ML20210H177

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs 3.8.1.1 Re EDG AOT Increase from 72 H to Ten Days
ML20210H177
Person / Time
Site: Waterford 
Issue date: 07/29/1999
From:
ENTERGY OPERATIONS, INC.
To:
Shared Package
ML20210H145 List:
References
NUDOCS 9908030296
Download: ML20210H177 (19)


Text

e:

l l

t i

l 1

NPF-38-220 ATTAC9 MENT A EXISTING SPECIFICATIONS i

9908030296 990729 PDR ADOCK 05000302 P

PDR-

INDEX ADMINISTRATIVE CONTROLS I

SECTION PAGE 1

6.11 RADIATION PROTECTION PR0 GRAM...............................

6-22 6.12 HIGH RADIATION AREA........................................

6-22 6.13 PROCESS CONTROL PR0 GRAM....................................

6-23 6.14 0FFSITE DOSE CALCULATION MANUAL............................

6-24

' 6.15 CONTAINMENT LEAKAGE RATE TESTING PROGRAM...................

6-24 l

4 WATERFORD UNIT 3 XVIII Amendrant No. 64,124

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8 A.C. SOURCES OPERA 1NG g

NG CONDITION FOR OPERATION i

3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

Two physic' ally independant circuits between the offsite transmission a.

network and the onsite Class IE distribution system, and b.

Two separate and independent diesel generators, each with:

1.

Diesel oil feed tanks containing a minimum volume of 339 gallons of fuel, and 2.

A separate diesel generator fuel oil storage tank containing:

a.

A minimum volume of 38,760 gallons of fuel, or b.

A fuel oil volume less than 38,760 gallons and greater than 38,000 gallons of fuel for a period not to exceed j

5 days (provided replacement fuel oil is onsite within the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />), and 3.

A separate fuel transfer pump.

APPLICABILITY: MODES 1, 2, 3, and 4.

Engg:

a.

With one offsite circuit of 3.8.1.la inoperable, demonstrate the OPERASILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.la within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Restore the offsite A.C. circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least H0T STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.

With one diesel generator of 3.8.1.lb inoperable, demonstrate the OPERASILITY of the offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.la (separately for each offsite A.C. circuit) within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the diesel generator became inoperable due to any cause other than an inoperable i

support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERA 81LITY of the remaining OPERABLE diesel generator (unless it has been successfully tested in the last 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />) by performing Surveillance Requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless the absence of any potential common mode failure for the remaining diesel generator is demonstrated.

Restore the diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be l

in at least H0T STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With one offsite A.C. circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERA 8ILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.la within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and, if the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining 0PERABLE diesel generator by performing Surveillance Requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (unless it is already operating) unless the absence of any potential common mode failure for the remaining diesel generator WATERFORD - UNIT 3 3/4 8-1 AMENDNENT N0. H,R 126

o 3/4.8 ELECTRICAL POWER SYSTEMS BASES 3/4.8.1. 3/4.8.2. and 3/4.8.3 A.C. SOURCES. D.C SOURCES. and ONSITE POWER DISTRIBUTIONiSYSTEMS

.The OPERASILITY of the A.C. and D.C. power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety-related equipment required for (1) the safe shutdown of the facility and (2) the mitigation and control of accident conditions within the facility.

The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix A to 10 CFR Part 50.

The Limiting Condition for Operation (LCO) ensures that each ditsel generator storage tank contains fuel oil of a sufficient volume to operate each diesel I

generator for a period of 7 days. The minimum required volume is 6ased on the time-dependent loads of the diesel generator following a loss of offsite power and a design bases accident and includes the capacity to power the engineered safety features in conformance with Regulatory Guile 1.137 October 1979., The minimum onsite stored fuel oil is sufficient to operate the diesel generator for a period longer than the time to replenish the onsite supply from the outside sources discussed in FSAR 9.5.4.2.

