PRAIRIEISLAND NUCLEAR 2
GENERATING PLANT Red Wing, Minnesota UNITS 1 AND 2-1 t
MINNE APOLl$ e ST. PAUL
.. = =.
l INSERVICE INSPECTION - EXAMINATION
SUMMARY
FEBRUARY 20, 1987 TO MARCH 3, 1987 FORCED EDDY CURRENT OUTAGE i
INSPECTION PERIOD 1 1
6-SECOND INTERVAL 4
NORTHERN STATES POWER COMPANY MINNEAPOLIS, MINNES0TA i
Report Date:
Commercial Service Date:
May 5,1987 December 16, 1973 V
'L_
- 1
I I
NORTHERN STATES POWER COMPANY PRAIRIE ISLAND NUCLEAR GENERATING PLANT - UNIT I INSERVICE INSPECTION - EXAMINATION
SUMMARY
FEBRUARY 20, 1987 TO MARCH 3, 1987 FORCED EDDY CURRENT OUTAGE INSPECTION PERIOD 1 SECOND INTERVAL Report Date:
May 5, 1987 Prepared by:
L.C. Dahlman M&SP Specialist Reviewed by:
R.A.Kellerhall M&SP Specialist Approved by: U
~
J.L.
Ricker Superintendent, Materials and Special Processes
~
6 Commercial Service Date:
December 16, 1973
~
o
$e 2
m 1
u
I Inservice Inspection - Examination Summary j
PRL RIE ISLAND NUCLEAR GENERATING PLANT - UNIT I INDEX
1.0 INTRODUCTION
2.0
SUMMARY
OF RESULTS 3.0 ASME CLASS 1 AND 2 COMP 0NENTS 3.1 Examination Plan 3.2 Examination Methods 3.3 Examination Procedures 3.4 Equipment and Materials 3.5 Personnel 3.6 Evaluation 3.7 Examination Reports and Documentation 3.8 Summary of Results 4.0 EDDY CURRENT EXAMINATION OF STEAM GENERATOR TUBING APPENDIX A - ASME Class 1 Examinations Inservice Inspection - Examination Summary Tables:
Table SI.3
- Steam Generators Table S1.5
- Piping Pressure Boundary Table S-II
- Examination Comparison Summary Table III
- Isometric Summary APPENDIX B - ASME Class 2 Examinations Inservice Inspection - Examination Summary Tables:
Table S2.1.1
- Pressure Vessels - Steam Generators Table S-II
- Examination Comparison Summary Table III
- Isometric Summary APPENDIX C - Component Supports Inservice Inspection - Examination Summary Tables:
Table SCSI.1
- ASME Class I Component Supports Table S-II
- Examination Comparison Summary APPENDIX D -
, Table I
- Personnel Listing Table II
- Ultrasonic Calibration Blocks Table III
- Procedure Listing Table IV
- Equipment and Materials APPENDIX E - STEAM GENERATOR NO. 12 H0T LEG Eddy Current Tube Sheet Maps and Cumulative Data Reports
$a APPENDIX F - STEAM GENERATOR N0. 12 COLD LEG E
s Eddy Current Tube Sheet Maps and Cumulative date Reports 9
01 APPENDIX G - NIS-1 Form
- lii Form NIS-1. Owners' Data Report for Inservice insoections i
\\
INSERVICE INSPECTION - EXAMINATION
SUMMARY
PRAIRIE ISLAND NUCLEAR GENERATING PLANT - UNIT l' j
February 20, 1987 to March 3, 1987
1.0 INTRODUCTION
This report is a summary of the examinations performed during a forced outage at the Prairie Island Nuclear Generating Plant - Unit 1.
The examinations were performed during the plant's forced out-age from February 20, 1987 to March 3, 1987.
Prairie Island - Unit I began commercial operation on December 16, 1973.
This report identifies the components examined, the examination methods used, the examination number; and, summarizes the examina-tion results of each of the following areas:
- 1. Pressure retaining components and supports of the reactor coolant and associated systems classified as ASME Class 1 and 2.
- 2. Eddy current examination of the Steam Generator Tubing.
2.0
SUMMARY
OF RESULTS The evaluation of all the results from the inservice examinations indicated that the integrity of these systems has been maintained.
To assure continued integrity of the steam generators (S.G.),
a to-tal of 19 tubes in S.G.12 were mechanically plugged.
3.0 ASME CLASS 1 3.1 EXAMINATION PLAN The examination plan focused on the pressure retaining compo-nents and their supports of the reactor coolant and associated auxiliary systems classified as ASME Class 1.
The examination plan was based on the examination requirements of the ASME Boiler and Pressure Vessel Code Section XI, 1980 Edition through and including the Winter 1981 Addenda, and complied with Prairie Island's Technical Specification, Sec-tion TS 4.15.
The examination is in accordance with the pro-gram submitted to the United States Nuclear Regulatory Commis-sion on March 27, 1981 titled, "ASME Code Section XI Inservice Inspection and Testing Program and Information Required for NRC Review of Requests for Relief From ASME Code Section XI Requirements".
3.2 EXAMINATION METHODS Ultrasonic examination methods and techniques were used to 5
perform the volumetric examinations. The ultrasonic test sys-g tems consisted of an ultrasonic digital / analog tester and a a:
two channel strip chart recorder. One channel of the recorder Of was calibrated to reflect ultrasonic screen height (amplitude) and the second channel was calibrated to indicate metal path g
a.
,I (range) to the reflector.
This approach to the examination j
gives a permanent record to the extent possible.
Liquid penetrant or magnetic particle examination methods were used to perform the surface examinations.
The liquid pen-etrant examinations were performed using color contrast-solvent removable materials. Magnetic particle ex-aminations were performed using either a yoke with dry powder or an AC L-10 coil with fluorescent prepared bath.
All visual examinations were aided, when necessary, with arti-ficial lighting and verified for adequacy with an 18% neutral gray card with a 1/32 inch black line.
3.3 EXAMINATION PROCEDURES The ultrasonic examination procedures for piping welds com-plied with the requirements of Appendix III of ASME Section XI that was issued in the Winter 1981 Addenda.
All other proce-dures complied with the requirements of the 1980 Edition through and including the Winter 1981 Addenda of ASME Section XI.
A listing of the procedures used for the examinations is shown in Table III of Appendix B.
3.4 E0VIPMENT AND MATERIALS All equipment and expendable materials used in the examina-tions are listed either by serial number or type along with their respective calibration date or batch number in Table IV of Appendix D.
The ultrasonic calibration standards used in the examinations are listed in Table II of Appendix D.
These standards are owned and maintained by NSP at the plant site.
3.5 PERSONNEL Northern States Power Company contracted Lambert, MacGill, Thomas, Inc. to perform balance of plant examinations.
Hart-ford Steam Boiler Inspection and Insurance Company, represent-ing ANII, provided the Authorized Inspection.
All personnel involved in the performance or evaluation of ex-aminations are listed along with their title, organization and ASNT Level of Certification in Table I of Appendix 0.
Certifications for examination personnel are maintained on file by Northern States Power Company.
3.6 EVALUATION (a
o Any indications disclosed in the examinations were evaluated g
by the examiner at the time, in accordance with the rules of m
the procedure and ASME Section XI.
y 2
a.
I The ultrasonic examiner (s) was aided in their evaluation by a j
calibration performed on a standard reference before each day's examination, checked before and after each individual examination and at intervals not exceeding four (4) hours.
In
- addition, the ultrasonic data was recoroed on strip charts which were made a part of the inspection report, and permitted further evaluation.
3.7 EXAMINATION REPORTS AND DOCUMENTATION All examination reports and documentation are maintained on file by Northern States Power Company. Table I of Appendix A, B,
and C identifies the examination report number (s) for each item examined.
Many of the items identify more than one ex-amination report because of the different types of examina-tions performed on the item.
Table I of Appendix A, B, and C summarizes all the examina-tions performed to date and identifies the amount that will be examined in the future to complete the ten year examination requirements.
For retrieval purposes, the prefix of the in-spection report number corresponds with the year the inspec-tion was performed.
The examination report numbers for this outage are prefixed with "87 ".
Table II of Appendix A,
B, and C compares the baseline ex-amination or previous results with the results obtained during this examination.
Table III of Appendix A, B, and C identi-fies the isometric drawings that were used for the examinations.
The personnel, ultrasonic calibration blocks, procedures, equipment and materials that were used for the in-spection are identified in the tables of Appendix D.
Appendix G contains the Form NIS-1 titled, "0wner's Data Report for Inservice Inspections".
3.8
SUMMARY
OF RESULTS The following is a list of anomalies detected:
TYPE AND NUMBER ITEM EXAM 0F SYSTEM ID METHOD INDICATIONS
$E Seal Injection A RCVCH-1247 VT Spring Canister o
Not Functional g
c:
RCC Crossover RCC-A-10 PT 4 Rounded W
2 m
I The anomalies were either accepted by an engineering evalua-tion or acceptable per code; the hanger that was found to be non-functioning was turned over to the system engineer and a design modification was issued; the rounded PT indications were found acceptable per IWB 3514.
4.0 EXAMINATION OF THE STEAM GENERATOR TUBING During the February 1987 unscheduled leaker outage 100% of all ac-cessible tubes in steam generator 12 hot leg and 23% of the acces-sible tubes in steam generator 12 cold leg were examined.
Included in the cold leg examination were 40 tubes of special interest (pre-viously degraded tubes). The examination was conducted utilizing the multifrequency eddy current technique. The probes were all differentially wound bobbin coil design multiplexed at frequencies of 400KHZ,
- 200KHZ, 100KHZ and 10KHZ in both the differential and absolute modes. The program was as follows:
- 1. Cold leg examinations were performed from the seventh support plate on the hot leg side through the tube end on the cold leg side. These examinations were completed using 0.720 inch diam-eter magnetically biased probes.
2.
Hot leg examinations were performed from the first support plate on the hot leg side through the tube end on the hot leg side. These examinations were completed using 0.740 inch diam-eter magnetically biased probes.
- 3. A select sample (approximately 78) of tubes were examined with the rotating pancake coil (RPC) technique in steam generator 12 hot leg. The inspection strategy was to supplement the bobbin coil data and further characterize indications of percent through wall, undefined and distorted signals. Included were 31 tubes which were examined with the RPC technique in March 1986.
Westinghouse Electric Corporation was contracted to acquire and evaluate the eddy current data. Canam Inspection was contracted to perform a completely independent evaluation of all data acquired.
The scope of all the work contracted was completed using remote po-sitioning devices and the Zetec MIZ-18 digital test equipment along with associated acquisition and DDA-4 analysis software.
Summaries of tubes examined, indication distribution, tubes plugged this outage and total tubes plugged can be found in Tables I through IV respectively.
Tube sheet maps and cumulative lists of plugged tubes and indica-tions by depth range can be found in Appendices E and F for steam generator 12 hot leg and cold leg respectively.
O he Y
8 E
a.
TABLE I Total tubes examined PROGRAM TUBE COUNT PERCENT 12 hot leg 3351 100 12 cold leg 761 23 TABLE II Distribution of indications INDICATION RANGE HOT LEG COLD LEG 0% T0 19%
3 11 20% TO 29%
4 10 30% TO 39%
2 3
40% TO 100%
11 1
NOTE: Hultiple indications in the same tube are categorized by the larger call.
TABLE III Tubes plugged this outage S/G NO.
R0W - COLUMN
%TWD LOCATION 12 7
20 UDI TEH + 4.9 12 8
21 81 TEH + 4.3 12 6
22 UDI TEH + 3.7 12 3
24 UDI TEH + 4.3 12 9
25 97 TEH + 4.4 12 8
33 UDI TEH + 3.9 12 1
35 99 TEH + 8.9 12 1
37 84 TEH + 6.8 12 1
38 96 TEH + 4.5 12 17 38 95 TEH + 6.5 12 20 38 81 TEH + 7.5 12 16 41 97 TEH + 5.8 12 4
48 51 TEH + 9.3 12 12 48 SQR TEH +13.0 12 8
50 44 TEH +15.3 12 1
57 90 TEH + 3.2 12 5
57 UDI TEH + 6.7 12 6
60 UDI TEH + 8.6 12 37 62 DTI TSH + 0.0 NOTES: Note from TABLE II applies.
SQR (Squirrel) indications are small non-quantifiable multiple stress corrosion cracks and is a pluggable indication. The six UDI's (undefined indication) and one DTI (distorted tube sheet indication) were removed from service 8
based on crack like RPC indications.
E C
is TABLE IV C
Total tubes plugged to date ni 8
S/G N0.
TUBE COUNT PERCENT
- s 12 56 1.65 E
i 1
i APPENDlX A s
ASME CLASS I EXAMINATIONS I
s a
s a
o x
$2c.
Q.
l
o NORTHERN STATES POWER CO.
TABLE SI.3-PRAIRIE ISLAND UN!T I PAGE 1
OF 3 INSERVICE INSPECTION-EXAMINATION
SUMMARY
~
MAJOR ITEM: STEAM GENFRATORS SUB EXAM COMPONENT OR SYSTEM INSP.
_ ITEM INSPECTION ITEM CATE-A D
R PT F
PER.
AMT.
EXAM (DENTIFICATION REPORT NOL G
B-B PRESSURE RETAINING WELDS IN OTHER THAN REACTOR VESSELS B2.30 B-B HEAD WELDS
-NONE-B2.40 B-B
_iU3ESHEET-TO-HEAD WELDS STEAM GENERATOR N0. 11 ONE 33%
33%
W-A 0'-12'87-023,024,025,012 W-A TWO 34%
THREE 33%
STEA, M' AERATOR NO.12 ONE 33%
W-o TWO 34%
THREE 33%
B-D FULL PENETRATION WELDS OF R6I1LE.IN VESSELS -
INSPECTION PROGRAM B B3.130 B-D
'N0ZZLE TO VESSEL WELDS
-NONE-B3.140 P-D N0ZZLE INSIDE RADIUS SECTION STEAM GENERATOR NO. 11 INLET N0ZZLE ONE 1
- RELIEF NO. 66 0UTLET N0ZZLE THREE 1
STEAM GENERATOR N0. 12 INLET N0ZZLE THREE 1
- RELIEF NO. 66 0UTLET N0ZZLE TWO 1
Form 172476 p en PPM-0044, Rev. 0 (1/87)
(M&SP 5.2) g gpgqiggggggi_g 7
o NORTHERN STATES POfER CO.
TABLE S1.3 PAGE 2 OF 3 PRAIRIE ISLAND UNIT INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: STEAM GENERATORS SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CAT A
D R
ON PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
G B-F PRESSURE RETAINING DISSIMILAR METAL WELDS B5.70 B-F NOMINAL PIPE SIZE 4" AND GREATER, N0ZZLE-TO-SAFE END BUTT WELDS STEAM GENERATOR NO. 11 INLET ONE 1
OUTLET THREE 1
STEAM GENERATOR NO. 12 INLET ONE 1
OUTLET THREE 1
B5.80 B-F NOMINAL PIPE SIZE LESS
-N0NE-THAN 4" B5.90 B-F SOCKET WELDS
-NONE-B6.90 B-G-1 PRESSURE RETAINING BOLTING GREATER THAN 2" IN DIAMETER
-NONE-B-G-2 PRESSURE RETAINING BOLTING, 2" AND LESS IN DIAMETER B7.30 B-G-2 BOLTS, STUDS AND NUTS STEAM GENERATOR NO. 11 INLET MANWAY ONE 5
16 BOLTS, 1 THRU 16 B5-023, 032 BOLTS, 1 THRU 16 86-014.018 (REPEAT)
TWO 5
THREE 6
r.. me pen PPM-0044, Rev. 0 (1/87)
I I
LCD031485WMH01-LT
NORTHERN STATES POyR CO.
