ML20207S977

From kanterella
Jump to navigation Jump to search
Rev 1 to McGuire Nuclear Station Unit 2 Electrical Controls Description,Electrical Penetration Circuits - Eza Sys
ML20207S977
Person / Time
Site: McGuire, Mcguire  
Issue date: 04/16/1986
From: Ahedford T, Haynes R, Rankin G
DUKE POWER CO.
To:
Shared Package
ML20207S970 List:
References
MCSD-0020-30.00, MCSD-0020-30.00-R01, MCSD-20-30.00, MCSD-20-30.00-R1, NUDOCS 8703230014
Download: ML20207S977 (65)


Text

MCGUIRE NUCLEAR STATION UNIT 2 ELECTRICAL CONTROLS SYSTEM DESCRIPTION ELECTRICAL PENETRATION CIRCUITS - EZA SYSTEM MCS0-0020-30.00 QA CONDITION 1 THE INFORMATION CONTAINED IN THIS DOCUMENT IS TO BE USED AS A FUNCTIONAL DESCRIPTION ONLY.

IT IS NOT TO BE USED AS AN OPERATING PROCEDURE OR GUIDELINE FOR OPERATION.

W red

$ 9 85 WA

' Control SysCems Engr.

I)ati Power 5fstems Engr.

Date

$OEdi4 %

Y8/Y Af/A Control Sys's Checker Date Power 59s's Checker Date

//Mb3~

Appro By Datt REV. ORIG.

DATE CHK'O BY DATE INSP. BY DATE INSP. BY DATE APP. BY DATE o RAMS SK 9/n/" "th&'

lMJ

  1. ff)%y, t+- 4Na, o&u Mk "shi

9.%)

W/// d / %

1

/

G703230014 870316 DR ADOCK 05000369 PDR

SYSTEM CHANGE / MODIFICATION LIST System design changes / modifications included in this sytem description:

System Description

Change / Modification Change / Modification Revision No.

Authorization Form No.

Implementation Date 0

Original Issue N/A 1

Editorial Rev.

N/A e

O MCSD-0020-30.00

TABLE OF C6NTENTS Section Title Page

1. 0 E11HED.SE 1
2. 0.

GENERAL DESCRIPTION 2

4 3.0 REFERENCE DOCUMENTS 3

~ 3.1 MANUFACTURER'S DRAWINGS 3

3.2 DUKE DRAWINGS 3

m 3.3 PSAR AND/0R FSAR APPLICABLE PARAGRAPHS 5

3.4 CALCULATIONS 5

4.0 DESIGN PARAMETERS 6

5.0 DESIGN CRITERIA 7

5.1 SAFETY CLASS DESIGNATION 7

5.2 APPLICABLE DESIGN STANDARDS AND CODES 7

5.3 REDUNDANCY REQUIREMENTS 7

5.4 SEPARATION REQUIREMENTS 7

5.5 DESIGN SEISMIC LEVEL 8

5.6 DESIGN ENVIRONMENT 8

6.0 SY11EM_0fEfMIl0B 9

6.1 CONTROL 1 9

6.2 POWER SUPPLIES 9

7.0 SYSTEM ALARMS 10 8.0 STATUS INDICATION 11 9.0 INTERFACES WITH OTHER SYSTEMS 12 10.0 LAYOUT ORAWING OF SYSTEM 13 11.0 PROTECTIVE RELAYING 14 12.0 SET POINTS 15 i

MCSD-0020-30.00

i TABLE OF CONTENTS (Cont'd)

Section Title Page 13.0 PRE-OPERATIONAL TEST REOUIREMENTS 16 14.0 PERIODIC TEST REQUIREMENTS 17 15.0 ACCEPTANCE TEST REOUIREMENTS 18 16.~ 0 PERIODIC MAINTENANCE REQUIREMENTS 19 17.0 OUALITY ASSURANCE 20 17.1 QUALITY ASSURANCE CLASS OF EQUIPMENT 20 17.2 REFERENCE QUALITY ASSURANCE FILE NUMBERS 20 k

e I

MCSD-0020-30.00

1.0 PJJHE0jif Electrical penetration assemblies are specially designed devices to allow circuits to enter / exit the containment vessel, while maintaining a pressure barrier between inside and outside containment during normal plant operations and under the postulated design basis loss of coolant accident (LOCA).

e l

MCSD-0020-30.00.

2. 0 GENERAL DESCRIPTION The electrical penetrations are designed to meet all electrical requirements for the specified service environment without dielectric breakdown or damage due to overheating. Typically, an electrical penetration assembly consists of electric conductors, conductor seals, and the mechanical assembly for securing the conductors and and conductor seal assemblies to the containment structure.

A pressure gauge and valve assembly are provided on the outboard end of each penetration assembly to permit periodic monitoring of the penetration gross-leak integrity.

The electrical penetration circuits are designed to perform their various electrical functions inside the reactor containment structure while their associated penetration assembly maintains a testable leak-tight pressure boundary. All electrical penetration assemblies are manufactured to maintain their leak-tight integrity and remain electrically functional during and following the postulated design basis loss of coolant accident.

