ML20212H351

From kanterella
Jump to navigation Jump to search
Ro:On 861209,diesel Generator 1DG01KB Output Breaker Did Not Close on Signal from Control Room.Breaker Circuitry & Linkages Inspected.Following Successful Surveillance Run, Diesel Generator Declared Operable on 861210
ML20212H351
Person / Time
Site: Braidwood 
Issue date: 02/03/1987
From: Hunsader S
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
2527K, NUDOCS 8703060079
Download: ML20212H351 (8)


Text

-_-____

.s N

g.

g One Fwst Nabonel Plaza, Checago, INinois

-\\

Address Reply to: Post Office Box 767 Ns Chica00. lHinois 60000 0767

-PRIORITY R0'Jil!IG fj rst 13ec ind kh lGs M February 3,.1987 om-tost'?D

, ttW3

,- s9 f t M:s hr.L s

jy 5S 0J,.,

ge a.

Mr. James-G. Keppler'

. Regional Administrator U.S. Nuclear Regulatory Commission Region'III' 799 Roosevelt Road Glen-Ellyn. IL.-60137 l

Subject:

Braidwood Unit 1 Diesel Generator 1DGolKB Failure NRC Docket No. 50-456

Reference:

(a)

NUREG-1223, Technical Specification, dated October, 1986

Dear Mr. Keppler:

Section 4.8.1.1.3 of reference (a). requires'that all diesel generator failures, valid or.non-valid,-be reported to the NRC

' pursuant to Specification 6.9.2.

Attachment "A" provides the description of the failure'of Braidwood Diesel Generator 1DG0lKB to meet surveillance starting criteria.

The annotated failure in Attachment "A" of the 1DG0lKA diesel generator occurred in September, 1986 prior to the formal

. implementation of reference (a).

1DG0lKA has completed the requisite surveillance testing and has been declared operable.

Attachment "B"

provides a summary of diesel ~ generator 1DGolKB's performance since the successful completion of pre-operational testing.

I Please direct any questions concerning this matter to this office.

Very truly yours, G703060079 870203

~

d PDR ADOCK 05000456 S

S.

C.

Hunsader PDR Nuclear Licensing Administrator

./klj cc:

Braidwood Resident Inspector 11 %

l 2527K

n

.CWS/87-18 Attachment A

.Braidwood Station's;1B diesel generator is currently being run on a weekly. basis per. operating surveillance 1BwCS 3.1.1.2.a-2.

On December 9th at 1820 hours0.0211 days <br />0.506 hours <br />0.00301 weeks <br />6.9251e-4 months <br /> 1B diesel generator was started. The diesel generator's output breaker did not-close when given the signal from the control room. After attempting to close the breaker again, the diesel generator was ' shutdown per normal operating procedures.

The 1B diesel generator was declared inoperable. This failure was the seventh since the completion of pre-operational testing.

The breaker's circuitry and linkages were inspected and troubleshooting was performed by Station electricians. The breaker functioned properly throughout all the troubleshooting phases.

Three successful load tests have been completed since the failure.

The 1B diesel generator will be started weekly for a 20 week duration per Technical Specification Table 4.8.1.

The diesel generator was declared operable following troubleshooting and a successful surveillance run on December 10, 1986.

The corrective action taken to address the seven existing failures have been successful in preventing the recurrence of identical failures. Due to the relative diversity of the failures no trends have been established, and general, major corrective actions are not warranted at this time. The fifth and sixth failures resulted from stopwatch start times of greater than ten seconds.

These are believed to have been caused by operator error.

However, due to the lack of information available, the cause cannot be definitely attributed to operator error. Therefore Braidwood Station is conservatively considering the two starts failures.

The diesel generators are inspected during every operability run. Any problems that develop are corrected in a timely manner.

Braiducod Station believes that this approach is appropriate to maintain proper diesel generator availability and operability.

Braiducod Station is confident that, through the weekly operability surveillance runs and continued close examination of the engine and its compcnents, the diesel generator's reliability can be demonstrated.

The 1A and IB diesel generators have met all testing and operability requirements of regulatory position C.2 of Regulatory Guide 1.108.