TABLE SI.3 PRAIRIE ISLAND UNIT PAGE 3
op 3 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: STEAM GENERATORS SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM D
RIPT O F
PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
EE D
OUTLET MANWAY ONE 5
16 BOLTS, 1 THRU 16 85-023, 032 BOLTS, 1 THRU 16 86-015,019 (REPEAT)
TWO 5
THREE 6
B7.30 B-G-2 STEAM GENERATOR N0. 12 INLET MANWAY ONE 5
16 BOLTS, 1 THRU 16 85-022, 023 BOLTS, 1 THRU 16 86-016,020 (REPEAT)
TWO 5
THREE 6
OUTLET MANWAY ONE 5
16 BOLTS, 1 THRU 16 85-022, 023 BOLTS, 1 THRU 16 86-017, 021 (REPEAT)
TWO 5
THREE 6
88.30 B-H INTEGRAL ATTACHMENTS FOR VESSELS
-NONE-B-P ALL PRESSURE RETAINING COMPONENTS B15.30 B-P PRESSURE RETAINING BOUNDARY
- PERFORMED BY PLANT PERSONNEL IN ACCORD-B15.31 B-P PRESSURE RETAINING BOUNDARY ANCE WITH IWA-5000 DURING EACH SYSTEM LEAKAGE TEST AND EACH SYSTEM HYDR 0-STATIC TEST REQUIRED BY IWB-5000 Form 17244 pe PPMM4, Rev. 0 (1/87)
(M&SP 52)
LCD031485WMH01-LT
NORTHERN CTATE3 POWER CO.
TABLE S1.5 PRAIRIE ISLAND UNIT I PAGE I
OF 15 fNSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRESSURE i
SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CA A
D RIPT O F
PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
D B-F PRESSURE RETAINING DISSIMILAR METAL WELDS B5.130 B-F NOMINAL PIPE SIZE 4" AND GREATER, DISSIMILAR METAL WELDS REACTOR VESSEL REACTOR CORE COOLANT ONE 1
2 RCC-A-1 S.E. (UT) 85-W REPORT SYSTEM TWO 1
RCC-B-1 S.E. (UT) 85-Il REPORT THREE 2
REACTOR VESSEL SAFETY ONE 1
INJECTION SYSTEMS THREE 1
STEAM GENERATORS NO. 11 REACTOR CORE C0OLANT ONE 1
1 RCC-A-5 S.E.87-010,027,011 SYSTEM THREE 1
STEAM GENERATORS NO. 12 REACTOR CORE COOLANT TWO 1
SYSTEM THREE 1
4 PRESSURIZER SAFETY LINES ONE 2
1 8010A-1 S.E.85-042, 053 SURGE LINE TWO 1
RELIEF LINE THREE 1
SPRAY LINE THREE 1
'""' '7 2*
- PPM-0044, Rev. 0 (1/87)
LCD031485WMH04-LT
e S1.5 NORTHERN STATES POWER CO.
TABLE PRAIRIE ISLAND UNIT I PAGE 2 OF 15-INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRESSURE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CAT A
D R
ON PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
gO B5.140 B-F NOMINAL PIPE SIZE LESS
-NONE-THAN 4" B5.150 B-F SOCKET WELDS
-NONE-B6.150 B-G-1 PRESSURE RETAINING BOLTING,
-NONE-GREATER THAN 2" IN DIAMETER B-G-2 PRESSURE RETAINING BOLTING, 2" AND LESS IN DIAMETER B7.50 B-G-2 BOLTS, STUDS AND NUTS SEAL INJECTION ONE 4
8 ORIFICE BOLTS15-076 0 W-9 ORFICE BOLTS36-121 TWO 4
0 W-3 ONE 4
WO 4
l RESISTANCE TEMPERATURE ONE 8
4 ORFICE BOLTS36-079 DETECTOR - RETURN TWO 8
0 W-7 PRESSURE SAFETY LINES ONE 12 12 FLANGE BOLTS35-031 THREE 12 0 8010A B-J PRESSURE RETAINING WELDS IN PIPING B9.10 B-J NOMINAL PIPE SIZE 4" AND GREATER r inos pe PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
i NORTHERN STATES POWER CO.
TABLE S1.5 i.
PRAIRIE ISLAND UNIT T PAGE 1 OF 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PTPTNG PDFttlinE -
SUB EXAM COMPONENT OR SYSTEM INSP.
' REQ'D AMT.
ITEM INSPECTION l
ITEM CA DE Al PER.
AMT.
EXAM IDENTIFICATION.
REPORT NOL 4
89.11 &
B-J CIRCUMFERENTIAL AND B9.12 LONGITUDINAL WELDS LONGITUDINAL WELDS
-NONE-r CIRCUMFERENTIAL WELDS (4.0 IN. NOM. DIA. SYSTEMS) l REACTOR VESSEL SAFETY ONE 1
NONE OF THESE WELDS ARE ACCESSIBLE, THEY INJECTION LOW HEAD A TWO ARE LOCATED WITHIN IHE CONCRETE SHIELD THREE WALL.
REACTOR VESSEL SAFETY ONE SOME OF THESE WELDS ARE ACCESSIBLE; OTHERS ARE LOCATED dITHIN THE CONCRETE i
INJECTION LOW HEAD.B TWO THREE 1
SHIELD WALL.
(6.0 IN. NOM. DIA. SYSTEMS)
REACTOR. VESSEL SAFETY ONE 2
2 W-8, W-5 36-042,043,056,057 INJECTION LOW HEAD A TWO THREE REACTOR VESSEL SAFETY ONE INJECTION LOW HEAD B
-TWO 1
THREE SAFETY INJECTION 0NE HIGH HEAD LOOP A TWO 1
THREE 4
SAFETY INJECTION ONE HIGH HEAD LOOP B TWO THREE 1
r numpo PPM-0044. Rev. 0 (1/87)
(M&SP 5.2) lLCD031485WMH04-LT
S1.5 NORTHERN CTATES POWER CO.
TABLE PRAIRIE ISLAND UNIT I PAGE 4 OF 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRESSURE SUB EXAM COMPONENT GR SYSTEM INSR REO'D AMT.
ITEM INSPECTION LTEM CA R O OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO g
B9.11 &
B-J CONT'D 1
89.12 PRESSURIZER SAFETY ONE 1
1 W-4 35-035, 052 LINE A TWO THREE 1
PRESSURIZER SAFETY ONE LINE B TWO 1
THREE 1
PLO-CAP LOOP A ONE TWO THREE 1
PLO-CAP LOOP B ONE TWO 1
THREE (8.0 IN. NOM. DIA. SYSTEMS)
RESIDUAL HEAT REMOVAL ONE 3
3 W-16, 18 36-030,030R,044, TAKE OFF LOOP A 359,059R,071 W-6 37-006,018 TWO 2
THREE 2
RESIDUAL HEAT REMOVAL ONE 2
1 W-16 B5-025, 061, 061A TAKE OFF LOOP B TWO 2
THREE 2
(10.0 IN. NOM. DIA. SYSTEMS)
RESIDUAL HEAT REMOVAL ONE 1
RETURN LOOP B TWO 1
THREE 1
% uwe p,3 PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
S1.5 NORTHERN STATES PO}ER CO.
TABLE D AD PRAIRIE ISLAND UNIT PAGE OF INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRES 5URE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CA D
R PT O OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
89.11 &
B-J CONT'D 89.12 PRESSURIZER SURGE ONE 1
1 W-4 35-140, 144 LOOP B TWO THREE 1
(12.0 IN. NOM. DIA. SYSTEMS)
ACCUMULATOR DISCHARGE ONE 1
1 W-5 35-078, 083 LOOP A TWO THREE 1
ACCUMULATOR DISCHARGE ONE 1
1 W-4 36-114, 118 LOOP B TWO 1
THREE 2
(27.5 IN. NOM. DIA. SYSTEMS)
REACTOR CORE COOLANT ONE COLD LEG (INLET) A TWO THREE 1
REACTOR CORE COOLANT ONE COLD LEG (INLET) B TWO 1
THREE (29.0 IN. NOM. DIA. SYSTEMS)
REACTOR CORE COOLANT ONE HOT LEG (0UTLET) A TWO THREE 1
REACTOR CORE COOLANT ONE 1
HOT LEG (0UTLET) B TWO THREE r uwe pan FTM-0044 Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
TABLE S1.5 NORTHERN OTATES POWpR CO.
PRAIRIE ISLAND UNIT PAGE 6 op 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEMPIPING PRESSURE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM A
D R O F
PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
B9.11 &
B-J CONT'D B9.12 (31.0 IN. NOM. DIA. SYSTEMS)
REACTOR CORE COOLANT ONE 1
1 RCC-A-10 07-007,026,009 CROSSOVER LINE A TWO THREE 1
REACTOR CORE COOLANT ONE CROSS 0VER LINE B TWO 2
THREE B9.20 B-J NOMINAL PIPE SIZE LESS THAN 4" B9.21 &
B-J CIRCUMFERENTIAL AND B9.22 B-J LONGITUDINAL WELDS LONGITUDINAL WELDS
-NONE-CIRCUMFERENTIAL WELDS l
(1.5 IN. NOM. DIA. SYSTEMS)
SEAL INJECTION ONE 1
1 W-8 06-052 LOOP A TWO 1
THREE 1
SEAL INJECTION ONE 1
1 W-5 H5-057 LOOP B TWO 1
THREE 1
ro,. g u m non PPMM, Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
S1.5 NORTHERN CTATE3 POWER CO.
TW PRAIRIE ISLAND UNIT I PAGE 7
15 g
INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEMyIPInu PRL55URE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CATE At D SCR PT N OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
89.11 &
B-J CONT'D B9.12 (2.0 IN. NOM. DIA. SYSTEMS)
SEAL INJECTION ONE 3
2 W-44 85-068, 068R LOOP A TWO 3
W-20 86-082, 082R THREE 3
SEAL INJECTION ONE 2
LOOP B TWO 2
THREE 4
CHARGING LINE CVCS ONE 6
5 W-23, 31A 85-009, 008 W-30, 38, 60 86-027,028,029,029R LOOP B TWO 6
THREE 6
LETDOWN LINE CVCS ONE 1
LOOP B TWO 1
THREE 2
AUXILIARY SPRAY TO ONE 1
1 W-13 85-027 PRESSURIZER TWO 2
THREE 2
RESIDUAL TEMPERATURE ONE 1
1 W-18 86-083 DETECTOR TAKE OFF TWO 1
COLD LEG LOOP A THREE 1
RESIDUAL TEMPERATURE ONE 1
1 W-12 86-081 DETECTOR TAKE OFF TWO 1
COLD LEG LOOP B THREE 1
con. m m o an PPM-0044. Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
.5 NORTHERN CTATES PO]ER CO.
TABLE PRAIRIE ISLAND UNIT PAGE OF INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PDF99ltDF SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CATE D
R PTIO PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
G B9.11 &
CONT'D B9.12 RESIDUAL TEMPERATURE ONE 1
1 W-4 35-079 DETECTOR TAKE OFF TWO I
HOT LEG LOOP A THREE 2
RESIDUAL TEMPERATURE ONE 1
DETECTOR TAKE OFF TWO I
HOT LEG LOOP B THREE 2
SAFETY INJECTION ONE 1
HIGH HEAD LOOP A TWO THREE 1
SAFETY INJECTION ONE 1
1 W-8 35-039 HIGH HEAD LOOP B TWO 1
THREE 2
DRAIN ON CROSSOVER ONE 1
1 W-13 36-053 LOOP A TWO 1
THREE 1
DRAIN ON CROSS 0VER ONE LOOP B TWO 1
THREE 1
REACTOR VESSEL SAFETY ONE INJECTION LOW HEAD TWO 1
LOOP A THREE 2
REACTOR VESSEL SAFETY ONE 1
INJECTION LOW HEAD TWO 1
LOOP B THREE 1
%"d'Q)'
PPM-0044, Rev. 0 (1/87)
LCD031485WMH04-LT
NORTHERN STATES POWER CO.
TAIBLE S1.5 PRAIRIE ISLAND UNIT I PAGE 9 OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEMPIPING PRESSURE SUB EXAM COMPONENT OR SYSTEM INSP.
REOT)
AMT.
ITEM INSPECTION ITEM CA A
DE R O PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
(3.0 IN. NOM. DIA. SYSTEMS)
B9.11 &
(CONT'D l
B9.12 SPRAY TO PRESSURIZER ONE 3
1 W-22A 85-141 BRANCH A TWO 4
THREE 4
SPRAY TO PRESSURIZER ONE 1
1 W-7 86-120 BRANCH B TWO 1
THREE 2
RESIDUAL TEMPERATURE ONE 1
1 W-2 85-080 DETECTOR RETURN A TWO 1
THREE*
1 RESIDUAL TEMPERATURE ONE 1
1 W-9 86-088 DETECTOR RETURN B TWO I
THREE 1
t PRESSURIZER RELIEF ONE 1
1 W-4 86-080 LOOP A TWO I
THREE 1
PRESSURIZER RELIEF ONE 1
1 W-14 85-058 LOOP B TWO THREE B9.30 B-J BRANCH PIPE CONNECTION WELDS
[
B9.31 B-J NOMINAL PIPE SIZE 4" AND GREATER (12.0 IN. NOM. DIA. SYSTEMS)
ACCUMULATOR DISCHARGE THREE 1
LOOP A
% me o en PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
NORTHERN STATES POWER CO.
TABLE S1.5 PRA8RIE ISLAND UN8T I
PAGE 10 OF 15-INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJORITEM: PIPING PRFSRIIRE SUB PONE OR SYSTEM INSP.
REOV AMT.
BTEM INSPECTION l
GORY ITEM TO BE EXAMINED B9.31 B-J CONT'D ACCUMULATOR DISCHARGE ONE 1
LOOP B (8.0 IN. NOM. DIA. SYSTEMS)
RESIDUAL HEAT REMOVAL TWO 1
TAKE OFF LOOP A RESIDUAL HEAT REMOVAL ONE 1
1 W-R 85-062, 104, 105 TAKE OFF LOOP B (10.0 IN. NOM. DIA. SYSTEM)
PRESSURIZER SURGE TWO 1
LOOP B (6.0 IN. NOM. DIA. SYSTEM) i PLO-CAP LOOP A ONE 1
1 W-R 87-005,022,019 PLO-CAP LOOP B THREE 1
SAFETY INJECTION TWO 1
HIGH HEAD LOOP A SAFETY INJECTION THREE 1
HIGH HEAD LOOP B
'o=' '7 2*5 **4 PPMN, Rev. 0 (1/87)
ICD 0314R5WMH04-1T
NORTHERN CTATE3 POWER CO.
TABLE S1.5 PRAIRIE ISLAND UNIT I PAGE 11 OF 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRESSURE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM O
Rt PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
B9.32 B-J NOMINAL PIPE SIZE LESS THAN 4" (3.0 IN. NOM. DIA. SYSTEMS)
SPRAY TO PRESSURIZER ONE 1
LOOP A SPRAY TO PRESSURIZER TWO 1
i l
LOOP B RESIDUAL TEMPERATURE THREE 1
DETECTOR RETURN A RESIDUAL TEMPERATURE THREE 1
DETECTOR RETURN B (2.0 IN. NOM. DIA. SYSTEMS)
RESIDUAL TEMPERATURE TWO 1
DETECTOR TAKE OFF COLD LEG LOOP A RESIDUAL TEMPERATURE THREE 1
DETECTOR TAKE OFF COLD LEG LOOP B DRAIN ON CROSSOVER TWO 1
LOOP A DRAIN ON CROSSOVER ONE 1
LOOP B CHARGING LINE CVCS THREE 1
LOOP B l
PPM-0044. Rev. 0 (1/87) g LCD031485WMH04-LT
ER CO.