Electrical penetrations functionally fall into the following service classifi-cations:

1) Type A, medium voltage electrical power penetration assemblies, supply power to reactor coolant pump motors; 2) Type B, C, D, E, F and G, low voltage electrical power and control rod drive, reactor protective systems, and other equipment circuits; and 3) Type H, J, K, M, N and BH, electrical instTu-mentation and control penetration assemblies, form a vital link in circuitry for nuclear instrumentation, control rod position indication, environmental sensing, and communications.

Electric penetration areas through the concrete Reactor Buildings are limited to the segments of the building enclosured between column lines 44-53, DD-BB between elevations 733', 750' and 767' and between column lines 49 and 53, DD-AA between elevation 767' and 786'.

~

Cable trays are routed between the concrete Reactor Building penetrations and Containment vessel electric penetrations in tha annulus.

Containment vessel electric penetrations are located in accessible areas outside the ice condenser.

Approximately eighteen twelve-inch diameter electric penetration assemblies are located in the upper Containment between elevations 769' + 5" and 922' + 5" to provide for electric circuits located in the upper Containment.

These include circuits for equipment such as polar crane, manipulator crane, ice condenser air handling units, ice condenser bridge crane, hydrogen recombiner, air return fans and miscellaneous control, communication, and instrumentation. Approximately forty-five twelve-inch diameter electric penetrations are located in the lower Containment between elevation 748' + 6" and 762' + 9".

These penetrations are grouped in five locations distributed approximately 270 degrees around the Contoenment vessel.

Four thirty-two inch diameter electric penetrations provide power for the reactor coolant pump motors.

The twelve inch diameter electric penetrations provide circuits for all other power control and instru-mentation required in the lower Containment.

All electrical penetrations are located above the maximum expected post-LOCA water level inside Containment.

MCSD-0020-30.00 -

_~

3.0 REFERENCE DOCUMENTS 3.1 MANUFACTURER'S DRAWINGS MCM-1361.00-0007 Low Voltage Electrical Penetration Installation Diagram, Types B, C, D, E, F and G (D. G. O'Brien, Inc.)

MCM-1361.00-0008 Instrument and Control Electrical Penetration Installation Diagram, Types H, J, K, L and M (D. G. O'Brien, Inc.)

MCM-1361.00-0012 Cathodic Protection Electrical Penetration (D. G. O'Brien, Inc.)

MCM-1361.00-0015 Medium Voltage Electrical Penetration Outline and Wiring Diagram, Type A (D. G. O'Brien, Inc.)

MCM-1361.00-49 Instrumentation Electrical Penetration Assembly Layout, Type N and BH (Conax Co.)

MCM-1361.00-60 Packaging,. Shipping and Storage Procedure for Electrical Penetration Assemblies (Conax Co.)

MCM-1361.00-65 Instrument Electrical Penetration Sub-Assembly, Type N -

(ConaxCo.)

MCM-1361.00-69 Instrument Electrical Penetration Sub-Assembly, Type BH (Conax Co.)

Manufacturer's Instruction Manuals MCM-1361.00-0013 D. G. O'Brien, Inc. Instruction Manual No. 1048 (Cathodic Protection)

MCM-1361.00-0016 D. G. O'Brien, Inc. Instruction Manual No. 1050 (Types B, C, D, E, F and G)

MCM-1361.00-0017 D. G. O'Brien, Inc. Instruction Manual No. 1051 (Types H, J, K, L and M)

MCM-1361.00-0018 D. G. O'Brien, Inc. Instruction Manual No. 1052 (Type A)

MCM-1361.00-63 Conax Co. Instruction Manual IPS-1040 (Type N and BH) 3.2 DUKE DRAWINGS General Arrangements MC-2921-03 Electrical Equipment Layout Drawing for Unit 2 Reactor Building Penetration MC-2767-(Series)

Electrical Equipment Connection Diagrams MC-1042-(Series)

Reactor Building Containment Vessel Base Liner Plate, Anchors and Embedded Items MCSD-0020-30.00 _ _.. _

~

MC-1948-(Series)

Electrical Equipment Layout Drawings Procurement Specifications MCS-1361.00-00-0007

" Electrical Penetration Assemblies" Medium Voltage Power (Type A).

MCS-1361.00-00-0002, " Electric Penetration Assemblies" Low Voltage Power and Control (Types B, C, 0, E, F and G).

MCS-1361.00-00-0003, " Electric Penetration Assemblies" Instrumentation and Control (Types H, J, K, L and M).

MCS-1361.00-00-0005, " Electric Penetration Assemblies" (Cathodic Protection).

MCS-1361.00--00-0008 " Electrical Penetration Assemblies" Instrumentation and Control (Types N and BH)

Installation Specifications MCS-1390.01-00-0010, " Cable Grounding Details and Terminations".

MCS-1390.01-00-0099, " Procedure for Corrective Action for Electric Penetrat4ons which have a marginal or possible unacceptable SFs leak rate or pressure (Types A through M)"

MCS-1390.01-00-0046, " Procedure For Installation of Type A (6900 volt) Electric Penetration Assemblies" MCS-1390.01-00-0058, " Electrical Penetration Blinding Pin Verification" MCS-1390.01-00-0097, " Mechanical Installation Procedure for Electric Penetration Types B, C, 0, E, F, G, H, J, K, L and M" MCS-1390.01-00-0100 " Procedure for Termination of Electrical Cable to Electric Penetration Types B, C, D, E, F, G, H, J, K, L and M" MCS-1390.01-00-0098, " Procedure for Performing the Electrical Penetration 0-Ring Seal Leak Rate Test (Types A through M)"

MCS-1390.01-00-0092, " Bolted Cable Connection to Electrical Equipment Rated 13.8 KV and Below".