An additional provision is included in the LCO which allow the diesel generators to remain operable when their 7 day fuel oil supply is not available.

This provision is acceptable on the basis that replacement fuel oil is onsite within' the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after falling below the 7 day supply.

The ACTION requirements specified for the levels of degradation of the power sources provide restriction upon continued facility operation commensurate with i

the level of degradation. The OPERABILITY of the power sources are consistent with the initial condition assumptions of the safety analyses and are based upon maintaining at least one redundant set of onsite A.C. and D.C. power sources and y

associated distribution systems OPERABLE during accident conditions coincident with an assumed loss-of-offsite power and single failure of the other onsite A.C.

source.

The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.93, " Availability of Electrical Power Sources," December 1974.

When one diesel generator is inoperable, there is an additional. ACTION requirement to verify that all required systems, subsystems, trains, components, and devices that depend on the remaining OPERA 8LE-diesel generator as a source of emergency power are also OPERABLE, and that the steam-driven auxiliary feedwater pump is OPERA 8LE.

This requirement is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable.

The term verify as used in this context means to administrative 1y check by examining logs or other information to determine if certain components are out-of-service for maintenance or other reasons.

It does not mean to perform the Surveillance Requirements needed to demonstrate the OPERABILITY of the component.

-The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that (1) the facility can be maintained in the shutdown or refue1 Lng condition for extended time periods and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

WATERFORD - UNIT 3 8 3/4 8-1 AMENDMENT NO. 92

+

CONTAINMENT LEAKAGE RATE TESTING PROGRAM (Continued)

Leakage rate ac6eptance criteria are:

a.

Overall containment leakage rate acceptance criteria is s i t L,. Durine % first unit startup following each test performed in accordance with this program, the overall containment leakage rate acceptance criteria are 5 0.60 L for the Type B and Type C tests and 5 0.75 L, for Type A tests.

b.

Air lock acceptance criteria are:

1.

Overall air lock leakage rate is 10.05 L, when tested at 1 P,.

2.

Leakage rate for each door seal is 5 0.005 L, when pressurized to 110 psig.

I c.

Secondary containment bypass leakage rate acceptance criteria is 5 0.06 ( when I

tested at 1 F,.

r d.

Containment purge ve'ves with resilient seals acceptance criteria is 5 0.06 L, when tested at t P.

The provisions of Specification 4.0.? do not apply to the test frequencies specifed in the Containment Leakage Rate Testing Program.

The prnisions of Specification 4.0.3 are applicable to the Containment Leakage Rate Testing Program.

WATERFORD-UNIT 3 6 25 AMENDMENT NO. 494, 138

l NPF-38-220 ATTACHMENTB PROPOSED MARKED-UP SPECIFICATIONS i

l I

1 4

i l

I

E i

ADNINISTRATIVE CONTROLS 5ECTIGN y.A(f 6.11 RADIATION PROTECTION PR0 GRAM...............................

6-22 6.12 HIGH RADIATION AREA........................................

6-22 6.13 PROCESS CONTROL PR0GRAN....................................

6-23 6.14 6FFSITE 00SE CALCULATION MANUAL............................

6-24 6.15 CONTAlg4ENT LEAKAGE RATE TESTING PR0 GRAM...................

6-24 l

~

,w

(,, /[, C o n fo'g u a N oh A h lt M n ~ s p e k e n l S* ? '

  • M...

~

/

I I

i j

I WATERFORD UNIT 3 XVIII Amendment No. 64,124

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8 1 A.C. SOURCES OPERA"ING LIMITENG CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. eltetrical power sources shall be OPERABLE:

i Two physic' ally independent circuits between the offsite transmission a.

network and the onsite Class IE distribution system, and b.

Two separate and independent diesel generators, each with:

1.

Diesel oil feed tanks containing a minimum volume of 339 gallons of fuel, and 2.

A separate diesel generator fuel oil storage tank containing:

a.