TABLE S1.5 NORTHERN CTATE3 yT PRAIRIE ISLAND UNI PAGE 12 op 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PIPING PRESSURE SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM D
M PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
B9.32 B-J CONT'D REACTOR VESSEL SAFETY ONE 1
1 W-1 fl5-040 INJECTION LOW HEAD A REACTOR VESSEL SAFETY THREE 1
INJECTION LOW HEAD B B9.40 B-J SOCKET WELDS SEAL INJECTION ONE LOOP A TWO 1
THREE 1
SEAL INJECTION ONE 1
LOOP B TWO THREE 1
CHARGING LINE CVCS ONE 1
LOOP B TWO 1
THREE 1
LETDOWN LINE CVCS ONE LOOP B TWO 1
THREE AUXILIARY SPRAY TO ONE I
1 W-10 + PIPE 35-026 PRESSURIZER TWO THREE RESIDUAL TEMPERATURE ONE 1
1 W-8 37-015,016 DETECTOR TAKE OFF TWO I
COLD LEG LOOP A THREE 1
Y PPM-0044, Rev. 0 (1457)
( g$p"s LCD031485WMH04-LT
NORTHERN CTATES POWER CO.
TABLE S1.5 PRAIRIE ISLAND UNIT I
PAGE 13 OF 15 INSERVICE INSPECTION-EXAMINATION SUIMAARY MAJOR ITEM: PTPTNG PRFStilRF INSR REQ'D AMT.
ITEM INSPECTION I
y CAE-ND DE Rm PER.
AMT.
EXAM IDENTIFICATION REPORT NQ GORY ITEM TO BE EXAMINED 89.40 B-J CONT'D RESIDUAL TEMPERATURE ONE 1
DETECTOR TAKE OFF TWO I
COLD LEG LOOP B THREE 1
RESIDUAL TEMPERATURE ONE DETECTOR TAKE OFF TWO 1
HOT LEG LOOP A THREE 1
RESIDUAL TEMPERATURE ONE DETECTOR TAKE OFF TWO I
HOT LEG LOOP B THREE 1
SAFETY INJECTION ONE HIGH HEAD LOOP A TWO THREE 1
SAFETY INJECTION ONE 1
1 W-17 B5-038 HIGH HEAD LOOP B TWO THREE DRAIN ON CROSS 0VER ONE 1
LOOP A TWO THREE DRAIN ON CROSS 0VER ONE LOOP B TWO I
THREE 1
1 W-8 85-043 REACTOR VESSEL SAFETY ONE INJECTION LOW HEAD A TWO THREE 1
k&$P N. Rev. 0 O/SD 2
LCD031485WMH04-LT
d NORTHERN CTATED R CO.
TABLE S1.5 PRAIRGE ISLAND UNIT PAGE 14 OF 15 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJORITEM: PIPING PRESSURE sus EXAM COMPONENT OR SYSTEM INSP.
REOD AMT.
ITEM
- 4SPECT M ITEM CATE-AND DESCRIPTION OF PER.
AMT.
EXAM IDENTF M M gmg GORY ITEM TO BE EXAMINED B9.40 B-J CONT'D REACTOR VESSEL SAFETY ONE 1
1 INJECTION LOW HEAD B TWO THREE B-K-1 INTEGRAL ATTACHMENT FOR PIPING B10.10 B-K-1 INTEGRALLY WELDED ATTACHMENTS ACCUMULATOR DISCHARGE THREE 1
RESIDUAL HEAT REMOVAL ONE 1
TAKE OFF LOOP A TWO I
4 THREE 2
SPRAY TO PRESSURIZER ONE 1
1 K
05-075, 075R, 118 BRANCH A RESIDUAL HEAT REMOVAL ONE RETURN LOOP B TWO I
THREE 1
RESIDUAL HEAT REMOVAL ONE 1
1 P
d5-054, 055, 059, 054R TAKE OFF LOOP B TWO THREE 1
SAFETY INJECTION TWO I
AUXILIARY SPRAY 2" CVCS ONE 1
1 Al 36-119 LCDO[MM o (1/87)
SY (M&SP 5.2)
a S1.5 -
NORTHERN CTATES POfR CO.
TABLE PRAMIE ISLAND UNIT PAGE 15 OF 15 1
INSERVICE INSPECTION--EXARAINATION SURAGAARY RAAJOR ITEAA: PTPTNG PRFRRilRE
}
sus EXAM COMPONENT OR SYSTEM INSP.
REOV AMT.
ITEM INSPECTION j
ITEM AND DE PER.
AMT.
EXAM IDENTIFICATION REPORT NOL M
D B-P ALL PRESSURE RETAINING COMPONENTS B15.50 B-P PRESSURE RETAINING BOUNDARY
- PERFORMED BY PLANT-B15.51 B-P PRESSURE RETAINING BOUNDARY PERSONNEL IN ACCORD-ANCE WITH IWA-5000 1
DURING t!ACH SYSTEM LEAKAGE TEST AND i
EACH SYSTEM HYDRO-STATIC TEST REQUIRED BY IWB-5000 L
l r
l i,
i 1,
i
.i i
- pe PPMM, Rev. 0 (1/87)
(M&SP 5.2)
LCD031485WMH04-LT
=
TABLE S-II NORTHERN STATES POWER COMPANY Prairie Island Unit I Examination Com l............................................................................................................................parisonSummary
............................l l Sus-ITEM l STSTEN l CLASS l ISO lNETHl ITEN l REPORT PREVIOUS RESulTS CURRENT RESuLTS LIMITATIONS l........l....................l......g..........l....l...............l..........ll....................l....................ll..............................l l
l lB2.40 lS/s11 l
I l1-ISI-43 luTOju-A08-12'
[87 024 lResults: NOME lResults:NONE lNONE l
182.40 lS/s11 l
Il1-ISI43 luT4lwA0'-12' l87023 l Results:NONE lResults:GEO l NOME l
l l
l l
1 1
I I
i k=:2 I
I I
I I
I I
I I
I ITp:GEONETRY l
l l
l l
1 1
I i
i i A=ptitu*:25x i
I I
I I
I I
I I
I IAx Loc:
l l
l 1
I I
I I
I I
l Cire Loc:
I I
I I
I I
I I
I I
ILength:0'-12' l
l l82.40 lS/G11 l
I l1-ISI-43 luT6lWA0'-12' l87025 lResults:NONE lResults:NONE l NOME l
l82.40 lS/G11 l
I l1-ISI-43 lVT1lWA0'12'
,l87-012 lResults: NOME lResults:NONE l NOME l
lB5.130 lREACTORCOOLANTA l
I l1-ISI-12 lPT lRCC-A-5S.E.
l87-010 lResults:NONE lResults:NONE l NOME l
lB5.130 l REACTOR COOLANT A l
I l1-ISI-12 luT4 lRCC-A-5 S.E.
l87-027 lResults: NOME lResults:NONE lNoS-1,1S,25OuETON02ZLE l
lB5.130 lREACTORCOOLANTA l
Il1ISI-12 lVT1lRCC-A5S.E.
l87-011 lResults:NONE lResults: NOME lNONE l
[B9.11 lRCC CROSSOVER A l
I l1-ISI-12 lPT lRCC-A-10 l87 007 lResults: NOME lResults:IND lNONE l
l l
l l
l 1
1 I
I i s :* Rou men l
l l
1 I
I I
I I
I IAs Loca 75" l
I I
I I
I I
I I
I ICireLoc:45.25 i
i i
i i
I
.I I
I I
ILeneth:.125-1 i
lB9.11 lRCCCROSSOVERA l
Il1-ISI-12 lPT lRCC-A10 l87 007 lResults:NONE lResults:IND l NOME l
l 1
1 I
I I
I I
ITm: Rou mED l
l l
1 I
I I
I I
I I Ax Loc:.875-l l
l l
l l
1 I
I I
lCireLoc:10" 1
I I
I I
I I
I I
I ILeneth:<.125" I
i lB9.11 lRCCCROSSOVERA l
Il1-ISI-12 lPT lRCC-A10 l87-007 lResults:NONE lResults:!ND l NOME l
l l
I I
I I
I i
ITp: Rou men l
l 1
1 I
I I
I I
I I Ax Loc: 75" i
I I
I I
I I
I I
I lCiretoc:13-1 l
l l
l l
1 1
I I
ILength:<.125" l
l lB9.11
[RCCCROSSOVERA l
Il1-ISI-12 lPT lRCCA-10 l87-007 lResults:NONE lResults!IND lNONE l
l 1
1 I
I I
I I
I Twe: R0u men l
l l
l 1
1 I
i l
I i Ax Loc:-1" i
I I
I I
I I
I I
I ICiretoc:16.5-1 I
I I
I I
I I
I I
Iteneth:<.125" i
I lB9.11 lRCC CROSSOVER A l
I l1-ISI-12 luT4lRCCA-10 l87-026 lResults: NOME lResults:NONE lNONE l
lB9.11 lRCC CROSSOVER A l
I l1 ISI-12 lVillRCC-A-10 l87-009 lResults:NONE lResults:NONE l NOME l
l l
l 1
l_I I
I I
I I
Page j
TABLE S-II NORTNERN STATES POWER CONPANY Prairie Island Unit I Examination Cout j............................................................................................................................parisonSusunary
............................g l SUS-ITEM l SYSTEM l CLASS l ISO lMETNl ITEM l REPORT l PREVIOUS RESULTS CURRENT RESJLTS LIMITATIONS
[........l....................l......g..........l....l...............l..........l....................l....................l..............................l l
l l
l89.11 lRMR TAKE OfF A l
Il1-ISI-3A lPT lW-6 l87-006 lResults: NOME l Results NOME l NOME l
lB9.11 lRNR TAKE OFF A l
I l1-ISI-3A lVT1 lW-6 l87-018 l Results: NOME lResults: NOME lNONE l
I l1 ISI-46 lPT lW-R l87-005 lResults:NONE lResults: NOME l NOME l
I l1-ISI 46 lUT4lW-R l87 022 lResults: NOME lResults:NONE lNOS1,1$,2SDUETOBR.CONFIGl lB9.31 lPLOCAPLOOPA l
Il1-ISI-46 lVT1lW-R l87019 lResults:NONE l Results:NONE lNONE '
l lB9.40 lRTD TAKE OFF COLD A l I l1-ISI-7 lPT lW8 l87 015 lResults:NONE lResults:NONE lNONE l
lB9.40 lRTD TAKE OFF COLD A l I l1-ISI-7 lVT1 lW-8 l87-016 lResults:NONE lResults: NOME
[NONE l
l 1
1 I
l_I I
I I
l l
Page 2
\\
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 1 0F 7 ISOMETRIC
SUMMARY
CLASS I
!!SP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-I O
CHARGING LINE (GENERAL VIEW)
ISI-1A 1
B 2-RC-17 2"
.344" 3
ISI-1B 0
B 2-RC-17 2"
.344" 3
ISI-IC 0
B 2-VC-5 2"
.344" 3
ISI-lD 0
B 2-VC-5 2"
.344" 3
ISI-IE O
B 2-VC-6 2"
.344" 3
ISI-lf 0
B 2-VC-6 2"
.344" 3
ISI-2 0
ACCUMULATOR DISCHARGE A
12-RC-16A 12" 1.312" 11 A
12-SI-27A 12" 1.312" 11 ISI-3 0
RESIDUAL HEAT REMOVAL TAKE 0FF (GENERAL VIEW)
ISI-3A 1
A 8-RC-15A 8"
.812" 8
ISI-3B 0
A 8-RH-1A 8"
.812" 8
ISI-3C.
O A
8-RH-1A 8"
.812" 8
ISI-4 0
SAFETY INJECTION HIGH HEAD A
6-RC-13B 6"
.719" 6
ISI-5 0
SPRAY TO PRESSURIZER (GENERAL VIEW)
ISI-5A 2
A 3-RC-5 3"
.438" 4
ISI-58 1
A 3-RC-5 3"
.438" 4
ISI-SC 0
A 3-RC-5 3"
.438" 4
ISI-5D 1
B 3-RC-5 3"
.438" 4
PPM-0055, Rev. 0 (9/86)
Farm noaso
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 2 0F 7 ISOMETRIC
SUMMARY
CLASS I NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-6 0
RTD RETURN A
3-RC-6A 3"
.438" 4
ISI-7 0
RID TAKE OFF COLD LEG A
2-RC-8A 2"
.344" 3
ISI-8 0
RID TAKE OFF HOT LEG A
2-RC-7A 2"
.344" 3
ISI-9 1
SAFETY INJECTION HIGH HEAD A
2-SI-35A 2"
.344" 3
ISI-10 1
DRAIN ON CROSSOVER A
2-RC-10A 2"
.344" 3
A 2-RC-IIA 2"
.344" 3
ISI-ll 0
SEAL INJECTION (GENERAL VIEW)
ISI-IIA 1
A Il-VC-21A 11"
.281" 1
ISI-IIB 0
A 2-VC-21A 2"
.344" 3
ISI-llc 0
A 2-VC-21A 2"
.344" 3
ISI-llD 1
A 2-VC-21A 2"
.344" 3
ISI-12 2
REACTOR CORE COOLANT A
29-RC-IA 29" 2.335" 14A A
31-RC-2A 31" 2.495" 14A A
271-RC-3A 271" 2.215" 14A ISI-13 2
REACTOR CORE COOLANT B
29-RC-1B 29" 2.335" 14A B
31-RC-28 31" 2.495" 14A B
271-RC-38 271" 2.215" 14A 151-14 0
R C PUMP FLANGE BOLTING A
151-15 0
R C PUMP SEAL HOUSING BOLTS A
PPM-0055, Rev. 0 (9/86) ra no.so
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 3 0F 7 ISOMETRIC
SUMMARY
CLASS I NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-16 1
R C PUMP FLYWHEEL A
ISI-17 0
ACCUMULATOR DISCHARGE B
12-RC-16B 12" 1.312" 11 B
12-SI-278 12" 1.312" 11 ISI-18 0
RESIDUAL HEAT REMOVf.L RETURN 8
10-SI-26 10" 1.000" 10 ISI-19 0
RESIDUAL HEAT REMOVAL TAKE 0FF (GENERAL VIEW)
ISI-19A 0
8 8-RH-18 8"
.812" 8
ISI-198 0
B 8-RC-158 8"
.812" 8
ISI-20 0
SAFETY INJECTION HIGH HEAD B
6-RC-130 6"
.719" 6
ISI-21 0
RTD RETURN B
3-RC-6B 3"
.438" 4
ISI-22 0
RTD TAKE OFF COLD LEG B
2-RC-8B 2"
.344" 3
ISI-23 0
RTD TAKE OFF HOT LEG B
2-RC-78 2"
.344" 3
ISI-24 0
SAFETY INJECTION HIGH HEAD B
2-51-35B 2"
.344" 3
ISI-25 I
DRAIN ON CROSS 0VER B
2-RC-108 2"
.344" 3
8 2-RC-IIB 2"
.344" 3
ISI-26 0
CVCS LETDOWN B
2-RC-12 2"
.344" 3
).