MCS-1390.01-00-0063, " Procedure for Insulating Splices and Bolted Connections Rated 600 Volts and Below."

MCS-1390.01-00-0106 " Procedure for the Inspection, Repair and Protection of ElectricalPenetratIonMountingFlanges" MCS-1390.01-00-0103, " Class 1E Electrical Crimp Tools and Terminals".

MCS-1390.01-00-0065, " Handling and Control of QA Condition 1 Electrical Material Transfer" MCSD-0020-30.00,

MCS-1390.01-00-0036, "McGuire Electrical Separation Criteria 0C-1.01 and DC-1. 01-1".

MCS-1390.01-00-0107, " Procedure for Receipt, Storage and Maintenance of D. G.

O'Brien, Inc. Electrical Penetration Assemblies (Types A through M)"

3.3 PSAR AN0/0R FSAR APPLICABLE PARAGRAPHS FSAR Section 8.3.1.2.7.7 Penetrations 3.4 CALCULATIONS MCC-1381.05-00-0005 Electrical Penetration Leak Rate Maximum Leakage Estimate i

MCC-1381.05-00-0048 Conax Corp. Report No. IPS-1036 Design Report for Electrical Penetration Assembly MCC-1381.05-00-0063 0-Ring Seal Testable Volume for 12 Inch Electrical Penetration MCC-1381.05-00-0064 0-Ring Seal Testable Volume for 32 Inch Electrical Penetrations MCC-1381.05-00-0071 Torquing for 12 Inch Electrical Penetrations MCC-1381.05-00-0086 32 Inch Electrical Penetration Bolt Torque MCC-1131.00-00-0019 Duke Power Company Miscellaneous Containment Vessel Design and Analysis Calculations (Types A, B, C, 0, E, F, G, H, J, K, L, M, N BH and Cathodic Protection)

L i

l MC50-0020-30.00 -

t 4.0 DESIGN PARAMETERS Refer to Documentation listed in Sections 3.0 and 5.0 for electrical penetration assembly design parameters.

=i f

I

.]

?

o 1

t

'f l

i 4

f L

.i 1

i l

k MCS0-0020-30,00 I a

5.0 DESIGN CRITERIA 5.1 SAFETY CLASS DESIGNATION QA Condition 1, Class 1E, Nuclear Safety Related 5.2 APPLICABLE DESIGN STANDARDS AND CODES Ouke Electrical Division Desian Standards DC-1.01 Separation - McGuire DC-1.01 Standby Shutdown System (SSS)

Separation Criteria - McGuire DC-11.01 Electrical Penetrations 0C-16.02 Design and Installation Criteria for Electrical Penetration Assemblies Manufactured by D. G. O'Brien, Inc. - McGuire Industry Standards ASME Boiler and Pressure Vessel Code,Section III, Subsection NE, " Class MC Components" excluding conductors and insulation - 1971 edition including the Summer 1973 Addenda.

IEEE Standard 317-1972, " Electrical Penetration Assemblies in Containment Structures for N1 clear Power Generating Stations" 10CFR50, Appendix J " Primary Reactor Containment Leakage Testing for Water -

Cooled Power Reactors".

IEEE Standard 242-1975, " Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems.

NRC Regulatory Guides Regulatory Guide 1.63 - Electrical Penetration Assemblies in Containment Structures for Light-Water-Cooled Nuclear Power Plants.

5.3 REOUNDANCY REQUIREMENTS Refer to Section 5.2 of this system description and to FSAR Paragraph 8.3.1.2.7.7

- Penetrations.

5.4 SEPARATION REQUIREMENTS Separation criteria for cables entering the Reactor Building between elevations 733' and 767' are:

Cables associated with Engineered Safety Features Train A functions are located between elevation 750' and 761'.

Cables associated with Engineered Safety Features Train B functions are located between elevation 733' and 750'.

MCS0-0020-30.00 -

.~

1' l

vi a.

Cables associated with reactor protection and Engineered Safet)' Features _

l instrumentation entering the Reactor Buildin p

channels through penetrations elevation 733'g are separated by. routing two L

l and 750' and two cnannels between elevation 750' and 767'.

Horizontal separation between Reactor Building penetrations for redundant channels on each elevation is accomalished by l

routing cables through penetrations at opposite ends of the Penetration Room,

with a minimum horizontal separation of five feet between penetrations.

Cable separation within the penetration rooms conforms to that defined in' items above.

3 Separation criteria for Containment vessel electric penetrations are:

Cables associated with Engineering Safety Features Train A are routed through electric penetrations which contain no Engineered Safety Features Train B i

circuits.

Minimum separation, horizontal and vertical between electric penetrations carrying mutually redundant circuits is five feet.

Cable separation within the annulus between the Containment vessel and the concrete Reactor Building conforms to that defined in items above.

Refer to Section 5.2 of this system description.

5.5 DESIGN SEISMIC LEVEL f

l Refer to the Procurement Specifications listed in Section 3.2.

l 5.6 DESIGN ENVIRONMENT Refer to the Procurement Specifications listed in Section 3.2.

