OIL PRESSURE LOW ALARM o COMPUTER POINT X069 i

OPERATOR ACTIONS FOR A VALID ALARM:

o MONITOR MVP-1C BEARING TEMPS DISCUSSION:

i l

THIS ALARM IS AN INDICATION OF INADEQUATE LUBRICATION TO THE MAKE-UP PUMP.

MONITOR THE MAKEUP PUMP VIA COMPUTER GROUP 72.

CONSIDERATION SHOULD BE GIVEN TO SWAPPING MAKEUP PUMPS.

l l

REFERENCES:

DRAWING 208-041 SHEET MU-32 SENSING ELEMENT: CS/SC, CS/0, CR1

(>

I AR-305 Rev. 26 Page 25

l ENCLOSURE 1 Os (Page 24 of 52)

ESE ANNUNCIATOR RESPONSE ESB-3H2-04-06 E-04-06 AUX STEAM ISO (ASV-196)

BYPASSED EVENT POINT 1961 INDICATED CONDITION:

o CONTROL SWITCH FOR ASV-196 AUX STEAM SOLEN 0ID VALVE IS IN THE OPEN/8YPASS POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ASV-196 SELECTOR SWITCH POSITION OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-608 DISCUSSION:

THIS ALARM INDICATES THAT THE AUTOMATIC CLOSURE OF ASV-196 ON HIGH TEMPERATURE OR LOW AUX STEAM PRESSURE IS DISABLED. THIS IS A HIGH ENERGY LINE BREAK CONCERN.

REFERENCES:

DRAWING 208-008 SHEET AS-05 SENSING ELEMENT: CS/NC AR-305 Rev. 26 Page 26

(']

ENCLOSURE 1

, \\_f (Page 25 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-05-02 E-05-02 MAKEUP PP C LUBE OIL PRESS LOW EVENT POINT 1043 i

INDICATED CONDITION:

o LUBE OIL PRESS AS SENSED BY MU-48-PS3 IS 53 PSIG.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(

o MVP-3C, BACK UP LUBE OIL PUMP, AUTO STARTS OPERATOR ACTIONS FOR A VALID ALARM:

I o ENSURE MVP-3C HAS STARTED l

I l

i DISCUSSION:

i THIS ALARM INDICATES INADEQUATE LUBRICATION FOR MVP-1C. IF THE PUMP IS RUNNING, IT SHOULD BE SECURED AND AN ALTERNATE MAKEUP PUMP PLACED IN SERVICE. REFER TO OP-402 FOR DIRECTIONS ON STARTING MAKEUP PUMPS.

REFERENCES:

DRAWING 208-041 SHEET MU-01 SENSING ELEMENT: 43/3C, MU-42-PS3 AR-305 Rev. 26 Page 27

I I

/'

ENCLOSURE 1 C

(Page 26 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-05-03 E-05-03 i

i MAKEUP PP C LUBE OIL PUMP i

AUTO START EVENT POINT 1055 i

INDICATED CONDITION:

o MVP-3C CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION AND MOTOR IS ENERGIZED

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON MUP-3C CONTROL STATION o COMPUTER POINT X069 OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MVP-3C IS RUNNING DISCUSSION:

THIS ALARM IS AN INDICATION OF INADEQUATE LUBRICATION TO THE MAKE-UP PUMP.

MONITOR THE MAKE-UP PUMP VIA COMPUTER GROUP 72. CONSIDERATION SHOULD BE GIVING TO SWAPPING MAKE-UP PUMPS.

l

(

REFERENCES:

DRAWING 208-041 SHEET MU-32 I

SENSING ELEMENT: CS/ST, CS/ST, CS/0, CR1 AR-305 Rev. 26 Page 28

l-l l

{:

/"'

ENCLOSURE 1

( )s (Page 27 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-05-04 E-05-04 MAKEUP PP C OUT OF SERVICE EVENT POINT 1044 INDICATED CONDITION:

o MVP-1C BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

,,Q

\\

o NO INDICATING LIGHTS ON CONTROL STATION.

1 o ES STATUS LIGHTS INDICATE BREAKER POSITION.

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY CLOSED DPDP-5B SWITCH 10 o VERIFY DC KNIFE SWITCH FOR MVP-1C BREAKER CLOSED l

DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.

REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-04 i

SENSING ELEMENT: RELAY 27C LOCATED INSIDE BREAKER CUBICLE FOR MVP-1C AR-305 Rev. 26 Page 29

ENCLOSURE 1 AV (Page 28 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-05-04 E-05-04 MAKEUP PP C OUT OF SERVICE 1

EVENT POINT 1046

(

INDICATED CONDITION:

o MVP-1C BREAKER IS RACKED OUT AND MUP-1C IS SELECTED FOR ES START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o NO INDICATING LIGHTS ON CONTROL STATION o NO ES STATUS INDICATION i

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE THE CAUSE FOR BREAKER BEING RACKED OUT DISCUSSION:

l l

W O PUMPS SHOULD BE SELECTED FOR ES START.

l REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-01 SENSING ELEMENT: 43/3C CUBICLE 385, 52H/b CUBICLE 385 FOR MVP-1C AR-305 Rev. 26 Page 30

l ENCLOSURE 1

[T (Page 29 of 52) 1

(

ESE ANNUNCIATOR RESPONSE ESB-JH2-05-06 E-05-06 AUX STEAM ISO (ASV 196)

AUTO CLOSED 1

EVENT POINT 1817

{

INDICATED CONDITION:

o CONTROL SWITCH FOR ASV-196 AUX STEAM SOLEN 0ID VALVE IS IN THE AUTO POSITION AND THE VALVE IS CLOSED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ASV-196 SELECTOR SWITCH IN AUTO o GREEN INDICATOR LIGHT ON SELECTOR SWITCH 1

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-608 i

DISCUSSION:

THIS ALARM INDICATES THAT THE AUTOMATIC CLOSURE OF ASV-196 ON EITHER LOW l

AUX STEAM PRESSURE OR HICH AUX STEAM PRESSURE HAS OCCURRED, A LOW PRESSURE ACTUATION OCCURS AT <100 PSIG AND A HIGH PRESSURE ISOLATION OCCURS AT >250 PSIG AUX STEAM HEADER PRESSURE IN THE AUX BUILDING.

I

REFERENCES:

DRAWING 208-008 SHEET AS-05 t

I SENSING ELEMENT: 3ASV-196-SV1, 33C/ASV-196-SV, AS-36-PS1,AS-36-PS3

'\\.)

AR-305 Rev. 2C Page 31

i I

!O ENCLOSURE 1 (Page 30 of 52) l ESE ANNUNCIATOR RESPONSE ESB-JH2-06-01 E-06-01 l

l l

l MAKEUP PP B TRIP l

1 l

l l

EVENT POINT 1101 i

INDICATED CONDITION:

1 o MVP-1B BREAKER OPEN WITH CONTROL HANDLE IN NORMAL AFTER START POSITION.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l ("'\\

(

o GREEN LIGHT ON WITH A RED FLAG ON MVP-1B CONTROL STATION.

o ES STATUS LIGHT.

OPERA 10R ACTIONS FOR A VALID ALARM:

o REFER TO OP-402 FOR RESTORATION OF RCP SERVICES PRIOR TO STARTING ANOTHER MVP o CONSIDER MINIMIZING LETDOWN FLOW o INVESTIGATE MVP-1B BREAKER FOR DROPPED TARGETS o START ANOTHER MAKE-UP PUMP PER OP-402 IF CAUSE OF THIS TRIP WILL NOT TRIP I

ANOTHER PUMP DISCUSSION:

EXERCISE CARE WHEN STARTING ALTERNATE MU PUMPS. ENSURE ANY FAILURES SUCH AS IMPROPER FLOWPATH, WHICH MAY HAVE DIRECTLY OR INDIRECTLY HAVE CAUSED THIS PUMP TO TRIP DO NOT CAUSE ALTERNATE PUMPS TO TRIP AFTER THEY ARE STARTED.

t REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-13 SENSING ELEMENT: CS/SC, CS/0, 52H/A, 525/B l

AR-305 Rev. 26 Page 32 i

I i

ENCLOSURE 1 (Page 31 of 52) s ESE ANNUNCIATOR RESPONSE ESB-]H2-06-02 E-06-02 1

4 l

MAKEUP PP B l

LUBE OlL PRESS LOW EVENT POINT 1097 i

INDICATED CONDITION:

o LUBE OIL PRESSURE AS SENSED BY MU-45-PS3 IS 53 PSIG.