A minimum volume of 38,760 gallons of fuel, or j

b.

A fuel oil volume less than 39,760 gallons and greater than 38,000 gallons of feel for a period not to exceed 5 days (provided replacement fuel oil is onsite within the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />), and 3.

A separate fuel transfer pump.

APPLICABILITY: MODES 1, 2, 3, and 4.

1 gnQN:

a.

With one offsite circuit of 3.8.1.la inoperable, demonstrate the OPERA 8ILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.la within I hour and at least once' per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Restore the offsite A.C. circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least H0T STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i l

b.

With one diesel generator of 3.8.1.lb inoperable, demonstrate the OPERABILITY of the offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.la (separately for each offsite A.C. circuit) l within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining OPERA 8LE diesel generator (unless it has been successfully tested in the last 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />) by perfoming Surveillance Requirement i

4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless the absence of any potential commen mode failure for the remaining diesel generator is demonstrated.

Restore ths diesel generator to OPERABLE status within ?? Sure or be in at least HDT STAND 8Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and i OLD SHUTDOWN.

within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

g 4, c.

With one offsite A.C. circuit and one diesel generator of the above required A.C. electrical po er sources inoperable, demonstrate the OPERABILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.la within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and, if the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERA 8ILITY of the remaining 0PERA8LE diesel generator by perfoming Surveillance Requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (unless it is already operating) unless the absence of any potential common mode failure for the remaining diesel generator WATERFORD - UNIT 3 3/4 8-1 AMENOMENT N0. M 26

p 3/4.8 ELECTRICAL POWER SYSTEMS BASES 3/4.8.1. 3/4.8.2. and 3/4.8.3 A.C. SOURCES. D.C SOURCES. and ONSITE POWER DISTRIBUTLON SYSTEMS The OPERABILITY of the A.C. and D.C. power sources an'd associated distribution systems during operation ensures that sufficient power will be available to supply the safety-related equipmer.t required for (1) the safe shutdown of the facility and (2) the mitigation and control of accident conditions within the facility.

The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix A to 10 CFR Part 50.

The Limiting Condition for Operation (LC0) ensures that each diesel generator storage tank contains fuel oil of a sufficient volume to operate each diesel I

generator for a period of 7 days. The minimum required volume is 6ased on the time-dependent loads of the diesel generator following a loss of offsite power and i

a design bases accident and includes the capacity to power the engineered safety features ir conformance with Regulatory Guile 1.137 October 1979., The minimum onsite stored fuel oil is sufficient to operate the diesel generator for a period longer than the time to replenish the onsite supply from the outside sources discussed in FSAR 9.5.4.2.

,l An additional provision is included in the LCO which allow the diesel generators to remain operable when their 7 day fuel oil supply is not available.

This provision is acceptable on the basis that replacement fuel oil is onsite within the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after falling below the 7 day supply.

The ACTION requirements specified for the levels of degradation of the power sources provide restriction upon continued facility operation commensurate with the level of degradation.

The OPERABILITY of the power sources are consistent with the initial condition assumptions of the safety analyses and are based upon maintaining at least one redundant set of onsite A.C. and D.C. Iower sources and associated distribution systems OPERA 8LE during accident conditions coincident

  1. N with an assumed loss-of-offsite power and single failure of the other onsite A.C. I source.

The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.93, " Availability of Electrical Power Sources," December 1974.

When one diesel generator is inoperable, there is an additional ACTION requirement to verify that all required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE, and that the steam-driven auxiliary feedwater pump is OPERABLE. This requirement is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable.

The term verify as used in this context means to administrative 1y check by examining logs or other information to determine if certain componentr are out-of-service for maintenance or other reasons.

It does not mean to perform the Surveillance Requirements needed to demonstrate the OPERABILITY of the component.

The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that (1) tne facility can be maintained in the shutdown or refuel' ng condition for extended time periods and (2) sufficient instrumentation and control capability is available for mmitoring and maintaining the unit status.

