Proposed Tech Specs for Diesel Generator Testing,Allowed out-of-svc Time & Surveillance Requirements for Offsite & Onsite Ac Electrical Sources
ML20215C522
Person / Time
Site: Grand Gulf 
Issue date: 12/09/1986
From:
MISSISSIPPI POWER & LIGHT CO.
To:
Shared Package
ML20149C259 List:
References
TAC-55863, NUDOCS 8612150212
Download: ML20215C522 (9)


Text

.-

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES A.C. SOURCES - OPERATING LIMITING CONDITION FOR OPERATION 3.3.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

~

a.

Two physically independent circuits between the offsite transmission network and the onsite Class IE distribution system, and

b. ' Three separate and independent diesel generators, each with:

1.

Separate day fuel tanks containing a minimum of 220 gallons of fuel.

2.

A separate fuel s'.orage system containing a minimum of:

a) 57,200 gallons of fuel each for diesel generators 11 and 12, and b) 39,000 gallons of fuel for diesel generator 13.

t 3.

A separate fuel transfer pump.

I APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

ETION:

M M /? T With either enc effsite circuit ;r dic:ci g:ncr;t;r 11 ;r 12 ;f 150 above required A.C. electrical power sources inoperable, demonstr OPERABILITY of the remaining A.C. sources by performing S il-g lanc equirements 4.8.1.1.1.a within one hour and 4.8.1.1

.a.4,"

for one

' sel generator at a time, within two hours a at least once per 8 rs thereafter; restore at least two site circuits and diesel gene ors 11 and 12 to OPERABLE s us within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />

(

or be in at least SHUTDOWN within the 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD l

SHUTDOWN within the fo ing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

With one offsite circuit and s

generator 11 or 12 of the above

~

required A.C. electrical power ces inoperable, demonstrate the OPERABILITY of the remaini A.C. so es by performing Surveillance Requirements 4.8.1.1.1 within one hour d 4.8.1.1.2.a.4,a for one diesel generator a time, within two hours d at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> therea r; restore at least one of the perable A.C.

sources to RABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in least HOT SHUT-DOWN wi n the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN with the following 24 rs.

Restore at least two offsite circuits and diese nera-rs 11 and 12 to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of itial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and i CDLG SHUIDGW -ith;. thu felle.ing 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

" Specification 4.8.1.1.2.a.4 must be performed for diesel generator 13 only when the HPCS system is OPERABLE.

GRAND GULF-UNIT 1 3/4 8-1 Amendment No.

l 8612150212 861209 PDR ADOCK 05000416 P

PDR

Insert for Technical Specification Page 3/4 8-1

' ACTION:

a.

With one offsite circuit of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Demonstrate the OPERABILITY of the remaining OPERABLE diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4* for one diesel generator at a time within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTOOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

With either diesel generator 11 or 12 of the above required A.C.

electrical power sources inoperable, demonstrate the OPERABILITY of the above required A.C. offsite sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Demonstrate the OPERABILITY of the remaining OPERABLE diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4* within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the inoperable diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

1

?

i J16ATTC86050801 - 1

~

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION (Continued)

ACTION (Continued) y gg p-

"!th cith:r di:::? g:n:r:t:r Il er 12 Of th: 25::: r:g_?r:d ^.C.

/'

electrical power sources inoperable, in addition to ACTION a or b above, as applicable, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required syst s,

ubsystems, trains, components and devices that depend on the r aining diesel generator 11 or 12 as a source of emergency p er are 1so OPERABLE; otherwise, be in at least HOT SHUTDOWN wi in the next hours and in COLD SHUTDOWN within the following 24 curs.

d.

With two the above required offsite circuits inoper le, demonstrate he OPERABILITY of three diesel generator by performing Surveillance quirement 4.8.1.1.2.a.4*, for one di sel generator at a time, within o hours and at least once per 8 ours thereafter, unless the oiesel enerators are already opera 'ng; restore at least one of the inoperab offsite circuits to OP BLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at ast HOT SHUTDOWN wit n the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

With only one offsite c cuit restored to PERA8LE status, restore at least two offsite circ 'ts to OPERAB status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss o be in at east HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />'and in COLD SH OWN thin the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

e.

With diesel generators 11 and 1 the above required A.C.

electrical power sources inop able, demonstrate the OPERABILITY of the remaining A.C. sources perform' g Surveillance Requirements 4.8.1.1.1.a within one ho and 4.8.1..

.a.4", within two hours and at least once per 8 hou thereafter; res re at least one of the in-operable diesel gener ors 11 and 12 to OP BLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least H SHUT 00WN within the ne 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTOOWN within t following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Resto both diesel genera-tors 11 and 12 OPERABLE status within 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial i

loss or be in t least HOT SHUT 00VN within the nex 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUT 00" within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

f.

