h A
OPERATIN' G DATA REPORT 1
50-344 DOCKET NO.
DATE 8-6-86 COMPLETED BY F.
J.
U3mer TELEPHONE 503-556-3713 Ext. 495 CPERATING STATUS Notes Trojan Nuclear Plant
- 1. Unit Name:
July 1986
- 2. Reporting Period:
3411
- 3. Licensed Thermal Power (MWt):
1216
- 4. Nameplate Rating (Gross MWe):
1130
- 5. Design Electrical Rating (Net MWe):
1100
- 6. Maximum Dependable Capacity (Gross MWe):
1050
- 7. Maximum Dependable Capacity (Net MWep:
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:
~
N/A N/A
- 9. Power Level To %hich Restricted,if Any (Net MWe):
N/A
- 10. Reasons For Restrictions.If Any:
This Month Yr. to Date Cumulative 44 0
86 % 3
- 11. Hours in Reporting Period 744 3554 53104
- 12. Number Of Ifours Reactor Was Critical 0
0 3887
- 13. Reactor Reserve Shutdown Hours 744 3495 52549
- 14. Hours Generator On-Line 0
0 3249
- 15. Unit Reserve Shutdown Hours 2536944 11288621 166243426_
- 16. Gross Thermal Energy Generated (MWH) 831D3 3629381 54447697
- 17. Gross Electrical Energy Generated (MWH) 792740 3439164 51530468
- 18. Net Electrical Energy Generated (MWH) 100 68.7 60.5
- 19. Unit Service Factor 100 68.7 64.2
- 20. Unit Availability Factor 101.5 64.4 56.5
- 21. Unit Capacity Factor (Using MDC Net) 94.3 59.8 52.5 l
- 22. Unit Capacity Factor (Using DER Net)-
0 1.6 14.8
- 23. Unit Forced Outage Rate
- 24. Shutdowns Scheduled Oser Next 6 Months (Type. Date,and Duration of Each):
N/A
"!^
I
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achieved N/A N/A INITIAL CRITICALITY N/A N/A INITIAL ELECTLCITY N/A N/A COMMERCIAL OPERATION (9/77) g 86101 g h h
4
' AVERAGE DAILY UNIT POWER LEVEL DOCKET NO: 50-344 UNIT: Troian DATE:
8-6-86~
COMPLETED BY:
F.
J.
Ulmer TELEPHONE: 503-556-3713 Ext. 495
. MONTH JULY 1986 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 1064 17 1066 2
1069 18 1061 3
1072 19 1057 4
1070 20 1055 l
3 1070 21 1060 6
1064 22 1063.
7 1069 23 1062 8
1066 1061 24 1063 1069 9
25 1059 1074 10 26 1061 1073 11 27 1064 1070 12-28 1066 13 29 1069 14 1066 30 1066 l
.j 15 1068 31 1065 16' 1067 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.
(9/77)
o e
50-344 DOCRET NO.
UNIT SilUIDOWNS AND POWER REDUCTIONS UNIT NAME Tro3an DATE 8-6-86 REPORT MONT11 July 1986 COMPLETED BY F_
3.
U l m o r-1El.ErtlONE 503-577-3713 Ext. 495
- 3 se 2 5
rs E
g.gg Licensee E,
gg cause A cy,,,cig,,
. j _g M'.
DJie y
j}
Prevent Recurrence g
g
.E g a:
Event
- T 9-Acekm to g
jdig Report a 50 5E e
6 NONE l
l l
I 2
3 4
F: Forced Reason:
Method:
Exhibit G. instreetions S: Scheduled A Equipment Fallure(Explain) 1-Manual for Preparation of Data B-Maintenance of Test 2 Manual Scram.
Entry Sheets for Licensee C Refueling 3 AufomsticSe:sm.
Event Repert (LER) File (NUREG-D-Regulatory Restriction 4-Other (Explain) 01611 E-Operatur T sining & Ucense Examination F Adndnistrative 5
G-Opera lunal Errug(Emplafn)
Exhibit I SaeneSimice p)/77)
II Osher (Esplain)
F I
TROJAN NUCLEAR' PLANT DOCKET NO:
50-344
SUMMARY
OF OPERATING EXPERIENCE DATE:
8-6-86 COMPLETED BY:
F.
J.
Ulmer TELEPHONE:
503-556-3713 OPERATIONS:
The Trojan Nuclear Plant entered the month of July in Mode 1 at full power and maintained full power through the end of the month.
During July the reactor coolant dose equivalent iodine remained constant at 10.6% of the 1 mei/gm technical specification limit and steam gene-rator leakage remained steady at 1/2 gpd.
A new heat balance procedure based on a primary calorimeter was imple-mented which compensates for feedwater flow element fouling and allows the reactor to operate at or near full thermal power throughout the fuel cycle.
MAJOR SAFETY-RELATED MAINTENANCE:
Testing of the mechanical overspeed mechanism of the turbine-driven auxiliary feedwater pump was conducted in order to remove the electrical overspeed unit.
The removal of the electrical overspeed unit was based upon reliability reviews of the auxiliary feedwater system.
It was found that the mechanical overspeed unit was not reliable, therefore, the electrical-overspeed unit was verified operable and the mechan-ical trip was disabled.
The turbine vendor is scheduled to be on-site in September to assist in the repair and testing of the mechanical trip device.
MISCELLANEOUS MAINTENANCE:
1.
Replacement of a digital rod position indication (DRPI) card occurred for control rod C-7 due to card failure.
2.
The
'A' spent fuel pool cooling pump was completely overhauled to include a new one-piece pump shaft and new bearing design.
3.
The corrosion inhibitor for the component cooling water system was changed, action taken to return the system to within specif1-cations.
The type of corrosion inhibitor used caused erroneous analytical results for system chlorides.
4.
Recalibration was conducted for loop
'B' reactor coolant system flow indication due to higher than normal indication.
MISCELLANEOUS:
1.
An NRC audit was conducted of Trojan's safety parameter display system (Westinghouse P-2500 computer system).
2.
An NRC audit of Security was conducted during July 22 to July 31, 1986.
3.
An NRC audit of procurement (purchasing) of materials was conducted July 14 to July 19, 1986.
4.
Trojan was aesignated a branch member of the National Academy for Nuclear Training based on the recent accreditation of three operator training programs.
/
F
'/
Portland General Electric Company Trojan Nuclear Plant August 6, 1986 P.O. Box 439 WSO-264-86 Rainier, Oregon 97048 (503)S56-3713 Trojan Nuclear Plant Docket 50-344 License NPF-1 Office of Resource Management US Nuclear Regulatory Commission Washington, DC 20555 Gentlemen Monthly Operating Data Report In accordance with the Trojan Nuclear Plant Technical Specifications reporting requirements, the monthly operating data ~ report is submitted for July, 1986.
Sincerely, W.
S.
Orser General Manager Attachment c:
Mr. John B.
Martin Regional Administrator, Region V U.S.
Nuclear Regulatory Commission Mr. Lynn Frank, Director State of Oregon Department of Energy e
ac I l t