I i

1 h

MC50-0020-30.00 I

c) "

7t P

1 ",

N

- 6.0*

SYSTEM OPERATION

)

Each circuit passing through an electrical penetration assembly must have adequate circuit protection over the full current range (from continuous to the maximum current available) to prevent damage to the electrical penetration assembly.

~ 4 All electrical power, control, and instrumentation penetration circuits which are capable of supplying fault currents greater than the continuous current rating of their applicable penetrations shall be provided with two circuit overload protective devices in series.

This redundant protection is required in order to protect the electrical penetration assembly against sustained overcurrent resulting from faults or equipment overloads in the event that the

/ primary protective device should fail to clear the overcurrent condition.

Those circuits which are incapable of supplying a fault current sufficient to cause a loss of mechanical integrity of the penetration do not require circuit overload protection (e.g., thermocouple and RTD instrumentation, annunciators, transducers, monitor lights, computer, etc.).

Protective device is defined as a single device or combination of devices which provide both overcurrent detection and circuit interruption.

The redundant protective devices, each of which provides the type or types of protection required, are to be located in the circuit between the power sources and the penetration and are to be used in series with each other.

Thus, single failure of a penetration circuit protective device shall not jeopardize the mechanica)1 integrity of the penetration assembly and therefore of the contain-ment structure.

The overlaid c'urrent test value and corresponding breaker trip time for those protective devices are listed in Attachment 1.

The breaker trip times are per Table II, Westinghouse Application Data 29-160A WEA, Page 16, and Square D Breaker Characteristic Curves.

6.1 CONTROLS N/A l

G.2 POWER SUPPLIES N/A i

MCS0-0020-30.00.

N w-w

\\

7. 0 g

N/A S

6 l

1 e

l I

l MCSD-0020-30.00 10-

O 8.0 STATUS INDICATION N/A et O

MCSD-0020-30.00.

O 9.0 INTERFACES WITH OTHER SYSTEMS N/A e

MCSD-0020-30.00 -

10.0 LAYOUT DRAWING 0F SYSTEM MC-1948-Series O

MCSD-0020-30.00 -.

11.0 PROTECTIVE RELAYING N/A O

9 MCSD-0020-30.00 _ _

j 12.0 M

N/A e

e MCS0-0020-30.00 13.0 e,.

Refer to Section 3.2 of this system description.

(

4 s

em 9

e O

9 4

4 5

4 3

j MCS0-0020-30.00 -

4

.w p

r

,,,n,---,

w,n---

w-.

,--ara,-,,,,-,

-an-,n,--n-,,---s

--- -. - -, -. - - -., - -~ ~ -,, -

14.0 PERIODIC TEST REQUIREMENTS Refer to Technical Specifications Section 3/4.8.4.

U k

i i

e J

(

4 I

l d

i t

MCSD-0020-30.00,.

a-,n.n.,_

--,,--,,n.n,,-,--,..-.-_.,-

,,--,.,,..,,-,....,_,__,,wn.

,n-,---,..,_

n.w - -.

.. _. =

15.0 ACCEPTANCE TEST REQUIREMENTS

. Refer to Section 3.2 of this system description ~.

I i

.t i

P MCSD-0020-30.00 !

_. _ _ _,.. _.. _ - ~ -

16.0 PERIODIC MAINTENANCE REOUIREMENTS Refer to Section 3.2 of this system description.

6 J

MCSD-0020-30.00 - - - _. - _ _ - - _

17.0 OVALITY ASSURANCE 17.1 QA CLASS OF EQUIPMENT The electrical penetration assemblies are designated QA Condition 1, and, as such, require that necessary procedures be followed to assure the quality of their design.

17.2 REFERENCE QA FILE NUMBERS Documents concerning electrical penetration assemblies are filed under MC-1361.00.

RWH/CMM EL42109N e

9 MCSD-0020-30.00 -

N ATTACHMENT 1 l

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES a

l 4

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME i

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 1.

6900 VAC-SWGR Primary Bkr-RCP2A 5.0 15.4 @ 25A Reactor Coolant Pump 2A Backup Bkr - 2TA-5 5.0 16.5 @ 20A Primary Bkr-RCP2B 5.0 15.4 @ 25A Reactor Coolant Pump 2B Backup Bkr-2TB-5 5.0 16.5 9 20A I

Primary Bkr-RCP2C 5.0 15.4 9 25A Reactor Coolant Pump 2C Backup Bkr-2TC-5 5.0 16.5 @ 20A i

Primary Bkr-RCP2D 5.0 15.4 0 25A Reactor Coolant Pump 2D Backup Bkr-2TD-5 5.0 16.5 0 20A 4

2.

600 VAC-MCC l

2EMXA-2 1D Primary Bkr 20 45 @ 60A -

NC Pump 2C Thermal Barrier i

Backup Fuse 20 N.A.

Outlet Auto Isol Viv 1KC345A 2EMXA-2 1E Primary Bkr 20 45 @ 60A NC Pump 2A Thermal Barrier i

Backup Fuse 20 N.A.

Outlet Auto Isol Viv IKC394A 2EMXA-2 2A j

Primary Bkr 20 45 0 60A Cont Air Return Fan 2A Damper Backup Fuse 20 N.A.

2RAF-D-2 i

e I

l EL42109N I

=

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED s

2.

