Monthly Operating Rept for Feb 1987
ML20212P623
Person / Time
Site: Limerick  
Issue date: 02/28/1987
From: Alden W, Gropp R
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
NRC OFFICE OF RESOURCE MANAGEMENT (ORM)
References
CON-#187-2890 OL, NUDOCS 8703160174
Download: ML20212P623 (6)


Text

AVERAGE DAILY UNIT POE R LEVEL DOCKET No. 50 - 352 UNIT LIMERICK UNIT 1 DATE MARCH 16, 1987 COMPANY PHILADELPHIA ELECTRIC COMPANY R. N. GROPP TECHNICAL ASSISTANT LICENSING SECTION PAJCLEAR SUPPORT DEPARTMENT TELEPHONE (215) 841-5058 MONTH FEBRUARY 1987 DAY AVERAGE DAILY PONER LEVEL DAY AVERAGE DAILY PCHEM LEVEL (194E-NET 1 (PME-NET) 1 505 17 1035 2

719 18 1033 3

974 19 1042 4

1029 20 1047 5

1005 21 1048 4

1012 22 1036 7

1020 23 1034 8

985 24 1035 9

999 25 233 4

10 987 26 932 11 991 27 931

,N(

12 980 28 902 f\\;

13 942 i

14 960 l

15 1050 16 1043 8703160174 870228 PDR ADOCK 05000352 PDR R

4 OPERATING DATA REPORT e'

DOCKET No. 50 - 352 DATE MARCH 16, 1987 COMPLETED BY PHILADELPHIA ELECTRIC COMPANY R. N. GROPP TECHNICAL ASSISTANT LICENSING SECTION NUCLEAR SUPPORT DEPARTMENT TELEPHONE I215) 841-5058 OPERATING STATUS

1. WIT NAME: LIMERICK UNIT 1 1 NOTES: UNIT 1 EXPERIENCED TNO I

l l

2. REPORTING PERIOD: FEBRUARY, 1987 l

SCHEDULED LOAD REDUCTIONS l

l l

3. LICENSED THERMAL P0HERitMT):

3293 l

AND ONE FORCED SHUTDO W.

l l

l C. NAMEPLATE RATING (GROSS PME)I 1138 l

l l

l

2. DESIGN ELECTRICAL RATING (NET PMEnt 1055 l

l l

l

6. MAXIMLM DEPENDABLE CAPACITY (GROSS tME): 1092 l

l I

1

7. MAXIMUM DEPENDABLE CAPACITY INET WE18 1055 l

l S. IF CHANGES OCCUR IN CAPACITY RATINGS IITEMS NL2BER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS 8

9. PONER LEVEL TO NHICH RESTRICTED, IF ANY (NET PME):
10. REASONS FOR RESTRICTIONS, IF ANYI j

THIS MONTH YR-TO-DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD 672 1,416 9,432 l
12. NUPBER OF HOURS REACTOR HAS CRITICAL 672.0 1,320.1 8,037.1 I
13. REACTOR RESERVE SHUTDOW HOURS 0.0 0.0 0.0 1% HOURS GENERATOR ON-LINE 659.8 1,293.9 7,929.9
15. LNIT RESERVE SHUTDOPN HOURS 0.0 0.0 0.0 j

l

16. GROSS THERMAL ENERGY GENERATED ltMH) 2,015.088 4,026,662 25,624,824

=

17. GROSS ELECTRICAL ENERGY GENERATED (PMH) 662,100 1,324,150 8,451,030

=

18. NET ELECTRICAL ENERGY GENERATED ltMH) 636,205 1,271,943 8.120,793 PAGE 1 0F 2 i

t

OPERATING DATA REPORT (CONTIMJED)

DOCKET M3. 50 - 352 DATE MARCH 16, 1987 THIS MONTH YR-TO-DATE CLMJLATIVE

19. LMIT SERVICE FACTOR 98.2 91.4 84.1
20. LMIT AVAILABILITY FACTOR 98.2 91.4 84.1
21. UNIT CAPACITY FACTOR (USING MOC NET) 89.7 85.1 81.6
22. LMIT CAPACITY FACTOR (USING OER NET) 89.7 85.1 81.6
23. LMIT FORCED OUTAGE RATE 1.8 8.6 4.3
20. SHUTDope4S SCHEDULED OVER NEXT 6 MONTHS ITYPE, DATE, AND DURATION OF EACH)2 REFUELING OUTAGE MAY 16, 1987 TO AUGUST 1,1987
25. IF SHUTDoped AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP 8/1/87
26. LMITS IN TEST STATUS (PRIOR TO C0pmERCIAL OPERATION):

FORECAST ACHIEVED INITIAL CRITICALITY 12/19/84 12/22/84 INITIAL ELECTRICITY MID APRIL 85 4/13/85 CatNERCIAL OPERATION IST QTR 86 2/01/86 PAGE 2 0F 2 i

L

LMIT SHUTD0DetS AND POMER REDUCTIONS DOCKET No. 50 - 352 UNIT NAME LIMERICK UNIT 1 DATE MARCH 16, 1987 REPORT MONTH FEBRUARY, 1987 COMPLETED BY PHILADELPHIA ELECTRIC COMPANY R. N. GROPP TECHNICAL ASSISTANT LICENSING SECTION NUCLEAR SUPPORT DEPARTMENT TELEPHONE t2151 841-5058 1