j L

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MVP-3B BACK UP LUBE OIL PUMP AUTO STARTS I

OPERATOR ACTIONS FOR A VALID ALARM:

l o ENSURE MVP-3B HAS STARTED 4

DISCUSSION:

THIS ALARM INDICATES INADEQUATE LUBRICATION FOR MUP-18. IF THE PUMP IS 1

RUNNING, IT SHOULD BE SECURED AND AN ALTERNATE MAKEUP PUMP PLACED IN SERVICE. REFER TO OP-402 FOR DIRECTIONS ON STARTING MAKEUP PUMPS.

j l

REFERENCES:

DRAWING 208-041 SHEET MU-02 I

I SENSING ELEMENT: 43CS/3B7-3B, MU-45-PS3 p

O AR-305 Rev. 26 Page 33

I

/~'

ENCLOSURE 1 (Page 32 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-06-03 E-06-03 MAKEUP PP B MOTOR OVERLOAD l

l EVENT POINT 1099 l

INDICATED CONDITION:

o MVP-1B MOTOR AMPS 1115% RATED LOAD.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(IN

(-)

o HIGH MOTOR AMPS o MVP-1B TRIP l

o HIGH FLOWRATES THROUGH MVP-1B l

l OPERATOR ACTIONS FOR A VALID ALARM:

l o TRIP MVP-1B o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

i THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-041 SHEET MU-13 SENSING ELEMENT: 51 RELAY INSIDE BREAKER CUBICLE AR-305 Rev. 26 Page 34

. f' ENCLOSURE 1 (Page 33 of 52)

ESE ANNUNCIATOR RESPONSE ESB-)H2-06-04 E-06-04 i

MAKEUP PP B OUT OF SERVICE h

I l

EVENT POINT 1098 INDICATED CONDITION:

o MVP-18 BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

7 o NO INDICATING LIGHTS ON CONTROL STATION o ES STATUS LIGHTS INDICATE BREAKER POSITION OPERATOR ACTIONS FOR A VALID ALARM:

l o VERIFY CLOSED DPDP-5B SWITCH 10 o VERIFY DC KNIFE SWITCH FOR MVP-1B BREAKER CLOSED i

j DISCUSSION:

THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING REFER TO OP-703 FOR LOCAL BREAKER OPERATION. THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-02 SENSING ELEMENT: RELAY 27C LOCATED INSIDE BREAKER CUBICLE FOR MUP-1B l

AR-305 Rev. 26 Page 35 l

l i

ID ENCLOSURE 1

(

(Page 34 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-06-04 E-06-04 t

l l

MAKEUP PP B OUT OF SERVICE l

I EVENT POINT 1100 INDICATED CONDITION:

I o MUP-1B BREAKER IS RACKED OUT AND MVP-1B IS SELECTED FOR ES START.

f REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

V' o NO INDICATING LIGHTS ON CONTROL STATION o NO ES STATUS INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE THE CAUSE FOR THE BREAKER BEING RACKED OUT l

l

~

DISCUSSION:

l l

TWO PUMPS SHOULD BE SELECTED FOR ES START.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-041 SHEET MU-13 SENSING ELEMENT: 43/38 ON CUBICLE 3B5, 52H/B IN CUBICLE 3B4 AR-305 Rev. 26 Page 36

l i

I ENCLOSURE 1 l (~T

, \\s/

(Page 35 of 52) j ESE ANNUNCIATOR RESPONSE ESB-]H2-07-06 E-07-06 i

i b

H2 SAMPLING PANEL B TROUBLE EVENT POINT 0256 INDICATED CONDITION:

o PASS RB H2 ANALYZER "B" MALFUNCTION o HIGH RB H2 CONCENTRATION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(O,)

o LOSS OF POWER TO PANEL o OVERPRESSURE TO PANEL AT E4 PSIG o LOW FLOW TO PANEL AT $1 SCFH o THERM 0 ELEGRIC COOLER 50.1 AMPS o RB H2 CONCENTRATION 13%

l OPERATOR ACTIONS FOR A VALID ALARM:

l o NOTIFY NSS/NSM AND EC 0F HYDROCEN CONCENTRATION IE RB H2 2 3%

l IliEN GO TO EM-308 o OR NOTIFY I&C SUPERVISION OF H2 ANALYZER MALFUNCTION DISCUSSION:

