G7706110088 870604 DR ADOCK 05000354 PDR

'o TABLE 3.3.7.5-1 E

ACCIDENT N)NITORING INSTRUNENTATION m

n.

MINIMUM APPLICA8LE A

REQUIRED NUMER CHANNELS OPERATIONAL t

INSTRUNENT OF CHANNELS OPERA 8LE COISITIONS ACTION 1.

Reactor Vessel Pressure 2

1 1,2,3 80 f

j 2.

Reactor Vessel Water Level 2

1 1,2,3 80 3.

Suppression Chamber Water Level 2

1 1,2,3 80 2

4.

Suppression Chamber Water Temperature

  • 2 2

1,2,3 I

80 *)

5.

Suppression Chamber Pressure 2

1 1,2,3 80

+

)

6.

Drywell Pressure 2

1 1,2,3 80.

l 7.

Drywell Air Temperature 2

1 1,2,3 80 i

8.

Primary Containment Hydrogen /0xygen Concentration w1 Analyzer and Monitor 2

1 1,2,3 80 Y

9.

Safety / Relief Valve Position Indicators (c) 2/ valve **

1/ valve ** 1,2,3 80 10.

Drywell Atmosphere Post-Accident Radiation Monitor 2

1 1,2,3 81 l

11.

North Plant Vent Radiation Monitorf 1

1 1,2,3 81 12.

South Plant, Vent Radiation Monitorf 1

1 1,2,3 81 l

13.

FRVS Vent Radiation Monitorf 1

1 1,2,3 81 PrimaryCginnent'IsolationValvePosition 1

14.

Indication 2/ valve 1/ valve 1,2,3 82 i

i

  1. High range noble gas monitors.

j

  • Average bulk pool temperature.
    • Acoustic monitoring and tail pipe temperature.

l (a) Suppression chamber water temperature instrumentation must satisfy the availability requirements specified in Specification 3.6.2.1.

j (b)0ne channel consists of the open limit switch, and the other channel consists of the closed limit switch.

]

(c) The acoustic monitor for F013H SRV may be inoperable until September 21, 1987, or until the first forced outage of sufficient duration to effect repair prior to that date, without applying the shutdown requirement of ACTION 80(a).

I

,-