I I

I l METHOD OF l LICENSEE ISYSTEMICOMPONENTl CAUSE AND CORRECTIVE l

I TYPE l DURATION I RE ASON I SH'1TTING DODN I EVENT l CODE l CODE l ACTION TO NO.I DATE I i1)l tHOURSIl (2) l REACTOR I3) 1 REPORT S I (4) l ESI l PREVENT RECURRENCE I

I I

l 1

1 I

I i

3 l C70201 1 F l 109.9 l F l 2

l WA l CI l VALVEX l REACTOR COOLANT SYSTEM UNIDENTIFIED LEAKAGE I

I l

l l

l l

l 1 INSIDE THE LRYMELL APPROACHED TECH. SPEC.

l l

l l

l l

l l

l LIMIT. MISCELLANEOUS VALVE PACKING LEAKAGE l

l l

l l

l l

l l MAS IDENTIFIED AND REPAIRED. (01/27/87)

I I

I I

I I

I I

l 4 I 870212 l S I 000.0 l F l 4

l WA l ZZ l 777777 l P0HER REDUCTION TO ACCOPN0DATE CONTROL ROD l

l l

l l

l l

l l PATTERN ADJUSTMENT.

I I

I I

I I

I I

I 5 l C70225 l F l 012.2 l A l 1

l WA l EB l GENERA l P0HER REDUCTION AND MAPAJAL TRIP OF TURBINE TO l

l l

l l

l l

l l INVESTIGATE A FIELD GROUND INDICATION ON THE l

l l

l l

l l

l l MAIN GENERATOR. THE PROBLEM MAS ATTRIBUTED TO l

l l

l l

l l

l l THE GROUND DETECTION CIRCUITRY.

I I

I I

I I

I I

l 6 i C70227 i S I 000.0 l F l 4

I WA l ZZ l 777777 l P0HER REDUCTION TO ACCOPN0DATE CONTROL ROD I

l l

l l

l l

l l PATTERN ADJUSTMENT AND REMOVE EXTRACTION STEAM 1

l l

l l

l l

l l FROM THE SIXTH STAGE FEEDHATER HEATERS TO I

I l

l l

l l

l l MAXIMIZE P0HER OPERATIONS.

I l

l ----- 1 I

I I

I i

1 I

i 122.1 1 I

I I

I I

(1)

(2)

(3)

(4)

F - FORCED REASON HETHOD EXHIBIT G - INSTRUCTIONS S - SCHEDULED A - EQUIPHENT FAILURE (EXPLAIN) 1 - HANUAL FOR PREPARATION OF DATA B - HAINTENANCE OR TEST 2 - HANUAL SCRAM.

ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOHATIC SCRAM.

EVENT REPORT (LERI D - REGULATORY RESTRICTION 4 - OTHER (EXPLAIN)

FILE IPAJREG-0161)

E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)

G - OPERATIONAL ERROR (EXPLAIN)

H - OTHERIEXPLAIN)

EXHIBIT I - SANE SOURCE

1 f

DockGt No. 50-352

~

Attachment to Monthly Operating Report for February, 1987 Limerick Generating Station Unit 1 February 1 through February 28, 1987 I.

Narrative Summary of Operating Experiences The report period began as reactor power was being ramped up following a forced mini-outage during January.

On February 3, at 1908 hours0.0221 days <br />0.53 hours <br />0.00315 weeks <br />7.25994e-4 months <br />, full reactor power was achieved.

On February 2, the

'D' TIP machine was declared inoperable because the machine's "take-up" reel had failed causing damage to the TIP cable.

The cable detector assembly was replaced and the TIP machine was returned to service on February 9.

On February 18, Limerick Unit 1 received a technical specification amendment that permitted an increase in core flow to 105% and the removal of some feedwater heating which enables the reactor to maintain higher power levels during end-of-cycle coastdown.

On February 13, reactor power was reduced to 800 MWe to facilitate control rod pattern adjustment.

On February 27, reactor power was reduced to 630 MWe for control rod pattern adjustment and removal of extraction steam from the sixth stage feedwater heaters to maximize power operations.

On February 25, following a load reduction to 25% power, the turbine was manually tripped at 0613 hours0.00709 days <br />0.17 hours <br />0.00101 weeks <br />2.332465e-4 months <br /> to investigate a 4

field ground indication on the main generator.

During this period, the reactor remained at approximately 26% power by routing steam through the turbine bypass valves to the condenser.

It was determined that the problem existed in the ground detection circuitry.

The generator was synchronized and the unit returned to service at 1825 hours0.0211 days <br />0.507 hours <br />0.00302 weeks <br />6.944125e-4 months <br />.

The unit ended the report period operating at approximately 100% power.

II.

Challenges to Relief Valves During the month there were no challenges to the main steam safety-relief valves.

PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILADELPHIA. PA.19101 1285)841-4000 March 13, 1987 Docket No. 50-352 Director Office of Resource Management US Nuclear Regulatory Commission Washington, DC 20555

SUBJECT:

Limerick Generating Station Monthly Operating Report Gentlemen:

Enclosed is the monthly operating report for Limerick Unit 1 for the month of February, 1987, forwarded pursuant to Technical Specification 6.9.1.6.

Very truly yours, W. M. Alden Engineer-In-Charge Licensing Section Nuclear Support Department Attachment cc:

Director, Office of Inspection & Enforcement, USNRC (12 copies)

Dr. T.

E. Murley, NRC E. M. Kelly, Senior Resident Site Inspector Mr. David E. Ney, PA Dept. of Envir. Resources Mr.

P. A. Ross, NRC (2 copies)

INPO Records Center Mr.

D'. W. Diefenderfer, General Electric See Attached Service List h

' I