600 VAC-MCC (Continued) 2EMXA-2 28 Primary Bkr 20 45 0 60A N2 to Prt cont Isol Inside Backup Fuse 20 N.A.

V1v 2NC54A

)

2EMXA-2 2C Primary Bkr 20 45 @ 60A RCP Mtg Brg Oil Fill Isol Backup Fuse 20 N.A.

V1v 2NC196A 2EMXA-2 3A i

Primary Bkr 30 45 0 90A Accumulator 2A Disch Isol Backup Fer#

30 N.A.

Vlv 2NI54A 2EMXA-2 3B Primary Bkr 30 45 @ 90A Accumulator 2C Disch Isol Backup Fuse 30 N.A.

Viv 2NI76A 2EMXA-2 3C Primary Bkr~

20 45 @ 60A Test Hdr Inside Cont Isol t

Backup Fuse 20 N.A.

Vlv 2NI95A 2EMXA-2 4A Primary Bkr 20 45 @ 60A UHI Check V1v Test Line Isol Backup Fuse 20 N.A.

V1v 2NI266A i,

l EL42109N t

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-2 4B i

Primary Bkr 20 45 0 60A UHI Check Viv Test Line Isol Backup Fuse 20 N.A.

Vlv 2NI267A 2EMXA-2 4C Primary Bkr 20 45 0 60A Accum 2A Vent to 2NC34 for Backup Fuse 20 N.A.

B1kout Vlv 2NI430A 2EMXA-5 IB Primary Bkr 20 45 @ 60A Pzr Liquid Sample Line Inside i

Back Fuse 20 N.A.

Cont Isol Viv 2NM3A,C l

2EMXA-5 2C Primary Bkr 20 45 @ 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol V1v 2NM6A,C 2EMXA-5 3B Primary Bkr 20 45 @ 60A NC Hotleg 2A Sample Line Cont Backup Fuse 20 N.A.

Isol Viv 2NH22A,C 2EMXA-5 2D Primary Bkr 20 45 @ 60A NC Hotleg 2D Sample Line Cont Backup Fuse 20 N.A.

Isol V1v 2NM25A,C 2EHXA-2 7A Primary Bkr 20 45 @ 60A SG 2A Upper Shell Sample Cont Backup Fuse 20 N.A.

Isol V1v 2NM187A.

i EL42109N s.

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE, CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) i 2EMXA-2 78 Primary Bkr 20 45 @ 60A SG 2A Blowdown Line Sample l

Backup Fuse 20 N.A.

Cont Isol Viv 2NM190A 2EMXA-2 7C Primary Bkr 20 45 @ 60A SG 2C Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM207A 2EMXA-2 8A Primary Bkr 20 45 0 60A SG 2C Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM210A 2EMXA-4 IB Primary Bkr 20 45 @ 60A NC Pump Seal Return Cont Backup Fuse 20 N.A.

Isol. Vlv 2NV94A,C 2EMXA-3 3A Primary Bkr 20 45 @ 60A H2 Purge Exhaust Cont Vessel Backup Fuse 20 N.A.

Isol Viv 2VESA

~

2EMXA-3 3B Primary Bkr 20 45 0 60A Cont. H2 Purge Blower Inlet Backup Fuse 20 N.A.

Viv 2VE8A 2EMXA-3 3C l

Primary Bkr 20 45 @ 60A H2 Purge Inlet Cont Vessel Backup Fuse 20 N.A.

Isol V1v 2VE10A EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECON05)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-3 4A Primary Bkr 20 45 0 60A H2 Skimmer Fan 2A Suction Backup Fuse 20 N.A.

Isol Vlv 2VX1A 2EMXA-3 5B Primary Bkr 20 45 @ 60A RCDT Pump Disch Cont Isol Backup Fuse 20 N.A.

V1v 2WL2A 2EMXA-3 SC Primary Bkr 20 45 @ 60A RCDT Vent Cont Isol Vlv Backup Fuse 20 N.A.

2WL39A i

2EMXA-3 6A l

Primary Bkr 20 45 @ 60A RB Sump Pump Disch Cont Isol Backup Fuse 20 N.A.

Vlv 2WL64A j

2EMXA-3 6B l

Primary Bkr 20 45 @ 60A Cont Vent Unit Condensate Backup Fuse 20 N.A.

Cont Isol Viv 2WL321A 2EMXB-4 IB Primary Bkr 20 45 @ 60A NC Pump 28 Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 2KC3648 2EMXB-4 1C l

Primary Bkr 20 45 @ 60A NC Pump 2D Thermal Barrier Backup Fuse 20 N.A.

Auto Isol V1v 2KC4138 i

l EL42109N

1 ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

t CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

2.

600 VAC-MCC (Continued) j 2EMXB-4 2A Primary Bkr 20 45 @ 60A NC Pumps Return'Ndr Pent Inside Isol Backup Fuse 20 N.A.

Vlv 2KC424B 2EMXB-4 2B Primary Bkr 20 45 @ 60A Reactor Bldg Drn Hdr Inside Cont j

Backup Fuse 20 N.A.

Isol Vlv 2KC4298 i

2EMXB-4 2C Primary Bkr 30 45 @ 90A Accumulator 28 Disch Isol Vlv Backup Fuse 30 N.A.

2NI65B j

2EMXB-4 3D Primary Bkr 30 45 9 90A Accumulator 20 Disch Isol V1v.

Backup Fuse 30 N.A.