PPM-0055, Rev. 0 (9/86)
Fen 94M2
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 4 0F 7 ISOMETRIC
SUMMARY
CLASS I NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-27 2
SEAL IriJECTION (GENERAL VIEW)
ISI-27A 1
B ll-VC-21B 11"
.281" 1
ISI-278 1
8 2-VC-21B 2"
.344" 3
ISI-27C I
B 2-VC-21B 2"
.344" 3
ISI-28 1
PRESSURIZER SURGE B
10-RC-4 10" 1.000" 10 ISI-29 1
PRESSURIZER SAFETY A
6-RC-20A 6"
.719" 6
B 6-RC-20B 6"
.719" 6
ISI-30 0
REACTOR VESSEL SPRAY A
4-RC-14A 4"
.438" 5
INJECTION A
6-RC-14A 6"
.719" 6
i A
6-SI-25A 6"
.719" 6
B 4-RC-1B 4"
.438" 5
B 6-RC-148 6"
.719" 6
8 6-SI-258 6"
.719" 6
ISI-31 0
PRESSURIZER RELIEF A&B 3-RC-21 3"
.438" 4
151-32 0
AUXILLARY SPRAY 2-RC-19 2"
.344" 3
2-VC-4 2"
.344" 3
ISI-33 0
REACTOR VESSEL SAFETY B
2-SI-24A 2"
.344" 3
INJECTION B
2-SI-248 2"
.344" 3
ISI-34 0
R C PUMP FLANGE BOLTING B
PPM-0055, Rev. 0 (9/86)
Faa= ime2
l l
NORTHERN STATES POWER COMPANY TABLE III I
PRAIRIE ISLAND UNIT II PAGE 5 0F 7 l
ISOMETRIC
SUMMARY
CLASS I NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER HUMBER DESIG NUMBER SIZE THICK STD ISI-35 0
R C PUMP SEAL 110VSING BOLTS B
ISI-36 0
R C PUMP FLYWilEEL B
ISI-37 0
REACTOR VESSEL STUDS, Y50 NUTS & WASilERS ISI-38 0
R V CONOSEAL BOLTS ISI-41 1
PRESSURIZER WELDS 4.4" 25A SKIRT 1.5" 16 i
ISI-42 0
PRESSURIZER SAFETY & RELIEF N0ZZLES ISI-43 1
STEAM GENERATORS AaB TS - HD 5.16" 25A ISI-44 0
REGENATIVE ilEAT EXCHANGER TS - HD
.719" 6
151-45 0
EXCESS LETDOWN llT EXCilANGER IID - FLG.719" 6
151-46 0
PLO CAP A
6-RC-13A 6"
.719" 6
ISI-47 0
PLO CAP B
6-RC-138 6"
.719" 6
ISI-48 0
REACTOR VESSEL SilELL WELDS l
l PPM @S5, Rev. O (9/86)
F== im**
l
l NORTHERN STATES POWER COMPANY TABLE III l
PRAIRIE ISLAND UNIT II PAGE 6 0F 7 l
ISOMETRIC
SUMMARY
CLASS I l
NSP ISO l REVISION l COMPONENT OR SYSTEM j LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD l
l ISI-49 0
REACTOR VESSEL CLOSURE 5.12" TO 25A HEAD WELD 6.299" ISI-50 2
REACTOR VESSEL N0ZZLE CONFIG.
SUPPORT COMPONENT PROGRAM ISI-59 0
STEAM GENERATORS (GENERAL VIEW) -
ISI-59A 2
SUPPORT BASE AaB 4/ GEN.
ISI-60 2
S G TOP SUPPORT A&B 4/ GEN.
ISI-60A 0
S G COLUMN PINS A&B 8/ GEN.
R C PUMP TIE BACK PINS A&B 3/ PUMP R C PUMP COLUMN PINS A&B 6/ PUMP ISI-61 0
REACTOR COOLANT PUMPS (GENERAL VIEW)
ISI-61A 2
R C PUMP SUPPORT BASE A&B 3/ PUMP ISI-62 2
R C PUMP SUPPORT TOP AaB 3/ PUMP ISI-63 0
S G LOWER SUPPORT RING A
ISI-64 2
R C PUMP LOWER LATERAL A
SUPPORT ISI-65 0
S G LOWER LATERAL SUPPORT B
PPMG55 Rev. 0 (9/86) p nom
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 7 0F 7 ISOMETRIC
SUMMARY
CLASS I NSP ISO l REVISION l COMPONENr OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD l
ISI-66 2
R C PUMP LOWER LATERAL B
SUPPORT ISI-66A 0
R C PUMP TIE BACK BOLTS AaB 3/ PUMP l
ISI-67 2
S G SUPPORT PAD A&B 4/ GEN.
ISI-67A 0
S G HELIC 0ll SCREWS AaB 24/ GEN.
ISI-70 1
S G UPPER SUPPORT A&B 4/ GEN.
ISI-72 0
S G UPPER SUPPORT SNUBBERS A&B 4/ GEN.
ISI-73 0
PRESSURIZER BASE ISI-74 0
ACCUMULATOR BASE A&B
- ),
PPM 0055, Rev. 0 (9/86) r= **
m
.I Ii 1
.f APPENDlX B ASME CLASS II EXAMINATIONS 1
1 i
e O
Q x
52 I
~
~
e.
NORTHERN CTATES POWER CO.
TABLE S2.1.1 PRAIRIE ISLAND UNIT I PAGE l OF 3 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PRESSURE VE55ELS SUB EXAM COMPONENT OR SYSTEM INSP REOV AMT.
ITEM INSPECTION ITEM CA R PTl PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
C-A PRESSURE RETAINING WELDS IN
- PRESSUREVESSELS C1.10 C-A SHELL CIRCUMFERENTIAL WELDS STEAM GENERATOR NO. 11 WELD C
.ONE 552" 552" W-C 87-014.020,017.013 WELD E TWO 552"
~
STEAM GENERATOR NO. 12 WELD F THREE 552" C1.20 C-A liEAD CIRCUMFERENTIAL WELDS STEAM GENERATOR NO. 11 WELD H THREE 100%
C1.30 C-A TUBESHEET TO SHELL WELD STEAM GENERATOR NO. 12 WELD B THREE 100%
C-B PRESSURE RETAINING N0ZZLE WELDS IN VESSELS C2.10 C-B N0ZZLE IN VESSELS 1/2" AND
-NONE-LESS NOMINAL THICKNESS C2.20 C-B N0ZZLE WITHOUT REINFORCING PLATE IN VESSEL GREATER THAN 1/2" NOMINAL THICKNESS
- "2*H8 84 PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
I Clin'41685WH0'4-1 T
NORTHERN STATE 3 POWER CO.
TABLE S2 I I PRAIRIE ISLAND UNIT I PAGE 2 OF 3 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PRESSURE VESSELS SUB EXAM COMPONENT OR SYSTEM INSP.
REOT)
AMT.
ITEM INSPECTION ITEM CAT D
R PER.
AMT.
EXAM IDENTIFICATION REPORT NO O
C2.21 C-B N0ZZLE TO SHELL (OR HEAD)
WELDS STEAM GENERATOR NO. 11 MAIN STEAM N0ZZLE TWO 1
FEEDWATER N0ZZLE STEAM GENERATOR N0. 12 MAIN STEAM N0ZZLE FEEDWATER N0ZZLE THREE 1
C2.22 C-B N0ZZLE INSIDE RADIUS.SECTION STEAM GENERATOR NO. 11 MAIN STEAM N0ZZLE FEEDWATER N0ZZLE ONE
- 1
- RELIEF NO. 66 STEAM GENERATOR N0. 12 MAIN STEAM N0ZZLE FEEDWATER N0ZZLE THREE
- 1
- RELIEF NO. 66 C2.30 C-8 N0ZZLES WITH REINFORCING
-NONE-PLATE IN VESSELS GREATER THAN 1/2" NOMINAL THICKNESS C-C INTEGRAL ATTACHMENTS FOR VESSELS
-N0NE-C3.10 C-C INTEGRALLY WELDED ATTACHMENTS Form 172475 (3 8a PPM-0044, Rev. 0 (V87)
LCD031685WMH03-LT
=.
NORTHERN STATES POWEFi CO.
TABLE S2.1.1 PRAIRIE ISLAND UNIT I PAGE 3 op 3 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: PRESSURE VESSELS SUB EXAM COMPONENT OR SYSTEM INSP.
REOT)
AMT.
ITEM INSPECTION ITEM CAT D SCR PT O PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
G B
C-D PRESSURE RETAINING BOLTING, GREATER THAN 2" IN DIAMETER
-NONE-C4.10 C-D BOLTS AND STUDS C-H ALL PRESSURE RETAINING COMPONENTS C7.10 C-H PRESSURE RETAINING BOUNDARY
- PERFORMED BY PLANT PERSONNEL IN ACCORil-C7.20 C-H PRESSURE RETAINING B0UNDARY ANCE WITH IWA-5000 DURING EACH SYSTEM LEAKAGE TEST AND EACH SYSTEM HYDRO-STATIC TEST REQUIRI D.
1
%. inus o sa PPM-0044 Rev. 0 (1/87)
(M&SP 5.2)
LCD031685WMH03-LT l
l
'A TABLE S-II l
NORTHERN STATES POWER COMPANY Prairie Island Unit I Examination Com g............................................................................................................................parisonSummary l SUS-ITEM l STSTEM l CLASS l ISO lMETH ITEM REPORT PREVIOUS RESULTS CURRENT RESULTS l
g........l....................l......l..........l....l...............ll..........l....................l....................l......... LIMITATIONS l
l l
p,
.....................g lC1.10 lS/G11 l
IIl1ISI43 lUTOlW-C
[87 014 lResults:NONE lResults:NONE lNONE l
lC1.10 l$/G11 l
IIl1ISI43 lUT4lWC l87 020 lResults:NONE lResults: NOME lNONE l
lC1.10 lS/G11 l
II l1-ISI 43 luT6lW-C l87 017 lResults:NONE lResults:NONE lNONE l
lC1.10 lS/G11 l
IIl1-ISI43 lVT1lWC l87-013 l Results:NONE lResults:NONE l NOME l
l l
l l
l_I I
l l
I I
Page l
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT 11 PAGE 1 0F 4 ISOMETRIC
SUMMARY
CLASS II NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-43 1
STEAM GENERATORS A&B 3.5" 26 ISI-51 0
MAIN STEAM (GENERAL VIEW)
ISI-51A 0
A 32-MS-1 32" No.
ISI-51B 1
A 31-MS-1 31" 1.534" 24 --
A 30-MS-1 30" 1.045" 23 A
6-MS-1 6"
.432" 7
ISI-52 0
FEEDWATER (GENERAL VIEW)
A ISI-52A 1
A 16-FW-13 16" 1.031" 13/36 ISI-528 0
A 16-FW-8 16" 1.031" 13 A
3-AF-ll 8"
.594" No.__
ISI-53 2
A 10-RH-3 10"
.365" 22 ISI-54 2
RHR PUMP SUCTION (HANGERS)
A 8-RH-4A 8"
.322" 29 A
8-RH-5A 8"
.322" 29 A
12-RH-5A 12"
.375" 32 A
12-RH-6A 12"
.375" 32 A
10-SI-9A 10"
.365" 22 ISI-55 2
A 8-RH-7A 8"
.322" 29 ISI-56 0
RHR PUMP DISCllARGE (HANGERS)
A 8-RH-9A 8"
.322" 29 A
6-RH-10A 6"
.280" 27 A
6-SI-10A 6"
.280" 27 A
6-SI-10B 6"
.718" 6
1 PPM-0055. Rev. 0 (9/86) ron. na
NORTilERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 2 0F 4 ISOMETRIC
SUMMARY
CLASS II NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-68 0
MAIN STEAM (GENERAL VIEW)
B ISI-68A 0
B 32-MS-2 32" No.~~
ISI-688 1
B 31-MS-2 31" 1.534" 24 B
30-MS-2 30" 1.045" 23 8
6-MS-2 6"
.432" 7
ISI-69 0
FEEDWATER (GENERAL VIEW) 8 ISI-69A 1
B 16-FW-16 16" 1.031" 13/36 ISI-69B 0
B 16-FW-15 16" 1.031" 13 8
3-AF-12 8"
.594" No.__
ISI-76 2
RilR PUMP SUCTION (WELDS)
B 8-Ril-4B 8"
.322" 29 ISI-77 1
RHR PUMP SUCTION (11 ANGERS)
B 8-Ril-5B 8"
.322" 29 B
12-Ril-5B 12"
.375" 32 B
12-Ril-6B 12"
.375" 32 B
10-SI-98 10"
.365" 22 ISI-78 2
B 8-Ril-7B 8"
.322" 29 ISI-79 0
RilR PUMP DISCHAGRE (llANGERS)
B 8-RH-9B 8"
.322" 29 8
6-Ril-10B 6"
.280" 27 8
10-Ril-ll 10"
.365" 2?
B 6-RH-12 6"
.280" 27 PPM-0055, Rev. 0 (9/86) rann o m a
5 NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 3 0F 4 ISOMETRIC
SUMMARY
CLASS II NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-80 2
REFUELING WATER STORAGE 14-SI-l 14"
.250" 34 TANK DISCHARGE (WELDS) 12-SI-3A 12"
.180" 33 ISI-81 0
(HANGERS) 12-SI-3B 12"
.180" 33 12-SI-4 12"
.180" 33 10-SI-8 10"
.165" 31 12-SI-Il 12"
.180" 33 ISI-82 2
SAFETY INJECTION PUMPS' 12-S1-11 12"
.180" 33 SUCTION 8-SI-17 8"
.148" 30 8-SI-8 8"
.148" 30 ISI-83 1
SAFETY INJECTION PUMPS' 6-SI-13A 6"
.133 28 SUCTION AND 6-SI-13A 6"
.133" 28 SAFETY INJECTION PUMPS 11&l2 No__
ISI-84 1
BORIC ACID SUPPLY 8-SI-18 8"
.148" 30 ISI-85 1
ACCUMULATOR DISCHARGE A
12-SI-28A 12" 1.312" 11 A
12-SI-29A 12" 1.312" 11 B
12-SI-28B 12" 1.312" 11 B
12-SI-29B 12" 1.312" 11 ISI-86 1
ACCUMULATOR TANKS 11&l2 SHELL 2.75" No HEAD 1.39" No((
PPM-0055, Rev. 0 (9/86) rn. m m
^
NORTHERN STATES POWER COMPANY TABLE III PRAIRIE ISLAND UNIT II PAGE 4 0F 4 ISOMETRIC
SUMMARY
CLASS II NSP ISO l REVISION l COMPONENT OR SYSTEM l LOOP l LINE l LINE l WALL l UT-CAL NUMBER NUMBER DESIG NUMBER SIZE THICK STD ISI-87 1
CONTAINMENT SUMP DISCHARGE A
14-SI-33A 14"
.25" 34 (WELDS)
A 12-SI-34A 12"
.375" 32 ISI-88 0
(HANGERS)
B 14-SI-33B 14"
.25" 34 8
12-SI-348 12"
.375" 32 ISI-89 1
REACTOR VESSLE SAFETY A
6-SI-25A 6"
.718" 6
INJECTION (WELDS)
B 6-SI-25B 6"
.718" 6
ISI-90 0
(HANGERS)
ISI-91 2
ALTERNATE CONTAINMENT SPRAY A
6-RH-10A 6"
.280" 27 SUCTION (WELDS)
B 6-RH-10B 6"
.280" 27 ISI-92 0
(HANGERS)
ISI-93 0
RESIDUAL HEAT EXCHANGERS ll&l2 HEAD
.500" No__
ISI-94 0
BORIC ACID TANKS 11 &
SHELL
.312" No 121 B0T HD
.375" No((
PPM-0055, Rev. 0 (9/86)
N'" '7"
=
e o
O APPENDIX C COMPONENT SUPPORTS l
3
@S O
x 8
2c.