WATERFORD - UNIT 3 B 3/4 8-1 AMENDMENT NO. 92

p INSERT 1 -

and Combustion Engineering Owners Group (CEOG) Joint Applications Report for l

Emergency Diesel Generators AOT Extension; report Number CE NPSD-996. A Configuration Risk Management Program (CRMP) defined in Administrative Controls section 6.16 is implemented in the event of entry into ACTION (b).

t

l 1

i CONTAINMENT I PAKAGE RATE TESTING PROGRAM (Continued)

Leakage,sie aose,ianos c,iie,is are:

l a.

Overall containment leakage rate acceptance criteria is s 1.0 L,. During the first unit startup following each test performed in accordance with this program, the overall containment leakage rate acceptance criteria are 5 0.60 L, for the Type B and Type i

C tests and 5 0.75 L, for Type A tests.

i f

b.

Airlock acceptance criteria are:

{

1.

Overall air lock leakage rate is 5 0.05 t., when tested at 1 P,.

2.

Leakage rate for each door seal is 5 0.005 L when pressurtzed to 110 psig.

I c.

Secondary containment bypass leakage rate acceptance criteria is 5 0.06 L, when I

tested at 2 P.

i l

d.

Containment purge valves with resilient seals acceptance criteria is 10.06 ( when tested at 2 P,.

i l

The provisions of Specification 4.0.2 do not apply to the test frequenoes speedied in the Containment Leakage Rate Testing Program.

\\

The provisions of Specification 4.0.3 are applicable to the Containment Leakage Rate Testing Program.

/NSCR T %

WATERFORD-UNif 3 6 2C AMENDMENT NO. 494, 138

f.

INSERT 2 6.16 Configuration Risk Management Program (CRMP)

The Configuration Risk Management Program (CRMP) provides a proceduralized risk-informed assessment to manage the risk associated with equipment inoperability. The program applies to Technical Specification structures, systems, or components for which a risk-informed Completion Time has been granted. The program shallinclude the following elements:

a.

Provisions for the control and implementation of a Level 1 at power internal events PRA-informed methodology. The assessment shall be capable of evaluating the applicable plant configuration.

b.

Provisions for performing an assessment prior to entering the LCO l

Condition for preplanned activities, c.

Provisions for performing an assessment after entering the LCO Condition for unplanned entry into the LCO Condition.

d.

Provisions for assessing the need for additional actions after the discovery of additional equipment out of service conditions while in the LCO Condition.

e.

Provisions for considering other applicable risk significant contributors such as Level 2 issues, and external events, qualitatively or quantitatively.

o i

)

g NPF-38-220 ATTACHMENT C PROPOSED SPECIFICATIONS 1

i i

l

(

INDEX

@MINISTRATIVE CONTROLS SECTION PAGE 6.11 RADIATION PROTECTION PROGRAM.......................

6-22 6.12 HIGH RADIATION AREA............................

6-22 6.13 PROCESS CONTROL PROGRAM.,.....................

6-23 6.14 OFFSITE DOSE CALCULATION MANUAL........

6-24 6.15 CONTAINMENT LEAKAGE RATE TESTING PROGRAM......

6-24

$310NFIGURATION RISK MANAGEMENT PROGRAM (CRMP).......

6-25 4

i

)

i

-l WATERFORD - UNIT 3 XVill -

Amendment No. 66,-+24 4

Y.

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES i

OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a.

Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system, and b.

Two separate and independent diesel generators, each with:

1.

Diesel oil feed tanks containing a minimum volume of 339 gallons of fuel, and 2.

A separate diesel generator fuel oil storage tank containing:

a.

A minimum volume of 38,760 gallons of fuel, or b.

A fuel oil volume less than 38,760 gallons and greater than 38,000 gallons of frel for a period not to exceed 5 days (provided replacement fuel oil is onsite within the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />), and 3.