2 NIB 88 2EMXB-4 3E Primary Bkr 20 45 @ 60A Hotleg.Inj Check 2NI124, 2NI128 Backup Fuse 20 N.A.

Test Isol Viv 2NI122B I

2EMXB-4 4A Primary Bkr 20 45 0 60A Cont Air ' Return Fan 28 Damper j

Backup Fuse 20 N.A.

2RAF-D-4 2EMXB-4 4C l

Primary Bkr 20 45 0 60A NI Accum 2A Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv 2NM728 l

EL42109N i

j i

4 L

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME l

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 4

j 2.

600 VAC-MCC (Continued) i l

2EMXB-4 SA j

Primary Bkr 20 45 @ 60A NI Accus 28 Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Viv 2NM75B i

2EMXB-4 SB l

Primary Bkr 20 45 @ 60A NI Accum 2C Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv 2NM78B 2EMXB-4 SC Primary Bkr 20 45 @ 60A Accum 2B Vent to 2NC32 for Backup Fuse 20 N.A.

Bikout Viv 2NI4318-i 2EMXB-4 6A i

Primary Bkr 20 45 @ 60 NI Accus 2D Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv 2NM81B 2EMXB-4 68 Primary Bkr 20 45 @ 60A SG 2B Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 2NM197B 2EMXB-4 6C Primary Bkr 20 45 @ 60A SG 2B Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol V1v 2NM2008 2EMXB-4 78 Primary Bkr 20 45 0 60A SG 2D Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM2178 EL42109N

]

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVICES i

I TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXB-4 7C Primary Bkr 20 45 @ 60A SG 2D Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM2208 i

2EMXB-5 1A Primary Bkr 20 45 0 60A H2 Purge Exhaust Cont Vessel Backup Fuse 20 N.A.

Isol V1v'2VE6B-2EMXB-5 1C Primary Bkr 20 45 @ 60A H2 Skimmer Fan 28 Suction-Backup Fuse 20 N.A.

Isol Vlv 2VX2B 2EMXC-1A l

Primary Bkr 200 250 @ 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 2A i

2EMXC-2A Primary Bkr 200 250 0 600A Lower Containment Cooling-Backup Fuse 200 N.A.

Unit No. 2C 2EMXC-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent fan j

Backup Fuse 100 N.A.

No. 2A 2EMXC-30 1

Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2C EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXC-4C Primary Bkr 90 110 @ 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 2A 2EMXC-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. 2A 2EMXC-6A Primary Bkr 40 45 @ 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-2A 2EMXC-6B Primary Bkr 30 45 @ 90A Upper Containment' Air Backup Fuse 30 N.A.

Handling Unit 2A 2EMXC-6C Primary Bkr 30 45 0 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit 2C 2EMXC-60 Primary Bkr 90 110 9 270A Hydrogen Skimmer Fan Backup Fuse 90 N.A.

No. 2A 2EMXC-7A Primary Bkr 30 45 @ 90A Pzr Compt. Fan A Backup Fuse 30 N.A.

2MVLSF0038 EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXC-7C Primary Bkr 20 45 @ 60A Upper Cont Return. Air Fan Backup Fu e 20 N.A.

No. 2C 2EMXC-70 Primary Bkr 20 45 @ 60A Pzr Pwr Oper Relief Backup Fuse 20 N.A.

Isol Viv 2NC33A i

2EMXC-8C i

Primary Bkr 20 45 @ 60A Incore Instrumentation Rm Backup Fuse 20 N.A.

Air Hdlg Unit 2A 2EMXC-78 Primary Bkr 20 45 @ 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan No. 2A 2EMXA-4 3C Primary Bkr 30 45 0 90A NC Loop 2C Discharge to ND Backup Fuse 30 N.A.

System Cont Isol Vlv 2N02A,C 2EMX0-1A Primary Bkr 200 250 @ 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 28 2EMXD-2A I

Primary Bkr 200 250 0 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 20 EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

l i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-3B Primary Bkr 40 45 0 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-28 2EMXD-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2B 2EMXD-30 Primary Bkr 100 110 0 300A Control Rod Drive Vent. Fan Backup Fuse 100 N.A.

No.'20 2EMXD-4C Primary Bkr 90 110 0 270A Containment Air Return Fan Backup Fuse 20 N.A.

No. 2B 2EMXD-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner No. 28 Backup Fuse 90 N.A.

2EMXD-6C Primary Bkr 30 45 @ 90A Upper Containment Air Hdlg Unit Backup Fuse 30 N.A.

No. 28 2EMXD-60 Primary Bkr 30 45 @ 98A Upper Containment Air Hd1g Unit Backup Fuse 30 N.A.

No. 2D I,

EL42109N

4 ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PEhETRATION CONDUCTOR OVERCURRENT-PROTECTIVE DEVICES 1

i TRIP StIPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) i j

2EMXD-6E Primary Bkr 90 110 @ 270A Hydrogen Skimmer Fan No. 2B Backup Fuse 90 N.A.

i 2EMXD-78 i

Primary Bkr 20 45 0 60A Upper Cont Return Air Fan i

Backup Fuse 20 N.A.

No. 2D i

2EMXD-7C Primary Bkr 20 45 @ 60A Pzr Pwr Oper Safety Backup Fuse 20 N.A.