THIS ALARM INDICATES EITHER THE POST ACCIDENT H2 CONCENTRATION INSIDE THE RB IS HIGH, OR THE PASS H2 ANALYZER IS MALFUNCTIONING. EM-308 PROVIDES GUIDANCE TO MONITOR POST-ACCIDENT HYDROGEN CONCENTRATION IN THE REACTOR BUILDING ATMOSPHERE USING THE CONTAINMENT HYDROGEN MONITORING SYSTEM.

i i

I l

REFERENCES:

DRAWING 208-062 SHEET WS-06 Q

SENSING ELEMENT: VARIOUS FLOW / PRESSURE / CURRENT SWITCHES INSIDE THE SAMPLER (J

AR-305 Rev. 26 Page 37

ENCLOSURE 1 f

(Page 36 of 52) is ESE ANNUNCIATOR RESPONSE ESB-]H2-08-01 E-08-01 DIESEL GEN B FAILED TO START

]

l I

EVENT POINT 1208 INDICATED CONDITION:

o "B" EGDG HAS A START COMMAND AND LUBE OIL PRESSURE AS SENSED BY DL-10-PS IS 56 PSIG AFTER 7 SECONDS QB o

"B" ECDG HAS A START COMMAND AND ENGINE SPEED AS SENSED BY EG-20-SS IS $250 RPM AFTER 7 SECONDS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ECDG-1B TRIPS o CONTROL BOARD " CRANK" LIGHT GOES OUT AND WHITE " READY" LIGHT DOES NOT COME ON i

o ECDG-1B STARTING AIR PRESSURE LOW ALARM ANNUNCIATES OPERATOR ACTIONS FOR A VALID ALARM:

o INSPECT EGDG-18 FOR CAUSE OF FAILURE TO START o RESET PUSHBUTTON MUST BE DEPRESSED ON EGDG GAUGE BOARD PRIOR TO EGDG

]

RESTART.

DISCUSSION:

THIS ALARM INDICATES THE DIE 5EL TRIED TO START AND DID NOT. SOME POSSIBLE CAUSES OF THIS ARE: PROBLEMS WITH DIESEL FUEL SYSTEM, LUBE OIL SYSTEM PROBLEMS OR DIESEL SPEED SENSOR PROBLEMS. THIS ALARM IS STILL ACTIVE WITH AN ES SIGNAL PRESENT BUT WILL NOT DE-ENERGIZE Tile STARTING AIR SOLEN 0 IDS, 50 THE DIESEL WILL CRANK UNTIL IT EITHER STARTS OR RUNS OUT OF AIR.

(

REFERENCES:

DRAWING 208-027 SHEET EG-16, EG-02, EG-04, EG-06 SENSING ELEMENT: DL-10-PS, DL-20-SS, START FAIT. RELAY AR-305 Rev. 26 Page 38

F~

i ENCLOSURE 1 l (C '

l (Page 37 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-08-01 E-08-01 l

DIESEL GEN B FAILED TO START I

EVENT POINT 1215 INDICATED CONDITION:

o "B" ECDG HAS TRIPPED IT'S PHASE DIFFERENTIAL CURRENT RELAY o "B" ECDG TRIPS AND BREAKER 3210 OPENS o "B" EGDG 86 LOCKOUT RELAY HAS ACTUATED l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o "B" ES 4160V BUS DE-ENERGIZES I

o CONTROL BOARD "RUN" LIGHT COES OUT OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-770 o INSPECT EGDG-1B FOR CAUSE OF DIFFERENTIAL CURRENT CONDITION o LOCK 0UT RELAY MUST BE MANUALLY RESET ONCE PROBLEM IS RESOLVED.

I DISCUSSION:

THIS ALARM INDICATES THE DIESEL GENERATOR HAS EITHER, A PHASE TO PHASE SHORT OR A PHASE TO GROUND SHORT. THIS CONDITION WILL TRIP THE DIESEL AND PREVENT IT FROM STARTING. THE CAUSE OF THIS PROBLEM MUST BE RESOLVED PRIOR TO ANY ATTEMPT BEING MADE TO RESTART AND RELOAD THE DIESEL GENERATOR.

