Forwards Rept on Extent of Static O-Ring (Sor) Model 102 or 103 Differential Pressure Switches Installed as Electrical Equipment Important to Safety in Response to IE Bulletin 86-002.SOR Switches Not Installed in Subj Equipment
ML20214J735
Person / Time
Site: San Onofre  
Issue date: 07/28/1986
From: Medford M
SOUTHERN CALIFORNIA EDISON CO.
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
IEB-86-002, IEB-86-2, NUDOCS 8608150153
Download: ML20214J735 (4)


Text

E i

%,n f [f

%.f,f Southem Califom/s Edison Company P. O. BOX 800

[

O b3 2244 WALNUT GROVE AVENUE ROSEMEAD. CALIFORNIA 91770 July 28, 1986

<= i => =o= i 74=

u a.or..

ucer.a uccasmo U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention: Mr. John B. Martin, Regional Administrator Gentlemen:

Subject:

Docket Nos. 50-206, 50-361 and 50-362 San Onofre Nuclear Generating Station Units 1, 2 and 3 In IE Bulletin 86-02, " Static 'O' Ring Differential Pressure Switches," Southern California Edison (SCE) was requested to take the i

following actions within seven (7) days of receipt of this IE Bulletin:

l 1.

Submit a report on the extent to which SOR Model 102 or 103 (SOR 102/103) differential pressure switches are installed (or planned) l as electrical equipment important to safety, as defined in 10 CFR 50.49(b).

Include in the report: the model number of the switch, the system in which it is installed (e.g., low pressure safety injection), the application of the switch (e.g., water level

~

measurement, system flow measurement), and the function of the switch (e.g., control of minimum flow recirculation valve). A l

negative report, if appropriate, is required.

2.

Other actions are specified in this IE Bulletin for Licensees that have SOR 102/103 differential pressure switches installed in systems that are subject to Limiting Conditions for Operation in Technical Specifications.

Provided as an enclosure to this letter is the SCE response to l

Action 1, a report on the extent to which SOR 102/103 differential pressure switches are installed as electrical equipment important to safety.

In summary, based upon a thorough search of documentation and field walkdowns, it has been determined that the only such switches presently existing are in portions of the San Onofre Units 2 and 3 diesel generator fuel oil and lube oil systems which are not subject to Limiting Conditions for Operation in Technical Specifications.

Therefore, because the remaining actions specified in this bulletin are not applicable to San Onofre, no further response to this IE Bulletin 86-02 will be provided by SCE to the NRC.

I 8608130153 860728 PDR ADOCK 05000206 g

J6{- //

G PDR

o.

Mr. J. B. Martin It is not planned to use these SOR 102/103 differential pressure switches for quality affecting applications at San Onofre in the future.

Therefore, to provide assurance that SOR 102/103 differential pressure switches are not used in the future in other than the current application, these switches are being entered on the Control of Problem Equipment (C0FE)

Program master list. A search of this COPE listing is made for all quality affecting, including safety related, equipment purchase orders.

If these switches should be determined to be on a purchase order, the purchase order will be rejected or specific control will be implemented to assure the switch would only be used in the present application.

If you would like additional information concerning this matter, please let me know.

Subscribed on this Q S day of httfu

,1986.

L 6

Respectfully submitted, SOUTHERN CALIFORNIA EDIS0N COMPANY By: N[

.#/

M. O. Medford f Manager, Nuclear Licensing Subscribed and sworn o before me this

<Q 8 %

day of L,

/ '7 9/,,

V 0 h.

Al,k -

du h,

OFF b SE Notary Public4n and for the County of

.hA gjyQY q'h, g Los Angeles, State of California LOS ANGELES COUNTY My Comm En Apr.20.1930 My Commission Expires: hL c20, /970 TDM:7154F Enclosure cc:

U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 H. Rood, NRC Senior Project Manager, San Onofre Units 2 and 3 R. Dudley, NRC Project Manager, San Onofre Unit 1 F. R. Huey, NRC Senior Resident Inspecto.r, Units 1, 2 and 3

\\.

RESPONSE TO IE BULLETIN 86-02. ACTION Static "0" Rinq Oifferential Pressure Switches San Onofre Nuclear Generating Station Units 1, 2 and 3 The purpose of this bulletin was to request pressurized water reactor (PWR) licensees to determine whether or not Series 102 or 103 differential pressure switches supplied by SOR, Incorporated have been used in important to safety applications.

For those licensees utilizing the subject switches in Technical Specification systems, certain actions need to be accomplished in seven (7),

thirty (30) and sixty (60) days, respectively.

SCE response to the requested l

action is provided below.

t I

Action Required for all Licensees:

1.

Within 7 days, submit a report on the extent to which SOR Model 102 or 103 differential pressure switches are installed (or planned) as electrical equipment important to safety, as defined in 10 CFR 50.49(b).

Include in the report:

the model number of the switch, the system in which it is installed (e.g., low pressure safety injection), the application of the switch (e.g., water level measurenent, system flow measurement), and the function of the switch (e.g., control of the minimum flow recirculation valve). A negative report, if appropriate, is required.

Response for Unit 1:

Based on a review of all SONGS information systems by Instrumentation and Control personnel and cognizant engineers, and field inspections, SOR model 102 or 103 differential pressure switches are not utilized nor planned to be used at Unit 1 as part of safety related equipment.

This review satisfies the action required by this item and no further response is necessary for this bulletin.

Response for Units 2 and 3:

i As a result of the reviews conducted on Units 2 and 3 equipment important to safety, no Model 102 switches were found, and SOR Model 103 differential pressure switches were found on the Emergency Diesel Generator Fuel Oil and Lube Oil systems.

However, the SOR Model 103 switches are not subject to Limiting Conditions for Operation of the Technical Specifications. Their function is to alarm local and control room panels that the fuel oil or lube oil duplex filters have exceeded their allowable differential pressures and flow has been bypassed around the filters by the system relief valves.

For the fuel oil system, the discharge of the engine-driven fuel pumps is bypassed around the duplex filters by the system relief valve, should the filters develop high differential pressure.

Thus, the diesel engines would

, continue to operate. With respect to the lube oil system, the flow is also bypassed around the duplex filters by the system relief valves which prevents interruption of oil to the main lube oil and piston cooling pumps. Again, diesel engine operation is not affected.

The Unit 2 SOR switches have received one calibration during a refueling outage since installation in 1985, and data does not indicate any drift or difficulties with the switches, especial.ly in this low pressure application.

The following summarizes the design information associated with the SOR Model 103 differential pressure switches used at Units 2 and 3.

Design ReDort Model Number: SOR Model 103 Nnrmal Pressure Operating Switch System:

Emergency Diesel Generators Pressure SetDoint (A) Fuel Oil System 60 psig 65 psig (B) Lube Oil System 30 psig 38 psig Number of Switches:

One (1) switch on each fuel Oil and Lube 011 system for each Diesel Engine.

Four (4) Diesel Engines per Unit, 2 Units - for a total of 16 SOR Model 103 SOR d.ifferential pressure switches.

ADDlication: Differential pressure on fuel Oil and Lube Oil Duplex filters l

Function:

Alarm Local and Control Room panels that duplex filters have l

exceeded their maximum differential pressure and flow has been bypassed around them by system relief valves.

Based on the review of the subject differential pressure switch usage and calibration data, no further action is considered necessary. However, to ensure Model 102 or 103 SOR switches are not inadvertently used in other applications without proper engineering and safety reviews, SCE plans to add the SOR Model 102 and 103 switches to the SONGS Control of Problem Equipment list.