Relief Isol Vlv 2NC318 l

1 2EMXD-70 J

Primary Bkr 20 45 @ 60A Pzr Pwr Oper j

Backup Fuse 20 N.A.

Relief Isol Vlv 2NC35B 2EMXD 8A Primary Bkr 30 45 @ 90A Pzr Compt Fan B Backup Fuse 30 N.A.

2MVLSF0039 i

2EMXD-8B Primary Bkr 20 45 @ 60A Incore Instrumentation Rm Backup Fuse 20 N.A.

Air Hdig Unit 28 2EMXD-5C Primary Bkr 20 45 @ 90A Upper Containment Return Air l

Backup Fuse 20 N.A.

Fan 2B i

EL42109N

i ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SLIP 0 INT OR RESPONSE-CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-80 Primary Bkr 30 45 @ 90A NC Loop 2C Disch to NO System Backup Fuse 30 N.A.

Cont Isol Viv 2ND1B 2MXM-F2A Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR14 Backup Fuse 40 N.A.

2MXM-F2B Primary Bkr 40 45 0 120A Lighting Pn1bd 2LR15 Backup Fuse 40 N. A.

2MXM-F2C Primary Bkr 30 45 0 90A Pzr Compt Fan B Alt FDR Backup Fuse 30 N.A.

2MVLSF0039 2MXM-F2D Primary Bkr 20 45 0 60A Ice Cond AHU 2A1 Blower A Backup Fuse 20 N.A.

2MXM-F2E Primary Bkr 20 45 @ 60A Ice Cond AHU 2A2 Blower A Backup Fuse 20 N.A.

2MXM-F3A Primary Bkr 40 45 0 120A Lighting Pnlbd 2LR16 Backup Fuse 40 N.A.

EL42109N a

Y t

ATTACHMENT 1 (Continued) i UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES-

'l

\\

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECON05)

SYSTEM POWERED f

2.

600 VAC-MCC (Continued) 2MXM-F3B Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR17 Backup Fuse 40 N.A.

2MXM-F3C Primary Bkr 25 45 0 75A Reactor Bldg Equip Hdig 5 Ton Backup Fuse 25 N.A.

Jib Crane 2MXM-F3D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A3 Blower A Backup Fuse 20 N.A.

2MXM-F3E Primary Bkr 20 45 @ 60A Ice Cond AHU 2A4 Blower A Backup Fuse 20 N.A.

2MXM-F4A Primary Bkr 20 45 0 60A Ice Cond AHU 2A5 Blower A Backup Fuse 20 N.A.

2MXM-F48 Primary Bkr 20 45 @ 60A Ice Cond AHU 2A6 Blower A Backup Fuse 20 N.A.

2MXM-F4C Primary Bkr 20 45 0 60A Incore Inst Room Sump Pump Backup Fuse 20 N.A.

No. 2 EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM-F40 Primary Bkr 100 110 0 300A Upper Cont Welding Recpt Backup Fuse 100 N.A.

2MXM-FSA Primary Bkr 20 45 @ 60A Ice Cond AHU 2A7 Blower A Backup Fuse 20 N.A.

2MXM-F5B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A8 Blower A j

Backup Fuse 20 N.A.

I 2MXM-FIC Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Heater 2A 2MXM-F8C Primary Bkr 60 110 @ 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 2A 2MXM-F6A Primary Bkr 20 45 0 60A Ice Cond AHU 2A9 Blower A d

Backup Fuse 20 N.A.

2MXM-F6B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A10 Blower A Backup Fuse 20 N.A.

EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCHRRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM-F6C Primary Bkr 30 45 @ 90A Lower Cont Aux Charcoal Filter Backup Fuse 30 N.A. _

Fan 2A 2MXM-F7A Primary Bkr 20 45 @ 60A Ice Cond AHU 2All Blower A Backup Fuse 20 N.A.

2MXM-F78 Primary Bkr 20 45 @ 60A Ice Cond AHU 2A12 Blower A Backup Fuse 20 N.A.

2MXM-F7C Primary Bkr 20 45 @ 60A-Ice Cond AHU 2A13 Blower A Backup Fuse 20 N.A.

2MXM-RIA Primary Bkr 20 45 9 60A Ice Cond AHU 281 Blower A Backup Fuse 20 N.A.

2MXM-RIB Primary Bkr 20 45 @ 60A Ice Ccnd AHU.282 Blower A Backup Fuse 20 N.A.

2MXM-RIC Primary Bkr 20 45 @ 60A Ice Cond AHU 283 Blower Aj,

.;;(

Backup Fuse

- 20 N.A.

a-EL42109N 1

O

, -i q.

2 ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM-RID i

Primary Bkr 30 45 @ 90A RCP 2A Oil Lift Pump No. 1 Backup Fuse 30 N.A.

I 2MXM-R2A Primary Bkr 40 45 @ 120A-Lighting Pnlbd 2LR12 1

Backup Fuse 40 N.A.

1 2MXM-R2D Primary Bkr 20 45 @ 60A Ice Cond AHU 284 Blower A l

Backup Fuse 20 N.A.

2MXM-R2E i

Primary Bkr 30 45 @ 90A RCP 2B Oil Lift Pump No.-1 Backup Fuse 30 N.A.

2MXM-R30 Primary Bkr 20 45 @ 60A Ice Cond AHU 285 Blower A l

Backup Fuse 20 N.A.