REFERENCES:

DRAWING 208-027 SHEET EG-16

(

SENSING ELEMENT: 86-DG-38, 87A, 87B, 87C DIFFERENTIAL CURRENT RELAYS AR-305 Rev. 26 Page 39 1

l L

/'

ENCLOSURE 1 (Page 38 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-08-02 E-08-02 I

l l

DIESEL GEN B TROUBLE I

i EVENT POINT 1203 i

INDICATED CONDITION:

i o "B" EGDG LUBE OIL TEMP AS SENSED BY DL-12-TS IS $115"F QB o "B" EGDG JACKET COOLANT TEMP AS SENSED BY DJ-29-TS $ 30*F 1

t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL TEMP INDICATION FOR LUBE OIL OR JACKET COOLANT TEMPS LOW o DIESEL GENERATOR ALARM PANEL DROP TARGET FOR LOW LUBE OIL / JACKET COOLANT l

TEMP.

i l

l l

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PROPER OPERATION OF LUBE OIL HEATERS DLHE-4 o ENSURE PROPER OPERATION OF JACKET COOLANT HEATER DJHE-2 o REFER TO OP-707 I

l DISCUSSION:

ECDG LUBE OIL TEMP MUST BE MAINTAINED >110* F FOR OPERABILITY i

REQUIREMENTS.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

G

REFERENCES:

DRAWING 208-027 SHEET EG-08 SENSING ELEMENT: DL-12-TS DJ-29-TS AR-305 Rev. 26 Page 40

ENCLOSURE 1 (Page 39 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-02 E-08-02 l

i 1

l DIESEL GEN B TROUBLE i

EVENT POINT 1209 i

INDICATED CONDITION:

o "B" EGDG LOCAL ALARM PANEL HAS A DROPPED TARGET lQ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l

!k/

o INFORMED BY THE AUX BUILDING OPERATOR OF EGOG-1B LOCAL ALARM PANEL DROP TARGET.

i l

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AR-902 I

l I

DISCUSSION:

l THIS ALARM INDICATES A DIESEL GENERATOR LOCAL ANNUNCIATOR DROP TARGET HAS DROPPED. IMMEDIATE INVESTIGATION OF ALARM CAUSE SHOULD BE INITIATED.

l REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

l

REFERENCES:

DRAWING 208-027 SHEET EG-18 SENSING ELEMENT: VARIOUS SENSORS ASSOCIATED WITH LOCAL ALARM PANEL i

l AR-305 Rev. 26 Page 41

f ENCLOSURE 1 (3

(Page 40 of 52)

(/

)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-03 E-08-03 j

DIESEL GEN B l

OUT OF SERVICE EVENT POINT 1197 i

INDICATED CONDITION:

f o "B" EGDG HAS HAD A LOSS OF DC CONTROL POWER REDUNCANT INDICATION WHICH WILL VERIFY ALARM:

O o EGDG-18 STARTS WITH NO AUTO START SIGNAL i d EGDG-1B CONTROL CIRCUIT INDICATOR LIGHTS ON MAIN CONTROL BOARD OR INSIDE o

l THE DIESEL GENERATOR ROOM ARE OFF OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY DPDP-6B SWITCHES 12 AND 14 ARE CLOSED o CHECK ECOG-1B CONTROL POWER FUSES o REFER TO OP-707 3

l DISCUSSION:

A LOSS OF DC CONTROL POWER WILL AFFECT THE DIESEL DIFFERENTLY DEPENDING ON WHICH CIRCUIT LOSES POWER. IF ALL DC POWER IS LOST THE DIESEL WILL START l

AND YOU WILL ONLY BE ABLE TO SHUT IT DOWN LOCALLY BY TRIPPING THE FUEL RACKS. IF OTHER FUSES ARE BLOWN THE EFFECT WILL VARY FROM LOSS OF GOVERNOR CONTROL TO A LOSS OF PROTECTIVE RELAYING ASSOCIATED WITH THE DIESEL. THE CAUSE OF THIS ALARM SHOULD BE INVESTIGATED IMMEDIATELY.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-027 SHEET EG-18, EG-04, EG-10, EG-06, EG-16

, /~N

()