C.
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I
PAGE 1
OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
REQ'D AMT.
ITEM INSPECTION ITEM
- CATE, R O OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
ITEM NO.'S F-1, r
F-A PLATE AND SHELL TYPE SUPPORTS F-2, F-3 AND F-4 F-B LINEAR TYPE SUPPORTS FOR EACH CATEGORY F-C COMPONENT STANDARD SUPPORTS EXAMINED AS ONE COMPLETE ASSEMBLY REACTOR VESSEL LUGS THREE 2
PRESSURIZERS SUPPORT SKIRT ONE 33%
TWO 33%
THREE 34%
SUPPORT BOLTING ONE 8
8 BOLTS 1 THRU 8 35-126 TWO 8
THREE 8
STEAM GENERATORS S/G NO. 11 UPPER RING GIRDER ONE (SNUBBER PINS)
TWO THREE 4
UPPER RING GIRDER ONE 15 15 SN'JOBER PAD 85-016 (SNUBBER WALL BOLTS)
TWO THREE UPPER RING GIRDER ONE 30 30 PAD 1, 2, 3, 4 85-012. 013, 014, 015 (WALLBOLTS)
TWO THREE ren uaw ne PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMH02-LT
\\
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE 2 OF - 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
REQ'D AMT.
ITEM INSPECTION ITEM E
D SCR O PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
UPPER RING GIRDER ONE (SNUBBER BOLTS)
TWO THREE 32 UPPER RING GIRDER ONE (CONNECTINGBOLTS)
TWO 40 THREE UPPER RING GIRDER ONE (SPRING HANGERS)
TWO THREE 2
COLUMN PINS ONE 2
TWO 4
THREE 2
BASE ANCHOR BOLTS ONE 16 16 COL. 2 35-128 COL. 3 36-064 TWO 8
THREE 8
TOP COLUMN ONE 4
4 COL. 1 36-077 CONNECTING BOLTS TWO 8
THREE 4
SUPPORT PAD ONE 6
6 COL. 4 B5-142, 143 HELICOIL SCREWS TWO 6
THREE 12 LOWER LATERAL ONE SUPPORT ANCHOR TWO WALL BOLTS THREE 54 LATERAL SUPPORT ONE WALL BOLTS TWO 16 THREE Fem 172476 (387)
PPM-0044. Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WHH02-LT
SCSI.1 NORTHERN STATES POWER CO.
TABLE PRAIRIE ISLAND UNIT I PAGE 3
OF10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSR REOV AMT.
ITEM INSPECTION ITEM CATE JD D SCR ON F PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
S/G N0. 12 UPPER RING GIRDER ONE (SNUBBER PINS)
TWO THREE 4-UPPER RING GIRDER ONE 15 15 SNUBBER PAD 35-017 (SNUBBER WALL BOLTS)
TWO THREE UPPER RING GIRDER ONE 30 (WALL BOLTS)
TWO THREE UPPER RING GIRDER ONE (SNUBBER BOLTS)
TWO THREE 32 UPPER RING GIRDER ONE (CONNECTING BOLTS)
TWO 40 THREE UPPER RING GIRDER ONE (SPRING HANGERS)
TWO THREE 2
COLUMN PINS ONE 2
TWO 2
THREE 4
BASE ANCHOR BOLTS ONE 16 16 COL. 3 COL. 2 B6-065, 066 TWO 8
THREE 8
1 l
Fam U2476(3 A PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMH02-LT
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE 4 OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
REQ'D AMT.
ITEM INSPECTION ITEM CA
^
D SCR O OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
O l
Bg TOP COLUMN ONE 4
4 COL. 1 85-127 CONNECTING BOLTS TWO 8
THREE 4
SUPPORT PAD ONE 6
HELICOIL SCREWS TWO 12 THREE 6
LOWER LATERAL ONE 54 PAD 1, 2, 3, 4 85-131, 132, 133, SUPPORT ANCHOR TWO FIXTURE 1, 2, 3 134, 135, 136, 137 WALL BOLTS THREE 54 LATERAL SUPPORT ONE 12 12 PAD 5 85-137 WALL BOLTS TWO THREE CONNECTING BOLTS ONE 16 BEAM PLATE 85-138 IN LATERAL BEAM TWO 16 THREE PUMPS REACTOR CORE COOLANT PUMP NO. 11 COLUMN PINS ONE 2
TWO 2
THREE 2
BASE ANCHOR BOLTS ONE 8
8 COL. 3 86-068 TWO 8
THREE 8
r ina n on PPM-0044. Rev. 0 (1/87)
(M&SP 5.2) 1.CD031885WMH07-1T
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE 5 Op 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CA D
R PT O 4 F PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
GO COLUMN CONNECTING BOLTS ONE 4
4 COL. 2 86-115 TWO 4
THREE 4
TIE BACK BOLTS ONE 1
THREE 1
TIE BACK PINS ONE 1
TWO 1
THREE 1
THROUGH ANCHOR THREE 6
BOLTS LATERAL SUPPORT ONE 6
6 COL. 2 85-084 AND WALL BOLTS TWO 4
THREE REACTOR CORE COOLANT PUMP NO. 12 COLUMN PINS ONE 2
TWO-2 THREE 2
BASE ANCHOR BOLTS ONE 8
8 COL. 2 85-129 TWO 8
THREE 8
COLUMN CONNECTING BOLTS ONE 4
4 COL. 2 86-069 TWO 4
THREE 4
ro, ina p en PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMH02-LT
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE 6
OP 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CAT D SCR O F
PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
O B
TIE BACK BOLTS ONE 1
TWO 1
THREE 1
TIE BACK PINS ONE 1
TWO 1
THREE 1
THROUGH ANCHOR ONE BOLTS TWO THREE 6
LATERAL SUPPORT ONE 6
4 PAD. 2 86-070 AND WALL BOLTS TWO 4
THREE PIPING CHARGING LINE LOOP B ONE 7
4 D, G, Q1 85-045, 046, 074 L,D,(REPEAT)86-009, 008 TWO 7
THREE 7
ACCUMULATOR DISCHARGE ONE 1
1 D1 87-003 LOOP A TWO 1
THREE 1
RESIDUAL HEAT REMOVAL ONE 8
7 B. G2, P 85-139, 081, 028 TAKE OFF LOOP A TWO 8
N, J, Q1, Q 86-006, 010, 010R, 010R1 THREE 10 86-011, 098, 099 PPM-0044, Rev. 0 (1/87)
LCD031885WMH02-LT
SCSI.1 NORTHERN CTATES POWER CO.
TABLE PRAIRIE ISLAND UNIT I PAGE 7 OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
REQ'D AMT.
ITEM INSPECDON ITEM CA A
D R
O OF PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
SPRAY TO PRESSURIZER ONE 4
4 G, K1, H 85-093, 095, 099 BRANCH A TWO 4
K, H&G (REPEATS)86-024, 025, 026 THREE 6
SPRAY TO PRESSURIZER ONE 5
4 K
85-094, 094R BRANCH B TWO 5
A1, M1, E 86-022, 023, 116 THREE 6
RESIDUAL TEMPERATURE ONE 1
1 A
87-004 DETECTOR RETURN TWO LOOP A THREE 1
RESIDUAL TEMPERATURE ONE 2
2 B/F 85-101/87-001 DETECTOR TAKE OFF TWO 2
COLD LEG LOOP A THREE 2
RESIDUAL TEMPERATURE ONE 1
1 A
86-038 DETECTOR TAKE OFF TWO 1
HOT LEG LOOP A THREE 2
SAFETY INJECTION ONE HIGH HEAD LOOP A TWO 1
THREE 1
DRAIN ON CROSS 0VER ONE 1
1 B1 85-072 LOOP A TWO 1
B1 (REPEAT)86-036 THREE 1
SEAL INJECTION ONE 7
6 F, 0 85-069, 070 LOOP A II,F,Q1,A1 86-040, 041, 078, 086, 086R C,Al 87-008,002 TWO 7
THREE 8
5"' '7 2** (2 84 PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMHO?-lT
PM3RTHERN STATES PO4VER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE R OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM:COMPONFNT SilPPORTS SUB EXAM COMPONENT OR SYSTEM INSP.
ITEM INSPECTION ITEM CAT A
D R ON PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
gO l
REACTOR COOLANT ONE 1
LOOP A TWO 1
THREE 2
REACTOR COOLANT ONE 1
LOOP B TWO 1
THREE 2
ACCUMULATOR DISCHARGE ONE 1
1 B1 85-096 LOOP B TWO 1
81 (REPEAT) 36, 096, 096R THREE 2
RESIDUAL HEAT REMOVAL ONE 2
1 A
B6-060 RETURN LOOP B TWO 2
THREE 3
RESIDUAL HEAT REMOVAL ONE 5
4 E,J,P 35-030, 029, 063 TAKE OFF LOOP B TWO 5
K. P (REPEAT)36-061, 062 THREE 5
RESIDUAL TEMPERATURE ONE 1
1 B
B6-037 DETECTOR RETURN TWO 1
LOOP B THREE 1
RESIDUAL TEMPERATURE ONE 1
DETECTOR TAKE OFF TWO 1
COLD LEG LOOP B THREE 2
RESIDUAL TEMPERATURE ONE 1
2 A
35-090 DETECTOR TAKE OFF TWO 2
F 36-039 HOT LEG LOOP B THREE 2
ro in.m p en PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMH02-LT
NORTHERN STATES POWER CO.
TABLESCSI.1 PRAIRIE ISLAND UNIT I PAGE 9 OF 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM INSP REO'D AMT.
ITEM INSPECTION ITEM TE At D R PT ON F PER.
AMT.
EXAM IDENTIFICATION REPORT NOL H
D SAFETY INJECTION' ONE 1
TWO 1
THREE 1
DRAIN ON CROSS 0VER ONE 1
1 A
35-110 A (REPEAT)86-063 LOOP B TWO THREE LETDOWN LINE CVCS ONE 3
3 E, F 35-092, 091 B, E&F (REPEATS)36-047, 048, 049 LOOP B TWO 3
THREE 3
SEAL INJECTION ONE 4
3 A, C1 35-071, 073, 073R LOOP B TWO 4
El 36-046 THREE 4
PRESSURIZER SURGE ONE 3
1 E
B5-088, 088R LOOP B TWO 3
E (REPEAT)
B6-050 THREE 4
REACTOR VESSEL SAFETY ONE 1
1 C1 85-034 INJECTION LOOP A & B TWO 1
4" & 6" THREE 2
AUXILIARY SPRAY ONE 2
1 A1 86-087 CVCS TWO 3
THREE 3
r-.= mes oan PPM-0044, Rev. 0 (M&SP 5.2)
LCD031885WMH02-LT (1/87
NORTHERN STATES POWER CO.
TABLE SCSI.1 PRAIRIE ISLAND UNIT I PAGE 10 op 10 INSERVICE INSPECTION-EXAMINATION
SUMMARY
MAJOR ITEM: COMPONENT SUPPORTS SUB EXAM COMPONENT OR SYSTEM lNSR REO'D AMT.
ITEM INSPECTION ITEM CATE A
D R PT ON F PER.
AMT.
EXAM IDENTIFICATION REPORT NO.
GOR PRESSURIZER RELIEF ONE TWO I
THREE 1
REACTOR VESSEL SAFETY ONE 1
1 A1 86-076 INJECTION LOOP A & B TWO 1
2" THREE 1
roaa owe p aa PPM-0044, Rev. 0 (1/87)
(M&SP 5.2)
LCD031885WMH02-LT
TABLE S-II NORTHERN STATES POWER COMPANY Prairie Island Unit I Examination Com g............................................................................................................................parisonSummary
............................l lSUB-ITEM l SYSTEM l CLASS l ISO lMETH ITEN REPORT PREVIOUS RESULTS CURRENT RESULTS LINITATIONS l........l....................l......l..........l....ll...............l..........l....................l....................l..............................I l
l l
l lIWF lACCUM.CISCHARGEA l Il1-ISI2 lVT3lSIRH-22/01 l87-003 lResults:NONE lResults:NONE lNONE l
lIWF lRTDRETURNA l
Il1ISI-6 lVT3l138-R10-44/A l87-004 lResults:NONE l Results NONE lNONE l
lIWF lRTD TAKE OFF COLD A l I l1 ISI-7 lVT3lRPCH-118/F l87 001 lResults:NONE lResults:NONE lNONE l
lIWF l$EALINJECTIONA l
I l1-ISI-118 lVT3 l13A-CVCS-2/C l87008 lResults:NONE lResults:NONE lNONE l
lIWF lSEALINJECTIONA l
I l1-ISI-11A lVT3 lRCVCH-1247/A1 l87 002 lResults:NONE lResults:IND lNONE/ENGINEEREVALUATION l
l l
l l
l l
l l
l Type: RESTRICTED l
l l
l l
l l
l l
l l Ax toc:
1 I
I I
I I
I I
i l
icireLoc:
I l
i I
I I
I l
l l
lLegth:
l l
l l
l l
l_I I
I I
l l
Page I
.1a, e.,,-
l 1
4 4
9 9
e APPENDIX D TABLE I-PERSONNEL LISTING TABLE II-ULTRASONIC CALIBRATION BLOCKS TABLE III-PROCEDURE LISTING TABLE VI-EQIPMENT AND MATERIALS t
=
l
)
6 CD O
e N
8 m
I
PERSONNEL ROSTER CONTRACTOR:
04/20/87 Lambert, MacGill, Thomas, Inc.
515 Aldo Ave.
Santa Clara, CA 95054 NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-1 LVL VT-3 LVL VISION
. REMARKS JOB TITLE RECERT RECERT RECERT RECERT.
QUAL?
RECERT RECERT DUE DATE K.J. LEVESQUE II II II y
TECHNICIAN
/. /
06/14/89 05/01/88 04/08/88
/ /
/ /
04/15/87 D.B. RICHEY III III III Y
II II
+
TECHNICIAN
/ /
06/14/89 11/09/89 04/04/89 04/29/88 05/01/88 01/22/88 E.L. THOMAS III III III y
III III SUPERVISOR
/ /
01/02/89 12/30/88 12/30/88 05/13/89 05/13/89 09/08/87 A.S. WHEALDON III III III N
II II TECHNICIAN
/ /
06/26/87 06/26/87 05/24/87 01/08/89 07/27/84 01/09/88 L.J. WOOD I
II
.N TECHNICIAN
/ /
/ /
10/27/88 02/11/90
/ /
/ /
02/03/88 Page 1 of 1 i
- i 5
l l
. ~ ~
i PERSONNEL ROSTER CONTRACTOR:
-04/20/87 Conam Inspection 660 South 31st St..
Richmond, CA 94804 NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-1 LVL VT-3 LVL VISION REMARKS ~
JOB TITLE RECERT RECERT RECERT RECERT QUAL?
RECERT.
RECERT.
DUE DATE M.E. DOBSON IIA N
ANALYST 09/05/88
/ /
/. /
/ /
/ /
/ /
01/05/88 J.J. FUNANICH III N
ANALYST 09/18/89
/ /
/ /
/ /
/ /
//
11/10/87 C.L. GORTEMILLER IIA N
ANALYST 12/01/87
/ /
/ /
./ /
/ /
/ /
09/11/87 M.A. G0RTEMILLER IIA N
ANALYST 06/01/88
/ /
/ /
/ /
/ /
//
07/24/87 R.H. MERRIMAN IIA N
ANALYST.