The 1A diesel generator has experienced one valid failure since the completion of pre-operational testing. The 1A diesel generator's ability to provide electric power to engineered safety feature equipment has been demonstrated reliable.

Braidwood Station strongly believes that its ability to meet license requirements for an operable emergency power supply will be maintained in the future.

(4377:)

1

.C 7

^[,

. CWS/87--18 i AttachmQnt.B.

Summary of 1B Diesel Generator Starts Activity

Date-Activity
1) 10 Performed Load Reject Surveillance,18wVS~

8.1.1.' 2. f-12.

St' rip chart recorder _did not trace.

Invalid Test - Successful

~

L 2)- 8-10-86 Performed Load Reject Surveillance,.lBwVS 8.1.1.2.f-12.

Engine loaded to 5500 kw for < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

Invalid Test - Successful 1

3)L 8-11-86 Performed 18 month diesel generator inspection, IBwVS 8.1.2.e-2.'to check peak' firing and. compression pressures.

Run at 5500 kw 'for 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />. Valid Test -

Successful

4) 1'0-86 Attempted-to complete.18. month diesel generator inspection,'lBwVS 8.1.1.2.e-2.

~ Diesel generator

? tripped on " Incomplete Sequence".

Cause was improper fuel priming. Valid Test - Failure-(1) 5'). 9-10-86 Engine was started and tripped on " Incomplete.

~

Sequence". Troubleshooting Run - Invalid Test --

-Failure

6) 9-13-86 Ran diesel generator unloaded for 5 minutes.

Troubleshooting Run - Invalid Test - Successful 7)~

9-13-86 Ran diesel generator unloaded for 8 minutes.

Troubleshooting Run - Invalid Test - Successful 8);'9-21-86

~ Ran diesel generator to complete 18 month inspection, 1BwVS 8.1.1.2.e-2.

Ran' diesel ~generatcr 5500 kw for 4.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

Valid Test - Successful

9) 22-86 Attempted Auto-Start Surveillance of diesel generator 1BwVS 8.1.1.2.f-8.

Diesel generator tripped on

" Incomplete Sequence". Loss of fuel prime problem.

Valid Test - Failure (2) 10) 9-29-86 Diesel generator run to check repairs on fuel system. Troubleshooting Run - Invalid Test -

Successful 11) 9-30-86 Performed diesel generator auto-start on SI signal surveillance, IBwVS 8.1.1.2.f-8.

Diesel was run for less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Invalid Test - Successful 12) 9-30-86 Diesel generator run for less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to check fuel prime.

Invalid Test - Successful (4377:):

c_

\\

(CWS/87-18

.q Attachment B

' Summary of 1B Diesel ' Generator Starts Activity L Date Activity 13)1 110-01-86 Diesel generator run for less'than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to check fuel,phime. : Invalid Test - Successful 14)~ 10-02-86 Performed Trip Bypass Surveillance,12wVS 8.1.1.2.f-10.

Diesel generator was not loaded.

~ Invalid Test - Successful 15)l 10-02-86 Performed final.section of Trip Bypass Surveillance,

~

IBwVS 8.1.1.2.f-10.

Diesel generator was run for less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> unloaded.

Invalid Test - Successful 16 )'

10-02-86 Performed Alternate AC Power Surveillance,1BwCS 8.1.1.1.b-1.

Diesel generator.was run at 500 kw for less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Invalid Test - Successful-17) 10-02 Diesel generator run for 12 minutes unloaded to check frequency.

Invalid Test - Successful

-18)- 10-04-86 Operating attempted'to run operability-surveillance, IBwCS 8.1.1.2.a-4.

Diesel generator did not start.

Valid Test.- Failure'(3) 19)- 10-05-86 Ran SI signal override of Test Mode Surveillance, 1BwVS 8.1.1.2.f-20.

Diesel genarator was run for less than one hour.

Invalid-Test - Successful,

20). 10-05-86 Operating performed the semi-annual operability.

surveillance, IBwCS 8.1.1.2.1-4.

Valid Test -

-Successful 21). 10-06-86 Ran SI signal override of Test Mode Surveillance, 1Bw"S 8.l'.l.2.f-20.

Invalid Test - Successful 22) 10-14-86 Start diesel for 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> loaded run per IBwVS 8.1.1.2.f-14.