A separate fuel transfer pump.

APPLICABILITY: MODES 1,2, 3, and 4.

ACTION:

a.

With one offsite circuit of 3.8.1.1a inoperable, demonstrate the OPERABILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.1a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Restore the offsite A.C. circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With one diesel generator of 3.8.1.1b inoperable, demonstrate the OPERABILITY of the offsite A.C. circuits by performing Surveillance j

Requirement 4.8.1.1.1a (separately for each offsite A.C. circuit) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator (unless it has been successfully tested in the last 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />) by performing Surveillance Requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless the absence of any potential common mode failure for the remaining diesel generator is demonstrated.

Restore the diesel generator to OPERABLE status within 10 days or be l

i in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

c.

With one offsite A.C. circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demsnstrate the OPERABILITY of the remaining offsite A.C. circuit by performing Surveillance Requirement 4.8.1.1.1a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and, if the diesel generator became inoperable WATERFORD - UNIT 3 3/4 8-1 AMENDMENT NO. 23,-92,126 i

ELECTRICAL POWER SYSTEMS ACTION (Continued) due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by performing Surveillance Requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (unless it is already operating) unless the absence of any potential common mode failure for the remaining diesel generator is demonstrated. Restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at Icast HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

Restore the other A.C. power source (offsite A.C. circuit or diesel generator) to OPERABLE status in accordance with the provirions of ACTION statement a or b, as appropriate, with the time requirement of that ACTION statement based on the time of initial loss of the remaining inoperable A.C. power source. A successful test of diesel generator OPERABILITY per Surveillance Requirement 4.8.1.1.2a.4 performed under this ACTION statement satisfies the diesel generator test requirement of ACTION statement a or b.

d.

With one diesel generator inoperable, in addition to ACTION b. or c.

above, verify that:

(1)

All required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE, and (2)

When in MODE 1,2, or 3, the steam-drivan emergency feed pump is OPERABLE.

If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

e.

With two of the above required offsite A.C. circuits inoperable, restore one of the inoperable offsite A.C. circuits to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

Following restoration of one offsite A ). circuit, follow ACTION statement a with the time requirement of that ACTION statement based on the time of initial loss of the remaining inoperable offsite A.C.

circuit. A successful test of diesel generator OPERABILITY per Surveillance Requirement 4.8.1.1.2a.4 performed under this ACTION statement satisfies the diesel generator test requirement of ACTION statement a.

f.

With two of the above required diese! generators inoperable, demonstrate the OPERABILITY of two offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.1a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore one of the inonerable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Following restoration of one diesel generator.

follow ACTION statement b with the time requirement of that ACTION statement based on the time of initial loss of the remaining inoperable diesel generator.

WATERFORD - UNIT 3 3/4 8-2 AMENDMENT NO. 23,126

)

1 I

3/4.8 ELFCTRICAL POWER SYSTEMS BASES 3/4.8.1. 3/4.8.2: and 3/4.8.3 A.C. SOURCES. D.C SOURCES. and ONSITE POWER DISTRIBUTION SYSTEMS The OPERABILITY of the A.C. and D.C. power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety-related equipment required for (1) the safe shutdown of the facility and (2) the mitigation and control of accident conditions within the facility. The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix A to 10 CFR Part 50.

The Limiting Condition for Operation (LCO) ensures that each diesel generator storage tank contains fuel oil of a sufficient volume to operate each diesel generator for a period of 7

' days.1 The minimum required volume is based on the time-dependent loads of the diesel generator following a loss of offsite power and a design bases accident and includes the capacity to power the engineered safety features in conformance with Regulatory Guile 1.137 October 1979. The minimum onsite stored fuel oil is sufficient to operate the diesel generator for a period longer than the time to replenish the onsite supply from the outside sources discussed in FSAR 9.5.4.2.