With di el generator 13 of the above required A.C. elec ical power sourc inoperable, demonstrate the OPERABILITY of the rem 'ning A.C. sources by performing Surveillance Requirements 4.8.1.1..a wi in one hour and 4.8.1.1.2.a.4, for one diesel generator at ime, within two hours and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore the inoperable diesel generator 13 to OPERABLE status with 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> cr declare the HPCS system inoperable and take the ACTION c q. ired by Sp :!fic tier 3.5.1.

" Specification 4.8.1.1.2.a.4 must be performed for diesel generator 13 only when the HPCS system is OPERABLE.

GRAND GULF-UNIT 1 3/4 8-2 A m W m u ct-No.

E

~

Insert for Technical Specification Page 3/1 8-2 ACTION (continued) c.

With one offsite circuit and diesel generator 11 or 12 of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

Demonstrate the OPERABILITY of the remaining OPERABLE diesel generators, for one diesel generator at a time, by perfonning Surveillance Requirement 4.8.1.1.2.a.4* within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. Restore at least one of the inoperable A.C. sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

4 d.

With either diesel generator 11 or 12 of the above required A.C.

electrical power sources inoperable, in addition to ACTION b or c, as applicable, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> that all required systems, subsystems, trains, components and devices that depend on the remaining OPERABLE diesel generator 11 or 12 as a source of emergency power are also OPERABLE; otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />..

e.

With both of the above required offsite circuits inoperable, demon-strate the OPERABILITY of the three required diesel generators, by performing Surveillance Requirement 4.8.1.1.2.a.4* for one diesel generator at a time within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless the diesel generators are already operating.

Restore at least one of the above required offsite circuite to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least H0T SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

f.

With diesel generators 11 and 12 of the above required A.C.

electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

Restore at least one of the inoperable diesel generators 11 or 12 to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and demonstrate the OPERABILITY of diesel generator 13 within the next 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> by performing Surveillance Requirement 4.8.1.1.2.a.4* or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

g.

With diesel generator 13 of the above required A. C. electrical power sources inoperable, demonstrate the OPERABILITY of the offsite A.C.

sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Demonstrate the OPERABILITY of the remaining OPERABLE diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.4 for one diesel generator at a time within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. Restore diesel generator 13 to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or declare the HPCS system inoperable and take the ACTION required by Specification 3.5.1.

J16ATTC86050801 - 2

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the onsite Class 1E distribution system shall be:

a.

Determined OPERABLE at least once per 7 days by verifying correct breaker alignments and indicated power availability, and b.

Demonstrated OPERALLE at least once per 18 months during shutdown by manually transferring unit power supply from the normal circuit to the alternate circuit.

4.8.1.1.2 Each of the above required diesel generators shall be demonstrated OPERABLE:

a.

In accordance with the frequency specified in Table 4.8.1.1.2-1 on a STAGGERED TEST BASIS by:

1.

Verifying the fuel level in the day tank.

2.

Verifying the fuel level in the fuel storage tank.

3.

Verifyino the fuel transfer pump starts and transfers fuel from the storoge system to the day tank.

4.*

Verifyingthedieselstartsfromh condition and accelerates l

to at least 441 rpm for diesel generators 11 and 12 and 882 rpm for diesel generator 13 in less than or equal to 10 seconds.

The generator voltage and frequency shall be 4160 416 volts and 60 1.2 Hz within 10 seconds after the start signal.

The diesel generator shall be started for this test by using one of the following signals:

a)

Manual.

b)

Simulated loss of offsite power by itself.

c)

Simulated loss of offsite power in conjunction with an ESF actuation test signal.

d)

An ESF actuation test signal by itself.

5.# Verifying the diesel generator is synchronized, loaded to greater l

than or equal to 5450 kW but not to exceed 5740 kW fc: diesel generators 11 and 12 and 3300 kW for diesel generator 13 in less than or equal to 60 seconds, and operates with these loads for at least 60 minutes.

6.

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.

7.

Verifying the pressure in all diesel generator air start receivers to be greater than or equel to:

a) 160 psig for diesel generators 11 and 12, and b) 175 psig for diesel generator 13.

b.

At least once per 31 days and after each operation of the diesel where the period of operation was greater than or equal to I hour by checking for and removing accumulated water from the day fuel tanks.

  • INSERT G AND GULF-UNIT 1 3/4 8-3

/banboT O#*

n--

Insert for Technical Specification Page 3/4 8-3

  • All diesel generator starts for the purpose of this Surveillance Requirement The diesel generator start (10 may)be~ preceded by an engine prelube period.from standby conditions shall be perfor sec these surveillance tests. All other engine starts for.the purpose of this surveillance testing may be preceded by warmup procedures as recommended by the manufacturer so that the mechanical stress and wear on the diesel engine is minimized.

f The diesel generator loading (60 sec) shall be performed at'least once per 184 days in these surveillance tests. All other diesel engine runs for the purpose of this surveillance testing may include gradual loading as recommended by the manufacturer so that the mechanical stress and wear on the diesel engine is minimized.