03/15/88
/ /
/ /
/ /
/ /
/ /
05/30/87 R.G. THOMPSON IIA' N
ANALYST 08/06/88
/ /
/ /
/ /
/./
/ /
07/24/87 Page 1 of 1
)
e i
4 d
e i
1
PERSONNEL ROSTER CONTRACTOR:
04/20/87 Westinghouse Electric Corporation P. O. Box 855 Steam Generator Technology Div Pittsburgh, PA 15320 NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-1 LVL VT-3 LVL VISION REMARKS JOB TITLE RECERT RECERT RECERT RECERT QUAL?
RECERT RECERT DUE DATE S.J. BEEHNER IIA N
ANALYST 08/13/88
/ /
/ /
/ /
/ /
/ /
12/03/87 J.J. CHAPLA IIA N
ANALYST 08/13/88
/ /
/ /
/ /
/ /
/ /
07/17/87 M.S. DOHSE II N
TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
06/12/87 J.W. ESTEL II TECHNICIAN 09/25/87
/ /
/ /
/ /
/ /
/ /
11/20/87 F.D. GAROFALO III ANALYST 01/16/89
/ /
/ /
/ /
/ /
/ /
01/28/88 W.D. GLENN II TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
08/11/87 J.I. HORVATH II TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
01/27/88 F.. IDZIK I
TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
01/19/88 S.R. KING II TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
02/10/87 D.M. MARDELL I
TECHNICAIN 08/29/89
/ /
/ /
/ /
/ /
'/ /
07/11/87 Page 1 of 2
PERSONNEL ROSTER CONTRACTOR:
04/20/87 Westinghouse Electric Corporation P. O. Box 855 Steam Generator Technology Div Pittsburgh, PA 15320
]
7 1
NAME ET LEVEL MT LEVEL PT LEVEL UT LEVEL IGSCC VT-1 LVL VT-3 LVL VISION REMARKS J
JOB TITLE RECERT RECERT RECERT RECERT QUAL?
RECERT RECERT DUE DATE G.W. MILLER II TECHNICIAN 03/04/88
/ /
/ /
/ /
/ /-
/ /
11/20/87 J.E. MILLS II i
TECHNICIAN 09/04/88
/ /
/ /
/ /
/ /-
/ /
04/28/87 W.E. MONROE II TECHNICIAN 09/08/89
/ /
/ /
/ /
/ /
/ /
01/07/88 i
W.M. ROSSI II TECHNICIAN 08/28/89
/ /
/ /
/ /
/ /
/ /
09/18/87 l
D.J. TOMMARELLO IIA j
ANALYST 08/13/88
/ /
/ /
/ /
/ /
/ /
02/03/87 R.A. V0LLMER IIA ANALYST 08/13/88
/ /
/ /
/ /
/ /
/ /
12/05/87 J.M. ZEVCHAK IIA ANALYST 08/13/88
_/ /
/ /
~/ /
/ /
-/ /
12/02/87 1
Page 2 of 2.
i A
i 9
---s
NORTHERN STATES POWER COMPANY APPENDIX D
PRAIRIE ISLAND UNIT I TABLE II ULTRASONIC CALIBRATION BLOCKS PAGE 1 0F 1 s
NSP SIZE PIPE SCHEDULE MATERIAL SERIAL OR CALIBRATION DATE NO.
DIA.
& THICKNESS HEAT NO.
REPORTS 6
6" 160
.718" A376 TP-316 M3715 ASW-004 02-27-87 14A 29" 2.335" A376 TP316 D8770 DBR-002 02-27-87 25A BLOCK 5.312" A533 GR B CL 1 C2220/1 KJL-001 02-25-87 KJL-002 02-25-87 LJW-001 02-26-87 26 BLOCK 3.500" A533 GR A CL2 52391 ASW-001 02-26-87 ASW-002 02-26-87 DBR-001 02-26-87 PPM-0055, Rev. 0 (9/86)
Fonn M282 l
NORTHERN STATES POWER COMPANY APPENDIX __0_
PRAIRIE ISLAND UNIT I TABLE III PROCEDURE LISTING PAGE 1 0F 1 PROCEDURE NUMBER l FIELD l PROCEDURE TITLE l PLANT APPROVAL l CHANGE DESCRIPTION AND REVISION CHANGE DATE NSP-PT-1, REV. 4 NONE LIQUID PENETRANT 01-08-87 EXAMINATION NSP-UT-2, REV. 3 NONE AUTOMATIC DATA 01-08-87 RECORDING NSP-UT-3, REV. 3 NONE ULTRASONIC EXAMINATION 01-08-87 0F FERRITIC VESSELS NSP-UT-16, REV. 4 NONE ULTRASONIC EXAMINATION 01-08-87 FOR INTERGRANULAR STRESS CORROSION CRACKING NSP-VT-1.0, REV. 1 NONE VISUAL EXAMINATION 01-08-87 NSP-VT-2.0, REV. I NONE VISUAL EXAMINATION OF 01-08-87 HANGER ASSEMBLIES PPM-0055, Rev. 0 (9/86) e-nosso E' -
1
NORTHERN STATES POWER COMPANY Table IV Prairie Island Unit I EQUIPMENT & MATERIALS ULTRASON'C INSTRUMENTS MANUFACTURER MODEL SER.AL CALIBRATION REMARKS f
NUMBER DATE LMT' SLAVE 13 02 87 LMT SLAVE 14 02 87 LMT SLAVE 3
12 86 NORTEC 1310 111 02 87 NORTEC 131D 126 02 87 NORTEC 131D 530B 02 87 STRIP CHART RECORDIRS MANUFACTURER MODEL SERIAL CAl.IBRATION REMARKS NUMBER DATE
'bbbLb' "' 'bkb5k'3hb 'ibhkb'" ~55 bb'"
~ ~ ~ ~ ~ ~ ~ ~ ' ' " '
GOULD BRUSH 220 19023 01 87 SURFACE TEMP ERATURE GAUG ES MANUFACTURER MODEL SE.lIA.
TY )E REMARKS NUMBER PTC 310F 880 0 TO 300 PTC 310F 882 0 TO 300 PTC 310F 889 0 TO 300 MAGNETIC PARTICLE EQUIPMENT MANUFACTURER MODEL SERIAL TYPE REMARKS NUMBER ULTRASONIC REFERENCE BLOCKS MANUFACTURER BLOCK SERIAL MATERIAL REMARKS TYPE NUMBER TYPE
~3bkbkUhkh" 'kbkPIh'"" 'kbi'" kikb'bb""
JORGENSEN ROMPAS LMT-3 4140 CS NORTEC ROMPAS 785221 304 SS ORLA'S MS ROMPAS LMT-012 4140 CS LIOUl0 PENETRANT MATERIALS l MANUFACTURER MATERIAL BATCH TYPE REMARKS NUMBER z!
kkkkFLbk
bLkhhk bbkbbk hkb5hFkb5b'
~ ~ ' ' ' " ' " ' ' ' " '
7 MAGNAFLUX DEVELOPER 84C057 SKD-N ZP-9B MAGNAFLUX PENETRANT 83M051 SKL-H S 4
- i l
i i
s
\\
.)-
NORTHERN STATES POWER COMPANY Table IV Prairie Island. Unit I EQUIPMENT & MATERIALS
,I U.TRASONIC COUPLANT MANUFACTURER MATERIA.
BATCH TYPE REMARKS NUMBER 3bkkhhk' "
'bbbPEkkk
~5bbihh[kh
[ki dEE""
\\
EDDY CURRENT RECOR)ERS MANUFACTURER MODEL SERIA.
CA'IBRATION REMARKS NUMBER DATE EDDY CURRENT COMPUTERS MANUFACTURER s'
MODEL.
SERIAL TYPE REMARKS NUMBER
.1 3
UEW P bk ' 'bPhhhh khikkb7kbk
~~~
~~ ~~
HEW PACK HP 9836 2314A07885 HEW PACK HP 9836 2429A08955 HEW PACK HP 9836 2429A08977 EDDY CURRENT MIZ-18 MANUFACTURER MODEL SERIAL TYPE REMARKS NUMBER EDDY CURRENT STANDARDS MANUFACTURER MODEL SERIAL TYPE REMARKS NUMBER E
e e
. ~, - - -
l l
NORTHERN STATES POWER COMPANY Table IV Prairie Island Unit II EQUIPMENT & MATERIALS U_TRASONIC SEARCH UNITS MANUFACTURER TY'E SERIAL SIZE FREQUENCY NUMBER AER0 TECH SB E22050
.5" DIA.
2.25 AER0 TECH SB K07023 1" DIA.
2.25 4
AUTOMATION AB C85198
.5" X 1" 2.25 HARIS0NIC AB A1300
.5" X.5" 2.25 HARIS0NIC AB A1301
.5" X.5" 2.25 HARIS0NIC AB A1304
.5" X.5" 2.25 HARIS0NIC AB A1306
.5" X.5" 2.25 HARIS0NIC AB A52
.5" X 1" 2.25 HARIS0NIC AB B10123
.75"x.75" 2.25 HARIS0NIC AB B4401
.75"x.75" 2.25 HARIS0NIC SB B5238
.5" DIA.
2.25 HARIS0NIC AB D29
.5" X 1" 1.0 HARIS0NIC SB T2640
.5" DIA.
1.1 HARIS0NIC AB W8018
.5" x.5" 2.25 NORTEC SB 6807
.75" DIA.
2.25
1 t
APPENDIX E STEAM GENERATOR No.12 HOT LEG EDDY CURRENT TUBE SIIEET MAPS AND CUMULATIVE DATA REPORTS a
c) s sc wi O9 2
l I'
i i
LEGEND OF FIELDS AND CODES FIELD EXPLANINATION ROW Row number of tube location i
COL Column number of tube location LEG Channel head tested from l
REQ Required extent of test TST Actual tested extent REM Remarks REEL Reel number where data is located PROBE Probe size used LOCATION Location of call VOLTS Voltage of signal DEG Degree of signal Measured percent through wall depth CH Channel used for measurement FIELD CODE EXPLANINATION LEG C
Cold leg H
Hot leg PROBE EM Buttom/ magnetic manufactured by Echoram EB Button / magnetic manufactured by Echoram REQ,TST, LOCATION TEH Tube end hot (primary face)
TSH Tube sheet hot (secondary face)
OlH First support plate on hot leg side Second through sixth locations 07H Seventh support plate on hot leg side NV1 First new antivibration bar Second and third locations NV4 Fourth new 3ntivibration bar 07C Seventh support plate on cold leg side Sixth through second locations Olc First support plate on cold leg side TSC Tube sheet cold (secondary face)
TEC Tube end cold (primary face)
REM RPI Retest for positive identification RIT Retest for incomplete test PLG Plugged tube CH M1 Mix 1 400/100 differential, phase curve M2 Mix 2 200/100 absolute, amplitude curve 1
400KHZ differential, phase curve
2' f
i -
02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PROC: 01H HOT LEG INDICATION LOCATION: ALL DATE: 03/10/87 INDICATION RANGE 0% TO 19%
TIME:
12:45 i
_ l
- -- 1
'---~
y
_J.- __..
.7 1.-
j
~
c-
---7,.
7
)
t
. p.
j..
. g i
l
~
. _1._.
~
~
{
I 1
i
_ i:
~
I :
_j
_ i
~~
~
I f
~
~__
05 TO 195 '
3
_ m
_ 4
~
J L~
{
1 :
j I
HAIERIALS.E_SPECIALRBOCESSES _PRODUCTIDH_2LAHLMAINTENANCE
CUMULATIVE INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/10/87 INDICATION RANGE 0% TO 19%
TIME:
10:22:35 EMANT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH 7
7 T
M M
IPIU 7TDIE o1He o.o D
TCf M HI
~
12 91 H
OlH O1H 023 740EB OlH+
0.0 1.00 135 <20 M1 10
-92 H
OlH O1H 025 740EB OlH+
0.0 0.70 132
<20 M1
- o' NUMBER OF TUBES WITH INDICATIONS
3 I
e
(
i i
i L.- -
1 I
02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GEi1ERATOR: 2 PROC: OiH HOT LEG I N D I C A T I Otl L O C A T I O t1: ALL DATE: 03/10/87 INDICATIOtt RANGE 20% TO 29%
TIME: 12:47 j-
~~2-
- J_ J1_
~
I'~-C'L:
_. _..-.1 _ in.
- au i h
_ '^.
~
? :L '
=
- - ! - - - : ^
'i
- L-
~
], _ ~_ -
~
~
~
au
_ q
~ - - - - - - - -
1
-..... -.. __. s o 3
i
~
~
~
~
~
4
~
~
[
~
X.~~. un
_ 7
~
i~: :. :
1.
- ": I.
^
~
~
~
~~
~
~"
. b
=_
1_
~
2 0
~
~
~
~~
J:
. :..: -:-~ {~
~_-~.!
- -- su
~
~
- t:
- 1
~
~
~
I'Z:
~
2 l
- - - 20
~
~
4
~'
b'.
[::
20% TO 295 4
t u
[.
[
. }:
~'
~
~
lill till till lill lill lill lill till till lill lill till Illi lill till Illi till Illi till 9J tid 80 75 70 65 60 55 50 45 40 35 30 25 20
.15 to S
I' MAIERIALS.S_SPECIALPHOCESSES =_2fl000CTI0tLPLANT_ MAINTENANCE
CUMULATIVE INDICATION REPORT-02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/10/87 INDICATION RANGE 20% TO 29%
TIME:
12:47:12 EXn.NT GUKRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH T
T T
M M
7 7TUEB 01H o.0 1.86 IT6 T MI 44 60 H
OlH O1H 18 740EB O1H 0.0 1.31 124 28 M1 43 62 H
OlH O1H 018 740EB OlH+
0.0 1.50 126 20 M1 20 89 H
OlH O1H 23 740EB O1H 0.0 1.21 136 20 M1 j.
_i NUMBER OF TUBES WITH INDICATIONS:
4 1
.- ~,
~.
~i 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 6
STEAM GEt1ERATOR: 2 PROC: 01H HOT LEG.
INDICATIOt1 LOCATION: ALL DATE: 03/10/87 INDICATIOt1 RANGE 30% TO 39%
TIME:
12: 50 a
1
.,g.
j
~
- h
~
~
~
~~
.to
_. T 1
j 1
_[_
".. Z _ '. at$
~
~
lj
.}
t r
. 30
~'
~
l W1
- ;_- -3 1
~
~~-
~~-
1 j
. au
~
4
~~"
_~!
_ ii l
~~
f
{
- E C-!
~
~~
~
~
?T
[ :_
, E-.,
~~
~~
~
~
)
- Tl
~
~
~
~
f
~
- J :
26 i
t
~
~
~
---, to
. I _.
t
-~
~
~
!.~
j
}
hu I
305 TO 395 2
i
}
~
~
i i
i i
i 1
i till Illi Illi Illi Illi llll lill lill lill till llll llll llll llll llll llll llll llIl llll
'J H$-
80 7S 70 GS 60 55 60 45 40 3S' 30 ati 20.