SENSING ELEMENT: A,B,C,D,E, LOSS OF POWER RELAYS AR-305 Rev. 26 Page 42 l

i /7 ENCLOSURE 1 Q

(Page 41 of 52) i ESE ANNUNCIATOR RESPONSE ESB-]H2-08-03 E-08-03 DIESEL GEN B OUT OF SERVICE I

l l

EVENT POINT 1210 l

INDICATED CONDITION:

o "B" EGDG START AIR AS SENSED BY EG-12-PS IS 5225 PSIG o:U j

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW AIR PRESSURE ALARM.

o VERIFY EGDG-1B AIR COMPRESSOR, EGP-1B RUNNING j

o CHECK EGDG-1B FOR AIR LEAKS DISCUSSION:

A LOSS OF STARTING AIR WILL EVENTUALLY CAUSE THE DIESEL TO START WHEN PRESSURE IS NO LONCER HIGH EN0 UGH TO HOLD THE AUTO START VALVES CLOSED. IF l

EGP-1B IS OUT OF SERVICE THEN CONSIDERATION SHOULD BE GIVEN TO CROSS l

CONNECTING THE DIESEL START AIR SYSTEMS BY OPENING EGV-25 AND EGV-26.

i REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-027 SHEET EG-18, EG-08 SENSING ELEMENT: EG-12-PS l

i AR-305 Rev. 26 Page 43 l

t

l l

[

ENCLOSURE 1

\\

(Page 42 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-08-03 E-08-03 i

1 f

DIESEL GEN B i

OUT OF SERVICE q

l EVENT POINT 1211 INDICI.TED CONDITION:

o A..Y "B" ECOG AUT0/ MANUAL CONTROL SWITCH NOT IN THE AUTO POSITION l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o NOTIFIED BY PRIMARY PLANT OPERATOR EGDG-1B CONTROL SWITCH NOT IN AUTO l

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO RETURN CONTROL SWITCH TO AUTO l

i DISCUSSION:

I THE FOLLOWING SWITCHES NOT IN AUTO WILL GIVE YOU THII ALARM:

3ACKET COOLING PUMP JACKET COOLANT HEATER STANDBY LUBE OIL PUMP DC FUEL OIL PUMP DC FUEL OIL XFER PUMP AC FUEL OIL XFER PUMP l

AC AIR COMPRESSOR DIESEL AUT0/ MAN (MCB) l l

NORMAL /AT ENGINE SWITCH ON DIESEL GAUGE BOARD IN "AT ENGINE" J

f REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-027 SHEET EG-18, EG-08 SENSING ELEMENT: VARIOUS ECDG-1B CONTROL SWITCH CONTACTS O

AR-305 Rev. 26 Page 44

i i

/'

ENCLOSURE 1

(

(Page 43 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-04 E-08-04

)

J I

CF TANK B LEVEL filGH/ LOW

)

EVENT POINT 0117

)

INDICATED CONDITION:

o CFT-1B LEVEL AS SENSED BY CF-2-LS3 IS 213'4" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

C o CONTROL BOARD INDICATORS CF-2-LI3 OR CF-2-LI4 l(.)\\

o COMPUTER POINT P201 OPERATOR ACTIONS FOR A VALID ALARM:

I o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL LEVEL o REFER TO OP-401 FOR THIS CONDITION DISCUSSION:

A HIGH CORE FLOOD TANK LEVEL MAY INDICATE CORE FLOOD CHECK VALVES LEAKING BY. OBSERVE MAKEUP TANK LEVEL AND PRESSURIZER LEVEL TO VERIFY. ALSO CORE FLOOD ADDITION VALVES MAY BE LEAKING BY.

l l

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-013 SHEET CF-13 l

SENSING ELEMENT: CF-2-LS3 I

\\_/

AR-305 Rev. 26 Page 45 l

i

/

ENCLOSURE 1

(

(Page 44 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-04 E-08-04 CF TANK B LEVEL HIGH/LOTN EVENT POINT 0118 i

INDICATED CONDITION:

o CFT-1B LEVEL AS SENSED BY CF-2-LS4 IS ?.13'4" REDUNDANT INDICATION WHICH WILL VERIFY ALARM.

l

' f o CONTROL BOARD INDICATORS CF-2-LI3 OR CF-2-LI4 o COMPUTER POINT P201 s

OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL LEVEL o REFER TO OP-401 FOR THIS CONDITION DISCUSSION:

A HIGH CORE FLOOD TANK LEVEL MAY INDICATE CORE FLOOD CHECK VALVES LEAKING 1

BY. OBSERVE MAKEUP TANK LEVEL AND PRESSURIZER LEVEL TO VERIFY. ALSO CORE i

FLOOD ADDITION VALVES MAY BE LEAKING BY.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

l l

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-2-LS4 i

AR-305 Rev. 26 Page 46

ENCLOSURE 1 g

(Page 45 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-04 E-08-04 CF TANK B LEVEL HIGH/ LOW EVENT POINT 0119 INDICATED CONDITION:

o CFT-1B LEVEL AS SENSED BY CF-2-LS3 IS $12'3" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

)

[

o CONTROL BOARD INDICATORS CF-2-LI3 OR CF-2-LI4

\\.

o COMPUTER POINT P201 OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL LEVEL o REFER TO OP-401 FOR THIS CONDITION DISCUSSION:

A LOW CORE FLOOD TANK LEVEL MAY INDICATE CORE FLOOD ISOLATION VALVES ARE LEAKING BY. OBSERVE MAKEUP TANK LEVEL AND PRESSURIZER LEVEL TO VERIFY.

ALSO CORE FLOOD SAMPLE VALVES MAY BE LEAKING BY.

4 REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

i l

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-2-LS3 l

v[

AR-305 Rev. 26 Page 47 i

l

i t'

ENCLOSURE 1

(

(Page 46 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-04 E-08-04 l

CF TANK B LEVEL j

HIGH/ LOW l

1 EVENT POINT 0120 INDICATED CONDITION:

o CFT-1B LEVEL AS SENSED BY CF-2-LS4 IS 512'3" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

,p

!(

o CONTROL BOARD INDICATORS CF-2-LI3 OR CF-2-LI4 o COMPUTER POINT P201 i

l

\\

i OPERATOR ACTIONS FOR A VALID ALARM:

l i

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL LEVEL o REFER TO OP-401 FOR THIS CONDITION j

l DISCUSSION:

A LOW CORE FLOOD TANK LEVEL MAY INDICATE CORE FLOOD ISOLATION VALVES ARE LEAKING BY. OBSERVE MAKEUP TANK LEVEL AND PRESSURIZER LEVEL TO VERIFY.

j l

ALSO CORE FLOOD SAMPLE VALVES MAY BE LEAKING BY.

REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-2-LS4 O

AR-305 Rev. 26 Page 48

ENCLOSURE 1 l \\,

(Page 47 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-05 E-08-05 CF TANK B PRESS HIGH/ LOW EVENT POINT 0113 l

INDICATED CONDITION:

i 1

o CFT-1B PRESSURE AS SENSED BY CF-1-PS3 IS E615 PSIG 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[N o CONTROL BOARD INDICATORS CF-1-PI3 OR CF-1-PI4

\\

t OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL PRESSURE l

o REFER TO OP-401 FOR THIS CONDITION l

I DISCUSSION:

INCREASING REACTOR BUILDING TEMPERATURES, NITROGEN VALVE LEAKBY FROM N2

{

l BOTTLES, OR INCREASING CFT WATER LEVEL MAY CAUSE CORE FLOOD TANK PRESSURES TO RISE.

PRESSURE LIMITS ARE ESTABLISHED PER TS, REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-1-PS3 C

AR-305 Rev. 26 Page 49

(~

ENCLOSURE 1

( }/

(Page 48 of 52)

ESE ANNUNCIATOR RESPONSE ESB-JH2-08-05 E-08-05 1

CF TANK B PRESS HIGH/ LOW EVENT POINT 0114 I

INDICATED CONDITION:

o CFT-1B PRESSURE AS SENSED BY CF-1-PS4 IS >615 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 CONTROL BOARD INDICATORS CF-1-PI3 OR CF-1-PI4 OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL PRESSURE o REFER TO OP-401 FOR THIS CONDITION DISCUSSION:

INCREASING REACTOR BUILDING TEMPERATURES, NITROGEN VALVE LEAKBY FROM N2 1

BOTTLES, OR INCREASING CFT WATER LEVEL MAY CAUSE CORE FLOOD TANK PRESSURES

{

TO PISE.

l PRESSURE LIMITS ARE ESTABLISHED PER TS, REFER TO TS FOR ADMINISTRATIVE j

REQUIREMENTS.

