. _ _.
i APPENDIX A to License No. DPR-12 TECHNICAL SPECIFICATIONS for Peach Bottom Atomic Power Station Unit No. 1 1.0 LOCATION AND SITE The Peach Bottcm Atomic Power Station Unit No. 1 is located in Peach Bottom Township,. Pennsylvania, on the western shore of the Conowingo Pond at the mouth of Rock Run Creek on a site owned by Philadalphia Electric Company.
The Exclusion Area shall consist of an area within the Peach Bottom Atomic Power Station which is enclosed within locked barriers, and contains the Containment Vessel, Spent Fuel Pool Building and Radwaste Building.
The only activity carried on within the Exclusion Area shall be routine and emergency inspections and maintenance associated with the possession of the decommissioned Peach Bottom Station Unit No.
1.
The Peach Bottom Atomic Information Center may be located on the site and be open to the public, provided a suitable evacuation procedure is maintained.
Peach Bottom Atomic Power Station, Units 2 and 3 are also located on the site.
2.0 ADMINISTRATIVE AND PROCEDURAL SAFEGUARDS 2.1 Administrative Organizations and Controls (a)
Manager - Nuclear Plant c.y The' Manager - Nuclear Plant of Peach' Bottom shall have the responsibility for administration of all Unit No. 1 functions.
(b)
Controls 1.
Except when opened to provide egress for inspections, surveys and repairs, the following exclusion area barriers shall be maintained locked:
1.
The gate in the Exclusion Area. fence located outside the containment personnel access lock at Elevation 116'-0".
l fa R 5i g g.,,
'1 f.
App 3ndix A Page 2 11.
The gate in the Exclusion Area fence located outside the Spent Fuel Pool Area personnel door at Elevation 116'-0".
iii.
The gate in the Exclusion Area fence located outside the containment personnel access lock on Elevation 176'-6" iv.
Containment personnel access lock at Elevation 176'-6" v.
Containment personnel access lock at Elevation 116'-0" vi.
Grating over southwest stairway leading from refueling floor of Containment to Containment lower levels vii.
Personnel door into Spent Fuel Pool Area at Elevation 116'-0" viii.
Radwaste Room personnel door at Elevation 104'0" 2.
Employees of the Peach Bottom Atomic Power Station shall report to the Peach Bottom Manager - Nuclear Plant or his designated representative any observed indication of change in facility status as shown by smoke, fire, tornado, flood or attempted break-in and take any immediate action authorized.
3.
Administrative procedures shall be established for the notification and reporting of the following events:
1.
The entrance of an unauthorized person (s) into the facility.
ii.
A significant change in the radiation or contamination levels in the facility.
4.
Security of the facility shall be included as a part of the Peach Bottom Atomic Power Station security plan.
Appendix A.
Paga 3 5.
In the event of a Probable Maximum Flood, the personnel access door will be opened in accordance with the Peach Bottom Atomic Power Station Units 2 and 3 flood procedures.
2.2 Records Licensee shall keep logs and records in sufficient scope and detail to establish that the facility is being maintained within the limitations of the Part 50 Possession Only license.
The following items shall be recorded:
(a)
Facility radiation surveys (b)
Inspections of the physical barriers (c)
Reportable events Pe' iodic Inspections 2.3-r A definite inspection schedule shall be established for the Unit No. 1 facility that will be performed by personnel knowledgeable in nuclear radiation monitoring and with the radiological hazards associated with-the decommissioned. plant.
Inspections of the plant will be conducted concurrently with radiation monitoring.
The frequency of these inspections shall be no less than seminannua'lly.
The records of these inspections shall be maintained on file.
The inspection shall include a survey of radiation levels and surface contamination as well as air particulate activity in uncontrolled areas in the containment vessel.
The filter on the ventilation
" breather" tube from the containment vessel shall also be changed annually and surveyed for activity.
If entry and/or work in the controlled area of the containment should be necessary, radiation level and airborne activity surveys shall be performed prior to beginning work and all work shall be performed under controls, as appropriate, to minimize the radiation exposure of personnel and to prevent the release of radioactivity to the environment.
All radiation surveys, tests, counting work and radiation exposure control measures shall be performed
'in accordance with written instructions and procedures that conform with the requirements of the Peach Bottom
.' f ;
4f-CERTIFICATE OF SERVICE I hereby certify that copies of the foregoing Amendment were served on
.the following by deposit in the United States mail,.first-class' postage prepaid, on this 4th day of March,1987.
Regional Administrator U.S. Nuclear Regulatory Commission, Region I 631 Park Avenue King of Prussia,'PA 19406 T. P. Johnson, Resident Inspector U. S. Nuclear Regulatory Commission Peach Bottom Atomic Power Station P. O. Box 399 Delta, PA 17314 Mr. Thomas Gerusky, Director Bureau of Radiation Protection Department of Environmental Resources Fulton Bank-Building, 5th Floor Third 4 Locusts Streets Harrisburg, PA 17120 l
a
/
EugenpJ./Bradley
(
Attorney for Philadelphia Electric Company
..