Stopped diesel after 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded due to cylinder noise. Valid Test - Successful 23) 10-14-86 Started diesel for 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> loaded run per 1BwVS 8.1.1.2.f-14.

Valid Test - Successful 24). 15-86 Diesel generator was started on an under voltage and SI signal following the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run per 1BwVS 8.1.1.2.f-14.

Governor response to loads was unsatisfactory. Diesel was shutdown. Governor adjustments made. Valid Test - Failure (4) 25) 10-12-86 Started the IB diesel generator for speed servo governor adjustment. Troubleshooting Run - Invalid Test - Successful V

(4377=)

I

/GWS/87-18 g

Attachment B.

J Summary of IB Diesel' Generator Starts-Activity i-

"Date

" Activity

~

'I 126) 10-17-86 Started'the diesel on an-SI signal to adjust governor in the Emergency Mode. ~ Troubleshooting Run - Invalid Test - Successful 27) 10-17 Started'and loaded the diesel generator.to 5500 kw-for-2 hours-for the auto-actuation. portion of BwVS

.8.1.1.2.f-14. - Valid Test - Successful 28)~ 10-17-86 J Diesel generator emergency started for. surveillance 1BwVS 8.1.l.2.f-14.

Invalid Test - Successful

,29) 10-19 Diesel generator was started on an under voltage signal for surveillances lBwVS 8.1.1.2.f-16.

Engine-was run for 7 minutes and stopped.,. One strip chart channel did_not record.

Invalid Test'- Successful

30) 19-86 Diesel-generator 'was auto started on under ' voltage _

signal per 1BwVS. S. I. l.2. f-1.

Diesel generator was run for less than one hour.

Invalid Test'- Successful 31)- 10-19-86 -Operating performed Alternate AC Power Supply Surveillance. The diesel generator was run for less-than'one hour.

Invalid Test-- Successful 32).-10-24-86. Operating performed the monthly operability '

surveillance.

1BwCS 8.1.1.2.a-2.

The operato'r recorded an 11 second start with a stopwatch. Valid Test - Failure (5) 33) 10-31-86 Diesel generator was started to troubleshoot ~ start time. Strip chart connections uere loose causing erroneous diesel engine indication.

DG was stcpped.

Troubleshooting Run - Invalid Test - Failure.

34) 11-01-86 Diesel generator was started to check strip chart connection problem.

DG was run for less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Troubleshooting Run - Invalid Test - Successful 35) 11-01-86 Diesel generator was started for Monthly Operability Surveillance, IBwCS 8.1.1.2.a-2.

Valid Test -

Successful 36) 11-07-86 Operating performed the Monthly Operability Surveillance, 1BwCS 8.1.1.2.a-2.

Operator recorded a 13.2 second start with a stopwatch.

Valid Test -

Failure (6)

(4377z)

. m -g ms r

r

~

i>

,f CWS/ 87--IS -'

~

-AttachmInt B 2

Summary-of 13 Diesel-Generator Starts Activity-

"c!

Date,

-Activity o

37) 08-36 f Monthly Operability. SurveillanceilEwCS.8.1.1.2.a-2 o

was performed with 'stripf chartirecorder.to-;

~

investigate _ start time. Diesel generator started fwithin' limits' and was ; run.for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at.

5500 kw.

Valid. Test - Successful

- 38): 11-11-86. performed Operability Surveillance IBwOS.

8.~ 1.1. 2. a-2.' Diesel generator.run for greater than' l-hour at.5500 kw.

Valid Test - Successful

39) 21-86 i Diesel generator was started after. tightening air start valves and. adjusting timing.