An additional provision is included in the LCO which allow the diesel generators to remain operable when their 7 day fuel oil supply is not available. This provision is acceptable on the basis that replacement fuel oil is onsite within the first 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after falling below the 7 day supply.

The ACTION requirements specified for the levels of degradation of the power sources provide restriction upon continued facility operation commensurate with the level of degradation.

The OPERABILITY of the power sources are consistent with the initial condition assumptions of the safety analyses and are based upon maintaining at least one redundant set of onsite A.C.

and D.C. power sources and associated distribution systems OPERABLE during accident conditions coincident with an assumed loss-of-offsite power and single failure of the other onsite A.C. source. The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.03, " Availability of Electrical Power Sources," December 1974 and Combustion Engineering Owners Group (CEOG) Joint Applications Report for Emergency Diesel Generators

- AOT Extension; report Number CE NPSD-996. A Configuration Risk Management Program

-(CRMP) defined in Administrative Controls section 6.16 is implemented in the event of entry into ACTION (b). When.one diesel generator is inoperable, there is an additional ACTION requirement to verify that all required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE, and that the steam-driven auxiliary feedwater pump is OPERABLE. This requirement is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable. The term verify as used in this context means to administratively check by examining logs or other information to determine if certain components are out-of-service for maintenance or other reasons < It does not mean to perform the Surveillance Requirements needed to demonstrate the OPERABILITY of the component.

' The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that(1) the facility can be maintained in the shutdown or refueling condition for extended time periods and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.

WATERFORD - UNIT 3 8 3/4 8-1 AMENDMENT NO 92

l ADMINISTRATIVE CONTROLS CONTAINMENT LEAKAGE RATE TESTING PROGRAM (Continued)

Leakage rate acceptance cr;teria are:

a.

Overall containment leakage rate acceptance criteria is s 1.0 L,. During the first unit startup following each test performed in accordance with this program, the overall containment leakage rate acceptance criteria ares 0.60 L, for the Type B and Type C tests and s 0.75 L, for Type A tests.

b.

Air lock acceptance criteria are:

1.

Overall air lock leakage rate is s 0.05 L, when tested at 2 P,.

2.

Leakage rate for each do.. malis s 0.005 t, when pressurized toa 10 psig.

c.

Secondary containment bypass leakage rate acceptance criteria is s 0.06 L, when tested at 2 P,.

d.

Containment purge valves with resilient seals acceptance criteria is s 0.06 L, when tested ata P,.

The provisions of Specification 4.0.2 do not apply to the test frequencies specified in the Containment Leakage Rate Testing Program.

The provisions of Specification 4.0.3 are applicable to the Containment Leakage Rate Testing Program.

6.16-CONFIGURATION RISK MANAGEMENT PROGRAM (CRMP)

The Configuration Risk Management Program (CRMP) provides a proceduralized risk-informed assessment to manage the risk associated with equipment inoperability. The program applies to j

technical specification structures, systems, or components for which a risk-informed Completion I

Time has been granted. The program shall include the following e!.?ments:

a.

Provisions for the control and implementation of a Level 1 at power internal events PRA-informed methodology. The assessment shall be capable of evaluating the applicable plant configuration.

l b.

Provisions for performing an assessment prior to entering the LCO Condition for preplanned activities.

I WATERFORD - UNIT 3 6-25 AMENDMENT NO. 124,130, 1

l

.m i

ADMINISTRATIVE CONTROLS I

CONFIGURATION RISK MANAGEMENT PROGRAM (CRMP) (Cont:.dd)

Provisions for performing an assessment after entering the LCO Condition for c.

unplanned entry into the LCO Condition.

d.

Provisions for assessing the need for additional actions after the discovery of additional equipment out of service conditions while in the LCO Cor.dition.

Provisions for considering other applicable risk significant contributors such as e.

Level 2 issues, and external events, qualitatively or quantitatively.

l WATERFORD L.' NIT 3 6-26 AMENDMENT NO.

i 1

\\..

O