TABI,E 3.3-5 ENGINEERED SAFETY FEATURES RESPONSE TI5fES INITIATING SIGNAL AND FUNCTION RESPONSE TIhlE IN SECONDS 1.
Manual a.
Not Applicable b.
CSAS Containment Spray Not Applicable c.
CIS Containment Isolation Not Applicable d.
RAS Containment Sump Recirculation Not Applicable e.
AFAS Auxiliary Feedwater Initiation Not Applicable 2.
hgssurizer Pressure-Low a.
Safety Injection (ECCS) s 30*/30**
3.
Containment Pressure-liinh a.
Safety Injection (ECCS) s 30*/30**
b.
Containment Isolation s 30 c.
Containment Fan Coolers s 35*/10**
4.
Containment Pressure-Hinh a.
Containment Spray 5 60*/60**(l) 5.
Containment Radiation-High a.
Containment Purge Valves Isolation s7 Sih P
P CALVERT CLIFFS UNIT 1 3/4 3-20 Amendment No. 4/, //, //,
O TABLE 3.3-5 ENGINEERED SAFETY FEATURES RESPONSE TINfES INITIATING SIGNAL AND FUNCTION RESPONSE TIhfE IN SECONDS 1.
Manual a.
Not Applicable b.
CSAS Containment Spray Not Applicable c.
CIS Containment Isolation Not Applicable d.
RAS Containment Sump Recirculation Not Applicable e.
AFAS Auxiliary Feedwater Initiation Not Applicable 2.
Pressurizer Pressure-Low a.
Safety Injection (ECCS) s 30*/30**
3.
Containment Pressure-IIinh a.
Safety Injection (ECCS) s 30*/30**
b.
Containment Isolation s 30 c.
Containment Fan Coolers s 35*/10**
4.
Containment Pressure-flieh a.
Containment Spray s 60*/60**(l) 5.
Containment Radiation-Hinh a.
Containment Purge Valves Isolation s7 CALVERT CLIFFS - UNIT 2 3/4 7-9 Amendment No. /, //, //,
j
- _-