Diesel generator tripped on incomplete sequence. Troubleshooting Run-Invalid Test - Failure 40) 11-23-86 Diesel generator was run"to investigate' incomplete

-sequence trip. Diesel generator trips on incomplete sequence. Troubleshooting Run - Invalid Test - Failure

~

'41) 11-23-86 Diesel ~ generator was-run to investigate Incomplete,

-Sequence Trip. Diesel, generator tripped on incomplete sequence. Troubleshooting Run - Invalid

' Test - Failure 42)- 11-23-86 Diesel generator was run to investigate Incomplete Sequence Trip. Engine was run for 7 minutes'with a jumper installed. Troubleshooting Run - Invalid Test

--Successful

'43) 11-25-86 Diesel generator was run to investigate Incomplete Sequence - Trip. Diesel generator tripped on incomplete sequence. Troubleshooting Run - Invalid Test - Failure

-44) 11-25-86 Diesel generator was run to investigate Incomplete Sequence Trip. Diesel generator tripped on incomplete sequence. Troubleshooting Run - Invalid Test - Failure 45) 11-26-86 Diesel generator was run to investigate incomplete sequence trip. Engine was run for 10 minutes with a jumper installed. Troubleshooting Run - Invalid Test

- Successful 46) 11-26-86 Diesel generator was run to investigate incomplete sequence trip. DG was run for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at 5500 kw.

Troubleshooting Run - Invalid Test -

Successful (4377z)

Y

..m

'~

CWS/87-18

. Attachment B s

+

~

s.

' Summary of 'lB-Diesel 1 Generator' Starts Activity

-L

-- I lDate-3Netivity 47) l'l-26-86 Operating performed the Monthly.Operab'ility x

Surveillance:lBwCS 8.1.1.2.a-2.

Diesel generator was-run' for greater.than;1: hour at 5500 kw.

Valid Test -

Successful 48) 12-02-86 ' Operating performed the Monthly. Operating

. Surveillance 1BwCS 8.1.1.2.a-2.

Diesel-generator was' run for greater than 1. hour at:5500 kw. -Valid Test -

Successful 149) 09-86 Diesel generator was started on a quarterly slave

~

relay surveillance.

Diesel generator was:run for

~1ess than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

Invalid ~Testz-Successful 50) 12-09-86 Operating performed the Monthly Operability Surveillance.

The diesel generator output breaker did not close.. Valid Test - Failure (7) 51) 12-10-86 Diesel generator started to troubleshoot output breaker.. Breaker-functioned properly.. Diesel

. generator was run~for less,than one hour.

Troubleshooting Run - Invalid Test - Successful

~

.52) 12-10-86 : - Diesel ~ generator was started -on a quarterly slave relayisurveillance.

Diesel-generator.was run'for

.less than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

Invalid Test -~ Successful-53)~.12-10-86 Operating performed the Monthly Operability.

Surveillance 1BwCS 8.1.1.2.a-2.. Diesel generator was-run for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at 5500 kw.

Valid Test -

Successful

54) '12-17-86 Operating performed monthly operability surveillance 1BwCS 8.1.1.2.a-2.

Diesel generator was run for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at 5500 kw.

Valid Test -

' Successful

-55) 12-29-86 Performed a maintenance troubleshooting run. The diesel generator tripped on incomplete sequence.

Troubleshooting Run - Invalid Test - Failure 56) 12-30-86 Performed a troubleshooting run on the incomplete sequence trip. The diesel generator tripped on incomplete sequence. Troubleshooting Run - Invalid Test - Failure (4377 )

g' gm r -- -- g - -

.rw --

e

_x,-

r e

,3_

,~

-._s o.

'g1 -:w i.CWS/87-18;

'C -

^

~

wJ Attachment.B.

[,-

- =..:

-:Summarv of' 1B ' Diesel'. Generator Starts Activity --

L s'

Date Activity'

-' 57 )-.

l-02-87-: Performed a'maintenanceItroubleshooting run.

rTroubleshooting Run~. Invalid' Test - Successid1T

~

+

58).1 -l-02-87 [ Operating performed Monthly Op'erability Surveilla' ce :

n 1BwCS.8.1.l.2;a-2.

Diesel. generator'was run for-

.. greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> at 5500 kw.

Valid Test'-

Successful:

s ' ""

us

~

+,, -/

h s.

~

N

$5 j

4 i

f t

j i:

i 3

k (4377z) f s'

y cry,,


m-,-..----e,----

- - -,.-.-ev-

-~ra -ev -e v-es y-m v ww y w ~ -e c+ y--*~wv

+*remmw<-+

  • ew-r~=e-*e*-,w-e=-+

r v,

  • - ' - - - - -