.u 3/4.8 ELECTRICAL POWER SYSTEMS
+:
l, 3/4.8.1 A.C. SOURCES
' OPERATING
LIMITING CONDITION FOR OPERATION
- 3. 8.1.1 As a minimum, the following A.C.' electrical power sources shall be j
OPERABLE:
Two physically independent circuits between the offsite transmission a.
network and the Onsite Essential Auxiliary Power System, and b.
Two separate and independent diesel generators, each with:
t 1)
A separate day tank containing a minimum volume of 120 gallons of fuel, 2)
A separate Fuel Storage System containing a minimum volume of
'28,000 gallons of fuel, and 3)
A separate fuel transfer pump.
APPLICABILITY: MODES 1, 2, 3, and 4.
j ACTION:
With an offsite circuit of the above required A.C. electrical power a.
i sources inoperable, demonstrate the OPERABILITY of the remaining A.C.
sources by performing Surveillance Requirement 4.8.1.1.la. within l
1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; separately demon-strate the operability of two diesel generators by performing Sur-i veillance Requirements 4.8.1.1.2a.4 and 4.8.1.1.2a.5 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless this surveillance was performed within the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or unless the diesel is operating
, restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD j
SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
i b.
With one offsite circuit and one diesel generator of the above j
required A.C. electrical power sources inoperable *, demonstrate the OPERABILITY of the remaining A.C. source by performing Surveillance Requirement 4.8.1.1.la. within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />,
a
~
thereafter; demonstrate the operability of the remaining diesel generator by performing Surveillance Requirements 4.8.1.1.2a.4 and 4.8.1.1.2a.5 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless this surveillance was performed within the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or unless the diesel is operating **;
restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; with the diesel I
l j
- A diesel generator shall be considered to be inoperable from the time of failure until it satisfies the requirements of Surveillance Requirements j
j 4.8.1.1.2a.4) and 4.8.1.1.2a.5).
- This test is required to be completed regardless of when the inoperable j
i diesel gen'erator is restored to OPERABLE status. The provisions of Specification 3.0.2 are not applicable.
'1 I
I McGUIRE - UNITS 1 and 2 3/4 8-1 Amendment No. 71 (Unit 1)