J16ATTC86050801 - 4

C 4

TABLE 4.8.1.1.2-1 DIESEL GENERATOR TEST SCHEDULE Number of Failures in Last 100 Valid Tests

  • Test Frequency 11 At least once per 31 days 2

At least once per 1~ days 2 3 At least once per 7 days 1"

^t Ic::t tr.:: p:r 3 d:3; m

"Criter r determining number of failures and numb valid test shall be cordance with Regulatory on C.2.e of Regulatory Guide 1.1 ision 1, 1977, where the last 100 tests are determined on uclear unit basis.

For the purposes of this tes dule, only tests conducted after the OL issua e e shall be included in the tation of the "las valid tests." Entry into this. test schedu 1 be

_de at the 22 d:j tc:t 'rcque.;,.

  • Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108. Revision 1, August 1977 with exceptions as noted in the FSAR, but determined on a per diesel generator basis.

For the purposes of this test schedule, only valid tests conducted after the OL issuance date shall be included in the computation of the "last 100 valid tests".

For the purpose of determining the required test frequency, the previous test failure count may be reduced to zero if a major diesel overhaul is completed, provided that the overhaul, including appropriate post-maintenance operation and testing, is specifically approved by the manufacturer and if acccptable reliability has been demonstrated and accepted by the NRC.

GRAND GUcF t 1

3/4 8-8 b4 M '# N-

ELECTRICAL POWER SYSTEMS BASES A.C. SOURCES, D.C. SOURCES and ONSITE POWER DISTRIBUTION SYSTEMS (Continued) restricted as noted in a letter from E. G. Adensam to L. F. Dale, dated 17 July 1984.

The SSW pump load values are not used as the largest single load rejected from the diesel generators when testing to meet the requirements of Regulatory Guide 1.9.

Since the SSW system supplies cooling water to its associated diesel 4

generator, tripping the SSW pump to perform this test would result in loss of the diesel generator.

~ ;

An exception is taken with respect to Regulatory Guide 1.108 requirements on the surveillance test frequency for the diesel generators in relationship to the number of valid failures.

The test frequency provided in Table 4.8.1.1.2-1 provides adequate assurance of diesel generator availability without causing degradation due to excessive engine starts. The determination of valid failures on a per diesel generator basis reflects that failures on one diesel generator does not necessarily reflect the same problem on the remaining diesel generators.

GRAND GULF-UNIT.1 B 3/4 8-la Amendment No.

,,.O Ps.NT st$0N BAxith N AY BA ASwfLL h4/7p%

F R ANkLIN FUTull(

il il il l

ji tISay i

O O

d JS222 JS218 JS242 JS246 f

~~

S00mv E AST Bus 22nv TURBIN( l 6ENERATOR Butt 6tH l

{)

l MAIN Q y JS262 JS224 JS236 us uae 22Kv/Ss KV O"

N. 2(Y T I

JS211 JS223 JS235 g

__j HoffS i, g o

__o JS234 J33g3 JS200

. JS221 JS233 JS245 6.

015Cmm4CT JS209 I9F

$Culf SRCAmtli s ik e ISkvr4 e6mv -

J3208 JS220 JS232 JS2 4 4 JS207 JS289 JS238 JS243 OISCONNECT JS230 3

O-2.

SkN.WWNW

  • JS206 8GNPS DESIGNATION JS20S JS287 500KV/

JS220 JS248 gjxgggg,

seavict a y S00KV/

senvicg a ) j'"V 3*

usu etsioNAfl0N hFun JS204 JS286 mf uR JS228 JS240 2iy 34 5 v H.

ii J,6,,

JS20, JS215 J,6,5
JS22, m 3.

3A: r o,,,

I I

I N. 1 l 22xv i

WRATM 552 2105 JI652 S00nV'wf5T Bus l

Cl g

JI656 552-1905 l

(,

J66S3 JI657 og I_

34 Suv_ Sus 2in 34 Snv Sus lla l

Tupeisd 808tDING l unit I I

I I

I I ~

l I

I 569 20044 589-28014

$ 8 9-2102 A

$89-2 6 03 A 10 RabtAL will Seg.gl03A 569 il02A 589-II0lA 589-I I O4 A

~~~~~J IJ t 4 8 0 0 IJ I 6 t Si IJ t 60 38 tJ I 60 ?l LWif DK'E AR IJ f 6 3 Si IJ86278 IJ I 639)

IJ I 6 311

$$2 2 004 S$2-2808 S52 2002 552*2103 B DP BOP 552-1803 552-1102 552-1800 552-1104 IJ B 6121 (J 4 6186 (J 6 6041 IJ 8 60el kl uR Dl uR l> l 6 368 IJI628)

(J I 6 408 IJ t 6 3 21 N. 21 H. 6 3

$89-1903B

$89-18028 589-81010

$89-81048 589-20048 589-20068 589 21028 589 20038 f

f IJ t 6 3 73 IJI6281

. IJ 164 tl IJ I 63 3J IJ t 6 6 38 IJ 4 6 il IJ I 60Ss tJI6098 9

9 p

U g SF 34 Snv Sus 13M isa ip um kl um N.

2:

N.

Il 34 OnW but Elm 34 SEV sus 12R F/gswo

1. Swltchyard Power System