l

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-1-PS4 O

AR-305 Rev. 26 Page 50

ENCLOSURE 1

,/^(

(Page 49 of 52) l (m_/

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-05 E-08-05 CF TANK B PRESS HIGH/ LOW i

i EVENT POINT 0115 INDICATED CONDITION:

l o CFT-1B PRESSURE AS SENSED SY CF-1-PS3 IS $585 PSIG l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i

(

o CONTROL BOARD INDICATORS CF-1-PI3 OR CF-1-PI4 OPERATOR ACTIONS FOR A VALID ALARM:

o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL PRESSURE o REFER TO OP-401 FOR THIS CONDITION l

DISCUSSION:

DECREASING REACTOR BUILDING TEMPERATURES OR DECREASING CORE FLOOD TANK LEVELS MAY CAUSE CORE FLOOD TANK PRESSURE TO DECREASE.

PRESSURE LIMITS ARE ESTABLISHED PER TS, REFER TO TS FOR ADMINISTRATIVE REQUIREMERTS.

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-1-PS3

,n.

Nm AR-305 Rev. 26 Page 51

f

! (]j ENCLOSURE 1 (Page 50 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-05 E-08-05 CF TANK B PRESS HIGH/ LOW l

EVENT POINT 0116 INDICATED CONDITION:

o CFT-1B PRESSURE AS SENSED BY CF-1-PS4 IS $585 PSIG I

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CONTROL BOARD INDICATORS CF-1-PI3 OR CF-1-PI4 OPERATOR ACTIONS FOR A VALID ALARM:

l o DETERMINE CAUSE AND RETURN CORE FLOOD TANK TO NORMAL PRESSURE j

l o REFER TO OP-401 FOR THIS CONDITION DISCUSSION:

DECREASING REACTOR BUILDING TEMPERATURES OR DECREASING CORE FLOOD TANK j

LEVELS MAY CAUSE CORE FLOOD TANK PRESSURE TO DECREASE.

l PRESSURE LIMITS ARE ESTABLISHED PER TS, REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.

l l

I

~

REFEP' F.ES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: CF-1-PS4 O

AR-305 Rev. 26 Page 52 l

1 ENCLOSURE 1

(

(Page 51 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-06 E-08-06 CF TANK B DISCH VALVE OPEN/ CLOSED EVENT POINT 010 3 INDICATED CONDITION:

o RCS PRESSURE AS SENSED BY RC-3A-PS3 IS 5690 PSIG AND CFV-6 IS NOT FULL CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

(~.

s,,)

o CONTROL BOARD INDICATOR RC-158-PI2 AND CFV-6 POSITION INDICATION ts OPERATOR ACTIONS FOR A VALID ALARM:

o CLOSE CFV-6 OR STOP RCS PRESSURE DECREASE DISCUSSION:

CFV-6 IS A NORMALLY DE-ENERGIZED VALVE. THE BREAKER WILL HAVE TO BE CLOSED AT ES MCC 3AB PRIOR TO VALVE OPERATION.

REFERENCES:

DRAWING 208-013 SHEET CF-13 SENSING ELEMENT: RC-3A-PS3, 33C VALVE CLOSED CONTACT AR-305 Rev. 26 Page 53

1 n

ENCLOSURE 1

(

(Page 52 of 52)

ESE ANNUNCIATOR RESPONSE ESB-]H2-08-06 E-08-06 CF TANK B DISCH VALVE OPEN/ CLOSED EVENT POINT 0104 INDICATED CONDITION:

RCS PRESSURE AS SENSED BY RC-3A-PS3 IS 2702.5 PSIG AND CFV-6 IS NOT FULL OPEN REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CONTROL BOARD INDICATOR RC-158-PI2 AND CFV-6 POSITION INDICATION Qq OPERATOR ACTIONS FOR A VALID ALARM:

o OPEN CFV-6 OR STOP RCS PRESSURE INCREASE DISCUSSION:

CFV-6 IS A NORMALLY DE-ENERGIZED VALVE. THE BREAKER WILL HAVE TO BE CLOSED AT ES MCC 3AB PRIOR TO VALVE OPERATION.

SENSING ELEMENT: RC-3A-PS3, 33 VALVE OPEN CONTACT

[LJ AR-305 Rev. 26 Page 54 (LAST PAGE)