Su to S
J HATEBIALS_E.SPECIAL._Ra0 CESSES. eH00UCTION. PLANT HAINTEllANCE i
CUMULATIVE' INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/10/87 INDICATION RANGE 30% TO 39%
TIME:
12:49:43 EXT 1NT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH 44 T T
M M
NEP W 740EB TsHe 13.6 6
IT5 7 HI 29 82 H
O1H OlH 023 740EM 01H+
0.0 1.70 124 33 M1
~
NUMBER OF TUBES WITH INDICATIONS:
2 l
l
I i
j 4
02/87, NORTHERN STATES POWER, PRAIRIE. ISLAND, UNIT i STEAM GENERATOR: 2 PROC: 01H HOT LEG INDICATION LOCATION: ALL DATE: 03/10/87 i
INDICATION RANGE 40% TO 200%
TIME:
12: 52 l
~
~
~ :
~ -~l
~-
__._'.__-~-
~~ i'
'~ :--: :: t 1
" : : : : r
.. 30 i
_j _'
~
- ]
~
~
"I'~-'
l 5
2 -- -
1 T:_
1
- c.- -
~~
~
'30 t
r: _T_: ': ; Z ---'
t I
... au
~'
~
]
_ }
~.. j
. }
-_,, ; --n;-;
j
{
- 30 T
-+
r 4~
~
~
{ --
- - - _, a,u
}
' i
_ 1_ E : !
. I
~ p 4:
j..
~
~
~
~~
- ~
j
~
T~
~
su
}
j
~;-
~
E
~
j,
~__
_..7 7
go
._: l..
I 7
. I
~
~
~
'r--
~
~-
~
.T 'J
}
^
m 2u
~
~
~
I
~
~
~
~
}~
~
~
C 40% TO $00%
11 2
j p
r
n I;_.
lill Ill! Illi Illl lill lill Illi Illt till lill 1lll 14ll lill lill ll11 lift llll llll llll Os 66 80 75 70 65 60 US SO 45 40 35 30 au 20 sti to 5
MATEBIALE_E_SPECIAL.RROCESSES.:_ PRODUCTION PL AftI.M&INTENANN
CUMULATIVE INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/10/87 INDICATION RANGE 40% TO 100%
TIME:
12:51:54 EhtNT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH 8 ""EI T M
M HT 006 7T5H 'Tza+
4.3 3.30 T N
KI 9
25 H
01H 01H RPI 1 740EB :TEH+
4.4 1.35 36 97 M1 H
01H 01H;'RPI 001 740EB TEH+
5.7 0.90 50 90 M1 1
35 H
01H 01H RPI 011 740EB TEH+
8.9 1.30 36 99 M1 1
37 H
01H 01H RPI 011 '740EB TEH+
6.8 4.20 62 84 ' M1 '
1 38 H
01H O1H"RPI 013 '740EB TEH+
3.5 1.90 55 89l M1 H
01H 01H RPI 013 740EB TEH+
4.5 1.10 41 96 M1 17 38 H
01H 01H RPI 011 740EB TEH+
6.5 1.30 44 95 M1 H
01H 01H RPI 011 740EB :TEH+
8.7 3.60 48l 93 'M11 H
01H 01H RPI 11 740EB TEH+
9.6 0.54 67 80 'Mll H
01H 01H RPI 011 740EB TER+
11.1 1.40 65 83 M1 20 38 H
01H 01H RPI[ 011 740EB TEH+
7.5 0.50 67 81 M1 H
l01H 01H RPI 11 740EB TEH+
8.4 0.34 90 63l M1 16 41 H
.01H 01H 'RPI 001 740EB TEH+
4.2 1.30 78 72l M1 ?
H 01H 01H RPI 001 740EB TEH+
5.8 6.50 39 97 M1 H
01H 01H RPI 001 740EB TEH+
6.1 7.90 27 79 M1 H
01H 01H RPI 001 740EB TEH+
6.5 11.10 40 96' M1 l H
01H 01H RPI 001 740EB TEH+
7.4 1.10' 67 80; M1 H
01H 01H RPI 1 740EB TEH+
8.5 3.19 47 90 M1 H
01H 01H RPI 001 '740EB TEH+
9.7 0.60 74 75 M1 4
48 E
01H 01H RPI 15 '740EB ;TEH+
9.3 1.01 107 51 M1 8
50 E
01H 01H RPI 15 740EB 'TEH+
15.2 O.46 114 44 lM1 1
57 H
01H 01H RPI 17 740EB TEH+
3.2 2.39 54 90 M1 NUMBER OF TUBES WITH INDICATIONS:
11 J
'1 i
02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PROC: OiH llOT LEG' INDICATION LOCATIOti: ALL DATE: 03/10/87 It1DICATION CODE
- PLG
. TIME:
13:29 i
i j
.. _7_
. 46 T::
~
- ~~
~
~
~~~fr
~
~
-80
~
~
l H
~
~ I ;
i
- h
'-~
~
~
I'~ r;
~
4
. au
.1
. i ;
- [.
~
~
-~~
^
~
I
~~~
I
~
4 T
_- ;.c _
~
{
~
L
}
30 g
T.
. U l
i
~
- :7 -, -
~~~
~
l'
- ~~-:.
i 1
~~
~
~
, uu
[
. I i
f
-3_
(
au
~
~
'~
~
~
' I
,7 1
2 9
. }
- [:.
~
" - -.. s ts
~
~'~!
~
~~
~
2
~
~ T..
l '._
. j
. I
~
7
~
~
~
~
~
f
~
-~
20
$2 I
I
~
I
~
~
~
~
I 1
~
I h. ts
. Pl.6 19 i
i
~
~ r T
~'
l u
1
__._II.m l
lill Illi till lill lill lill Illi lill lill 11ll Illi Illi Illi Illi llll lill Illi lill ill!
OJ dr.i 30 75 70 GS tiO SS 50 45 40 35 30 atl 20
!!)
to
' ti MATEBIALS._L.SEECIAL PHOCESSES_=._Ef100UCTI0tLEl. ANT H&INTENANcE t
CUHULATIVE INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAH GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/10/87 INDICATION CODE
- PLG TIME:
13:28:12 EXIENT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH 7
7 T
UIH PIZl 8
21 H
O1H PLG 6
22 H
O1H PLG 3
24 H
01H PLG 9
25 H
O1H PLG 8
33 H
O1H PLG 1
35 H
O1H PLG 1
37 H
O1H PLG 1
38 H
O1H PLG 17 38 H
O1H PLG 20 38 H
O1H PLG 16 41 H
O1H PLG 4
48 H
O1H PLG 12 48 H
O1H PLG 8
50 H
O1H PLG 1
57 H
O1H PLG 5
57 H
O1H PLG 6
60 H
O1H PLG 37 62 H
O1H PLG NUMBER OF TUBES WITH INDICATIONS:
19
_ _ _ _ _. - -. _ _. =. - - _ _
02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT i STEAM GENERATOR: 2 PROC: TOTAL PLUG TUBES INDICATIOf t LOCATION: ALL DATE: 03/17/87 INDICATIOrt CODE
- PLG TIME:
14: 08 3-
- f__y._ __._ ~
_ _ Z !_ _T !.T ~. _ !'..
.a u
_ t
_:{.
.[-
-=
- ~:__
- T-~ }:-:
S
~
}
- -j
~
g 7
~
~
~~
- ~;
~
- n 1
- l
~ [:
. :_---- - n : _. _,
~
~
~
I
. : h'b :_
I I
~ T
~~~
'~- - -- - - :- - T : ~
S
^
^
'~~
~ ~ ~
y-__
..bI b-
- f I-3 0
~
~'^
~ L l '_
r--~~~
'M
~
- I c- ---
.,u
~
~
~
~~
~
~
j'-
~
u u
ao
~
~
~,
~
^
t 4
u
~
gg 1
ug 7
l
[
7 l
u u
~
~
a
~~if J :~
l I
un I
.I [
Z~
f I
~
II
~
~
5 g
~~ '.
.I
~
i I
~
=
litt liti lill lill Illi Illi till 1111 till lill Illi till till Illi till lill lill lill lill GJ d5 80 75 70 65 60 55 00 45 40 35 30 25 20 15 to S
HaTEBIALS &.SEECIAL.EHOCESSES =.RBQDUCTI0tt PLANT )fAINTENA!CF
i CUHULATIVE INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT l~
STEAH GENERATOR: 2 PAGE:
1 OF 2
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION CODE
- PLG TIHE:
14:00:28 EXTENT CURRENT ROW COL LEG REQ TST REH REEL PROBE LOCATION VOLTS DEG CH 7
7 T
UIH PI2l 13 15 H
O1H PLG 6
18 H
O1H PLG 4
19 H
O1H PLG 7
20 H
OlH PLG 2
21 H
OlH PLG 8
21 H
O1H PLG 6
22 H
O1H PLG 3
24 H
O1H PLG 13 24 H
O1H PLG 9
25 H
OlH PLG 9
26 H
O1H PLG 1
29 H
O1H PLG 8
33 H
O1H PLG 15 33 H
O1H PLG 16 33 H
O1H PLG 1
34 H
O1H PLG 20 34 H
OlH PLG 30 34 H
OlH PLG 1
35 H
OlH PLG
'32 35 H
OlH PLG 1
36 H
O1H PLG 1
37 H
OlH PLG 1
38 H
OlH PLG
,l' 3
38 H
O1H PLG 17 38 H
O1H PLG 20 38 H
O1H PLG 4
1 39 H
OlH PLG 1
41 H
O1H PLG 7
41 H
O1H PLG i
16 41 H
O1H PLG 17 41 H
OlH PLG 4
17 42 H
O1H PLG 4
45 H
OlH PLG j
18 45 H
O1H PLG 4
48 H
O1H PLG 12 48 H
OlH PLG 8
49 H
OlH PLG i
8 50 H
OlH PI,a 3
55 H
OlH PLG 4
1 57 H
O1H PLG 5
57 H
O1H PLG 16 59 H
O1H PLG 6
60 H
OlH PLG 1
62 H
OlH PLG 4
8 1
. ~.
1 CUMULATIVE INDICATION REPORT 02/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2
'PAGE:
2 0F 2
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION CODE
- PLG TIME:
14:00:28 EXTENT GUKRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH T
T T
UIH PIE 37 62 H
O1H PLG 39 68 H
O1H PLG 36 74 H
O1H PLG 37 75 H
O1H PLG 25 77 H
OlH PLG 34 78 H
O1H PLG 18 79 H
OlH PLG 27 85 H
O1H PLG 25 86 H
O1H PLG 6
93 H
O1H PLG NUMBER OF TUBES WITH INDICATIONF; 56 i
e r.
__.,,m..
I; i-d i
APPENDIX F STEAM GENERATOR NO.12 4
COLD LEG EDDY CURRENT TUBE SIIEET MAPS AND CUMULATIVE DATA REPORTS i
i t
1 O
i o
$e S
- s I
R-1
LEGEND OF FIELDS AND CODES FIELD EXPLANINATION
-ROW' Row number of tube location COL Column number of tube location LEG Channel head tested from REQ Required extent of test-TST Actual tested extent REM Remarks REEL Reel number where data is located PROBE Probe size used.
LOCATION Location of call VOLTS Voltage of signal DEG Degree of signal Measured percent through wall depth CH Channel used for measurement FIELD COQE EXPLANiJATION LEG C
Cold leg H
Hot leg PROBE EM Buttom/ magnetic manufactured by Echoram EB Button / magnetic manufactured by Echoram REQ,TST, LOCATION TEH Tube end hot (primary face)
TSH Tube sheet hot (secondary face)
O1H First support plate on hot leg side Second through sixth locations 07H Seventh support plate on hot leg side NV1 First new antivibration bar Second and third locations NV4 Fourth new antivibration bar 07C Seventh support plate on cold leg side Sixth through second. locations 01C First support plate on cold leg side TSC Tube sheet cold (secondary face)
TEC Tube end cold (primary face)
REM RPI Retest for positive identification RIT Retest for incomplete test i
g PLG Plugged tube CH M1 Mix 1 400/100 differential, phase curve M2 Mix 2 200/100 absolute, amplitude curve 1
400KHZ differential, phase curve
i
}
't 2/87, NORTHERN STATES POWER, PRAIRIF ISLAND, UNIT 1 t
j STEAM GENERATOR: 2 PROC: 07H COLD LEG INDICATION LOCATION: ALL DATE: 03/17/87 INDICATION RANGE 0% TO 19%
. TIME: 12:43 i
,.j
._~~~
. - ;: n _-- -- ",- ; - -
-- ;--- 7; - -
43
. l L I !_
~
~"~
-. }__.._...-
- - ~ -
- - - - ~ - ~ ~ ~ - - - -
.i
-.__._r-- - - - - - -
f
~i11 :
~
~2
'.~_~
~
I
~
~[i.
l
_ ~ - - -
~
~
- - - - - - - - -. 40
^
lL i
-4
= ~;~;
~~
~
r
}
. : l 36 l
- [
- 1__
~
' ~':1 J I
~
I I
~
~
~
39
[ [:
T~
~
~
-~
~
~
~
~
, pg.
~
~
~~'
~
~~
~
~
- --7--
~
~
~
~
~~
~
~
~
~
~
~
l E
1 2
~~ 20
~
~
~~
~
~
~
~
~
~.:-
" l
~
~ :
~
~
~
~
~
'~
~
~ ~T_
l
~
~
L l --- 7
~
'~
~
~
~
~
10 i
I
~
~
1.
~
{
~
- 2.._
I
~
10 05 TO 195 13
~'
.l.
1
~
I'
- ~ ~:
~
T_.
-,g t_..
.~
~
~
~
}_I~ 'I~
}
~
"~
~
~
~
_1
_ -_i
'(
1 llll 1111 ll11 lill Ill! Illi llll llll llll llll llll llll 1. l l l llll llll llll llll llll llll 90 OS 80 75 70 65.
60 55 50 45 40 35 30 25 20 15
$0 5
+
MATERIA S E SPECIAL PADCESSES_ _EBODUCTION_ PLANT _MINTENANCli
CUMULATIVE INDICATION REPORT 2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION RANGE 0% TO 19%
TIME:
12:37:48 EXTENT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH T
T T
M M
W 770TE osc-r o.o o.80 175 FI6 HI 31 27 C
07H 07H 012 720EB NV2+
2.0 0.30 0 <20 M2 C
07H 07H 012 720EB NV4+
4.7 0.40 0 <20 M2 39 27 C
07H 07H 12 720EB NV2+
14.5 0.46
<20 M2 35 35 C
07H 07H 024 720EB NV2+
31.7 0.40 0 <20 M2 41 35 C
07H 07H 014 720EB NV4+
6.5 0.60 0 <20 M2 31 37 C
07H 07H 024 720EB 07H+
24.9 0.40 0 <20 M2 13 40 C
07H 07H 021 720EB 02C+
2.4 1.40 160 <20 1
C 07H 07H O21 720EB 02C+
46.3.
0.60 156 <20 1
43 62 C
07H 07H 021 720EB OlC+.
0.0 0.90 130 <20 M1 38 66 C
07H 07H 021 720EB OlC+
0.0 0.90 134
<20 M1 38 68 C
07H 07H 021 720EB 01C+
0.0 1.10 136 <20 M1 25 84 C
07H 07H 021 720EB 01C+
0.0 0.80 138
<20 M1 22 86 C
07H 07H 021 720EB OlC+
0.0 1.00 142 <20 M1 17 90 C
07H 07H 021 720EB 01C+
0.0 0.50 139 <20 M1 NUMBER OF TUBES WITH INDICATIONS:
13 i
i s
4 4
2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PROC: 07H COLD LEG INDICATION LOCATION: ALL DATE: 03/17/87 INDICATION RANGE 20% TO 29%
TIME: 12:44
___::I
.-.I..
{--[_[
~
I-
-}
~
z 1
, _ _ _ _. - _ : ; --_3--- _ 3_,- - 4 0
~
"~
'~
1-2.
- _ 3 J
L:-
1 I
'-i 1
1 }-
33
.4
{
~
~
~~~
l
- ~_-
.._-}
~
'-~
~
}
. [
~
~
~
~
_~~I.
-~
Tf'
~
I
~ ~ ~ "
~
~
~
~
~
3a T'.-- :.'
_:~u~ I '__
__7
- J___
.t 1 :
- r_
- -- _ au
~
~
~~
~
~
~
~
~
u 1!
1
~
~
-~
~~
~
'-~~
~
r
. T il
]
~
~
-~
J
.1 j
~
- I.
q v.
. g
_ _1:
20
.1:
~
J~
~
4.
.I
~
[_
_.J. :
-. [
~~
-~
~
~
~
~
' ~{
~.!
__ {.
11
.'- : '- - - - -, g
~
+
9 L_ :
20% TO 29%
10 j._
ti
~
'-~
{'
f
'~
~
r J
I lill till till Illt till Illi till lill Illi lill lill Illi lill till lill Illl llll llll lill
.ta tid da 75 70 65 60 US 50 45 40 3G 30 2*i 20 10 to S
MATEBIALS.E.fl2ECIAL PJWr5SSFS - PIMIGUCTION_liANT.MAINTEtamcr
CUMULATIVE INDICATION REPORT 2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 l
STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION RANGE 20% TO 29%
TIME:
12:38:54 i
EXIANT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH T
T T
M U7H 7
7EEE osc o.o M
ITT T HI 18 27 C
07H 07H 019 720EB NV4+
- 2. 2 1.00 0
22 M2 13 40 C
07H 07H 21 720EB 02C+
37.7 1.40 152 24 1
l 45 50 C
07H 07H 21 720EB OlC 0.0 0.68 118 26 M1 44 60 C
07H 07H 21 720EB OlC 0.0 1.49 129 20 M1 36 76 C
07H 07H 21 720EB OlC 0.0 1.78 121 29 M1 29 80 C
07H 07H 21 720EB Olc 0.0 0.68 129 20 M1 31 80 C
07H 07H 21 720EB 01C 0.0 2.47 123 27 M1 29 82 C
07H 07H 21 720EB Olc 0.0 2.83 122 28 M1 24 86 C
07H 07H 21 720EB 01C 0.0 3.17 122 28 M1 NUMBER OF TUBES WITH INDICATIONS:
10 i
'I E
1 O
N f
2/87, NORTHERN STATES POWER, PRAIlIE ISLAND, UNIT i STEAM GErlERATOR: 2 PROC: 07H COLD LEG IIIDICATIOt1 LOCATION: ALL DATE: 03/17/87 It4DICATIO!! RATJGE 30% TO 39%
TIME: '12: 45 j:
,,_,,,, a s
_~:I.
Z c., -
'~'
~
J.
~~
~~
7
- }
'I
'~_~.:--------77;-
,,o
-~
7
~
~
. I..
_I :..
Tj ::
~
~
~
- ~
~~
14~
- '~-
~~
- as
-~~
~
- .:':: M'
~1
~'
"~
~ ::
.I::~
-:1.
1
~
7
. _g.
- p
_x
- p n:r
- t
_ y :-n--
-~
n:- ::
7
. I:
n_
7
}
_ _{.
p__
- as t.
1 j Tf :
~ :
~~
'I'"
~:1:
~
~
~
~
z__
~
~
~
- '_n-n _
- I: ::'~~;::' 1:
~~
_.-6_.;;_
4 7.
_ ao
~:~
h :'
h h
~
~~
~
~
~
h
~~
_'~~~~~n::~;_
J 3
I:
~
-'"~~
~~7-~
7 3,3
~~~
'~
~
- ~
^-'
-~~
[
~~
- Z~ }
~
g
~~~
- ~~~
'~~
~
go
.._n_.
~
7.._
~
~~
1:
1
_i:~
i
.l_T:_.._;U_
~
J~~
~
~
~~~ {'
"~
~
~'
~
~~~
~
~
t5
'30s TO 395 3
"~
T:
_._c:
till till till till Illi till lill Ill! Illi lill Illi till Illi Illi Illi Illi Ill! !!!! litt sa es so 75 70 65 so 55 50 45 40 35 ao 25 ao ss - so e
te&IESIAA.S a SPECTai PRGCFSSFS - PRg33;UQK,ft.33(I_jggIMrr-"W I
CUMULATIVE INDICATION REPORT 2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION RANGE 30% TO 39%
TIME:
12:39:27 EXnNT CURRENT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG CH T
7 T
m M
7 770TE 01c o.o M
m 7
HI 29 83 C
07H 07H 21 720EB OlC 0.0 1.64 120 30 M1 13 91 C
07H 07H 21 720EB OlC 0.0 1.29 114 37 M1 NUMBER OF TUBES WITH INDICATIONS:
3 1
?
I s'
i
2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAt4 GErlERATOR: 2 f.!OC: 07H COLD LEG IllDICATIOtt LOCATIOlt ALL DATE: 03/17/07 IllDICATIOtl RA!!GE 40% TO 100%
tit 4E:
12: 46
+ = = _.
._ - ---- 2 : _..-::_T. :. - -. ----. a u
:-~
E:
~
x,__-.---------------.___-.---.
4 __ _
- {f;.... ' J._l.:.._. fZ_.Tf Z ___. ~
r t 7 t
+
J-2
... J
.___:1 L
~
- j
__, ; 7, 7_ ;,-- - ---
2
.; ;--_7;- ; 7 ;-,7y 33 t
- IZ. " ~~.ZZZ __..'.
~~
1
~
~~
~
"_ ;;-- _;3 _ ;.
_-------_---30
- 'u.
. g
~
(
- _= - _ _ uu 7
~
~
f f
l
- ._. '.1... '
I--
[
{
f
,u
. J
~
I
~
h
~'
~_
~
~
[
t
-~~:
r 4
10
~
7 1
~
l f
_-. u
. [
-I
~
Z 40% TO 100%
1
+
1
. l
~
l f
litt till till till lill till Illi 1111 till lill lill lill lill Illi lill lill lill Illi lill 3J d5 do 7S 70 GS 60 US SO 4S 40 3S 30 ai 20 15 to S
L HATERIALS.S.SPECIAL. Ell 0 CESSES _Efl000CTI0tl.21.At1T.HAIrlTE!JANCE
CUMULATIVE INDICATION REPORT 2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION RANGE 40% TO 100%
TIME:
12:39:58
. EXTENT CURRENT ROW COL LEG RIQ TST REM REEL PROBE LOCATION VOLTS DEG CH
~
T TT T IP7H II7H NPT 'TYI 775 Elf olc+
o.o 2.80 TII 41 HI
.);. '
NUMBER OF TUBES WITH INDICATIONS:
1 i
f i
\\*
i, i
i l
l 1
.~
l
.3
- 7. -
u i
,v"'.
- ?
. je,
rf~
f.-
4 1
t)'
'i
.I i
1
{
2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT i i
t STEAM GENERATOR: 2 PROC: 07H COLD LEG l
INDICATION LOCATION: ALL DATE: '03/17/87 INDICATION CODE
- PLG TIME:
13: 45 I
.4
, = n
- _- ---f ;.
,; ;.__ _; _:--,_ __-- --- _.i u e
j
_{:'.:-
~
- ~
{
- T z_3._._ :
,,o q
.. g
~
3 1.-7,_
4 N-
_ :.5
^
^
~
L l
C -
- T - :X ~ '~ ~I--
au
[.
~
l 2
l
~~
~
^
~
. - - - ~ ~ - - -
. [
-- ; :;; :,,_~, ao 1
I t
. i
. 7_
_- au 1
~
-~
~
- ~
~ ~1 I
E
. o
}
3 j
. j ;
p l
L
_j 4
. g.
. p
- ,---, ao j
g
~
7 i t
~
L l
_ I I
~
WC l
1:
~
j su
-. }.
~
~
~~
~
~
~
~
~
g
~
- ~- { }:
i I
~
[
l n
Pt.6 19
~
~~
~
~ U i
I p
}_
g 3
3
,l~
IIst lill till Illi till Illi 1111 1111 till lill lill Illi Illi till till till Illi till Illi l
LBJ W.i 60 75 70 65 60. 55 S0 45 40 3S 30 2S 20 su so f.i l
bdATFATAf ft a fiPFCTal PROCFftFIFft - PftfMRICTYfM PI ANT._tlM)(TOM lE
/
I CUHULATIVE INDICATION REPORT 2/87, NORTHERN STATES POWER, PRAIRIE ISLAND, UNIT 1 STEAM GENERATOR: 2 PAGE:
1 OF 1
INDICATION LOCATION: ALL DATE:
03/17/87 INDICATION CODE
- PI4 TIME:
13:44:12 LKELNI GUKHANT ROW COL LEG REQ TST REM REEL PROBE LOCATION VOLTS DEG 4
CH 7
rs T m
m t
8 21 C
07H PLG 6
22 C
07.1 PLG 3
24 C
07H PLG 9
25 C
07H PLG 8
33 C
07H PLG 1
35 C
07H PLG 1
37 C
07H PLG 1
38 C
07H PLG 17 38 C
07H PLG 20 38 C
07H PLG a
16 41 C
07H PLG 4
48 C
07H PLG 12 48 C
07H PLG 8
50 C
07H PLG 1
57
- C 07H PLG 5
57 C
07H r
PLG 6
60 C
07H PLG 37 62
. C 07H PLG NUMBER OF TUBES WITH INDICATIONS:
19-f "h
t et f.
8 z
e 9
s i
i l'
t b
?,.
i 1
APPENDIX G NIS-I FORM FORM NIS-I, OWNERS DATA REPORT FOR INSERVICE INSPECTION
^
6
@S.
,~
o hx I
E 1
S
!=
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS
}
(As required by the Provision of the ASME Code Rules) 1.) Owner: Northern States Power Comoany Address: 414 Nicollet Mall. Minneaoolis. Minnesota 55401 2.) Plant:
PRAIRIE ISLAND NUCLEAR GENERATING PLANT Address: WELCH. MINNESOTA 3.) Plant Unit :
I 4.) Owner (Certificate of Authorization):
5.) Commercial Service Date: 12-16-73 6.) National Board NO. for Unit:
7.) Components Inspected:
Manufacturer Component or Manufacturer or Installer State or National Acourtenance or Installer Serial No.
Province No.
Board No.
STEAM GENERATORS B2.40 TUBESHEET-TO-HEAD WELDS GENERATOR 11 WESTINGHOUSE 1101 68-24 W-A 0 0' TO 12' B5.70 NOMINAL PIPE SIZE > 4 IN. N0ZZLE TO SAFE END BUTT WELDS REACTOR COOLANT NAVC0 A LOOP RCC-A-5 S.E.
PIPING B5.130 NOMINAL PIPE SIZE > 4 IN. DISSIMILAR METAL BUTT WELDS REACTOR COOLANT NAVC0 A LOOP RCC-A-5 B9.11 NOMINOL PIPE SIZE > 4".
CIRCUMFERENTIAL WELDS REACTOR COOLANT NAVC0 CROSS 0VE8 A RCC-A-10 RHR TAKE OFF A NAVC0 W-6 89.30 BRANCH PIPE CONNECTION WELDS B9.31 NOMINAL PIPE SIZE >4" PLO CAP LOOP A NAVC0 El w.R d
89.40 SOCKET WELDS Ei RTD TAKE OFF NAVC0 COLD LEG A W-8
[
P no 1 nf a c.
i
5e FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS j
(As required by the Provision of the ASME Code Rules) 1.) Owner: Northern States Power Comoany Address: 414 Nicollet Mall. Minneacolis. Minnesota 55401 2.) Plant:
PRAIRIE ISLAND NUCLEAR GENERATING PLANT Address: WELCH. MINNESOTA
~
3.) Plant Unit :
I 4.) Owner (Certificate of Authorization):
=
5.) Commercial Service Date: 12-16-73 6.) National Board N0. for Unit: -.
7.) Components Inspected:
Manufacturer Component or Manufacturer or Installer State or National Acourtenance or Installer Serial No.
Province No.
Board No.
ASME CLASS II C1.10 PRESSURE RETAINING WELDS IN PRESSURE VESSELS C1.10 SHELL CIRCUMFERETINAL WELOS STEAM GENERATOR 11 WESTINGHOUSE 1101 68-24 W-C GT
/
ci g
a:
Ei Ss Page 2 of 4
I FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS j
(As required by the Provision of the ASME Code Rules) 1.) Owner: Northern States Power Comoany Address: 414 Nicollet Mall. Minneaoolis, Minnesota 55401 2.)
Plant:
PRAIRIE ISLAND NUCLEAR GENERATING PLANT Address: WELCH. MINNESOTA
~
3.) Plant Unit :__I___ 4.) Owner (Certificate of Authorization):
5.) Commercial Service Date: 12-16-73 6.) National Board NO. for Unit: --
7.) Components Inspected:
Manufacturer Component or Manufacturer or Installer State or National Acourtenance or Installer Serial No.
Province No.
Board No.
COMPONENT SUPPORTS ASME CLASS I PIPING ACCUMULATOR NAVC0 DISCHARGE SIRH-22/D1 RTD RETURN A NAVC0 138-RTD-4A/A RTD TAKE OFF NAVC0 COLD LEG A RPCH-118/F l
SEAL INJECTION NAVC0 LOOP A 13A-CVCS-2/C RCVCH-1247/A1 GT E
EL I
o 5
cr
$i
- E Pace 3 of 4 0;
i
I F0RN NIS-1 (back)
)
8.) Examination Dates: 02-20-87 to 02-03-87 9.)
Inspection Interval: 12-16-83 to 12-16-93 10.) Abstract of Examinations: Include a list of examination and a statement concerning status of work required for current interval.
This is a summary of the inspections conducted during a force outage of period one of the 2nd Ten Year Inspection Interval. The examinations were conducted on systems classified as ASME Class I and II.
Eddy Cur-rent examination requirements for steam generator tubes was conducted this outage in accordance with Prairie Island Technical Specification Section TS 4.12.
11.) Abstract of Conditions Noted: Other than steam generator (S.G.) tubes, there were no signs of degra dation to systems scheduled for examina-tion. There were a total of 19 tubes for S.G. No.
12 were found ex-hibiting wall thinning greater than 45%.
The anomalies detected were: 4 rounded PT indications; I hanger with a non-functioning load settings.
12.) Abstract of Corrective Neasures Reconnended and Taken:
All degraded S.G.
tubes with greater than 45% wall thinning were me-chanically plugged, a total of 19 tubes for S.G. No.12.
All anomalies were either accepted by an engineering evaluation or ac-ceptable per code. The hanger with the non-functioninf was turned over to the system engineer and a design modification was issued; the rounded PT indications were found to be acceptable per IWB 3514.
We certify that the statements made in this report are correct and the ex-aminations and corrective measures taken conform to the rules of the ASME Code,Section XI.
Date/dc 5 19ff SignedMMksWNnrr Aw B
/ //
Owner Certificate of Authorization no. (If applicable)/M Expiration Date e/'/
CERTIFICATE OF-INSERVICE INSPECTION I,
the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and/or the State or Providence of MINNESOTA and employed by HARTFORD STEAM BOILER INSPECTION & INSURANCE COM-PANY of HARTFORD. CONNECTICUT have inspected the componentp d
in J wne,r's Data Report during the period c9/cJo #gscribed this 0
7 to 3/d AP7 and state that to the best of my knowledge ~and belief, the Ownef has preformed examinations and taken corrective measures described in this owner's Data Report in accordance with the requirements of the AShE Code,Section XI.
By signing the certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Data Report.
Futhermore, neither the In-spector nor his employer shall be liable in any manner for any personal in-r jury or property damage or loss of any kind arising form or connected with g
this inspection.