2MXM-R3E Primary Bkr 20 45 @ 60A Ice Cond AHU 786 Blower A Backup Fuse 20 N.A.

2MXM-R3F i

Primary Bkr 30 45 @ 90A RCP 2C Oil Lift Pump No. 1 Backup Fuse 30 N.A.

't EL42109N

ATTACHMENT.1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT.' RATING TIME DEVICE NUMBER u LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED-2.

600 VAC-MCC (Continued)-

2MXM-R4D Primary Bkr 20 45 9 60A Ice Cond AHU 287 Blower A Backup Fuse 20 N.A.

- I 2MXM-R4E Ice Cond AHU 288 Blower A Primary Bkr 20 45 0 60A Backup Fuse 20 N.A.

2MXM-R4F Primary Bkr 30 45 @ 90A RCP 20 Oil Lift Pump No. 1 Backup Fuse 30 N.A.

2MXM-R5B Primary Bkr 20 45 @ 60A Ice Cond AHU 289 Blower A.

Backup Fuse 20 N.A.

2MXM-RSC Primary Bkr 20 45 @ 60A Ice Cond AHU'2810 Blower A Backup Fuse 20 N.A.

2MXM-R50 Primary Bkr 175 200'@ 525A Ice Cond Equip Pwr Pnibd 28 Backup Fuse

.175 N.A.

2MXM-R6A Primary Dkr 20 45 0 68A Rod Cntrl Cluster Change Backup Fuse 20 N.A.

Fixture Hoist Drive EL42109N

ATTACHMENT 1 (Continued)

UNIT'2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM-R68 Primary Bkr 20 45 @ 60A Ice Cond AHU 2811 Blower A Backup Fuse 20 N.A.

2MXM-R7A Primary Bkr 20 45 0 60A Stud Tensioner Hoist No. 2 Backup Fuse 20 N.A.

2MXM-R60 Primary Bkr 150 110 0 450A 175 Ton Polar Crane Backup Fuse 150 N.A.

2MXM-R78 Primary Bkr 20 45 @ 60A Incore Inst Drive 2A Backup Fuse 20 N.A.

2MXM-R7C Primary Bkr 30 45 0 90A S/G Compt 20 Fan Backup Fuse 30 N.A.

2MVLS0037 2MXM-R70 Primary Bkr 20 45 @ 60A Ice Cond AHU 2B12 Blower A Backup Fuse 20 N.A.

2MXM-R7E Primary Bkr 20_

45 @ 60A Ice'Cond AHU 2813 Blower A Backup Fuse 20 N.A.

EL42109N

4 ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 600 VAC-MCC (Continued) 2.

i I

2MXM-R8A Primary Bkr 20 45 @ 60A Incore Inst Drive 2B Backup Fuse 20 N.A.

2MXM-R8B Primary Bkr 20 45 @ 60A Incore Inst Drive 2C Backup Fuse 20 N.A.

2MXM-R8C Primary Bkr 30 45 0 90A S/G Compt 2A Fan Backup Fuse 30 N.A.

2MVLSF0036 2MXM-R8D Primary Bkr 20 45 @ 60A Ice Cond AHU 2814 Blower A Backup Fuse 20 N.A.

2MXM-R8E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B15 Blower A Backup Fuse 20 N.A.

2MXHA-ID Primary Bkr 20 45 0 60A Ice Cond AHU 2A14 Blower A Backup Fuse 20 N.A.

2MXMA-1E Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2A1 EL42109N

c

'9 1

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM-R2C Primary Bkr 20 45 @ 60A RCPM Maintenance Crane Recpt-Backup Fuse 20 N.A.

-2A, 28, 2C, & 2D 2MXMA-2B Primary Bkr 25 45 0 75A Lighting Pnibd 2LR6 i

Backup Fuse 25 N.A.

J 2MXMA-2C 1

Primary Bkr 40 45 @ 120A Lighting Pn1bd 2LR18 Backup Fuse 40 N.A.

I 2MXMA-20 Primary Bkr 20 45 0 60A Ice Cond AHU 2A15 Blower A Backup Fuse 20 N.A.

2MXMA-3A Primary Bkr 25 45.@ 75A Lighting Palbd 2LR9 Backup Fuse 25

.N.A.

I 2MXMA-3B j

Primary Bkr 20 45 0 60A Ice Cond Equip Access j

Backup Fuse 20 N.A.

Door 2A 2MXMA-3C Primary Bkr 50 110 9 8150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 2A~

EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

, RESPONSE CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXMA-3D Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 2B Backup Fuse 20 N.A.

Pump 281 2MXN-F2A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A1 Blower B Backup Fuse 20 N.A.

2MXN-F2B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A2 Blever B l

Backup Fuse 20 N.A.

2MXN-F2C Primary Bkr 20 45 0 60A Ice Cond AHU 2A3 Blower B Backup Fuse 20 N.A.

1 2MXN-F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A4 Blower B Backup Fuse 20 N.A.

i 2MXN-F3A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A5 Blower 8 Backup Fuse 20 N.A.

2MXN-F3B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A6 Blower B.

Backup Fuse 20 N.A.

1 EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES

i TRIP SETPOINT OR

RESPONSE

i CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED' 1

2.

600 VAC-MCC (Continued) i 2MXN-F3C Primary Bkr 20 45 @ 60A.

Ice Cond AHU 2A7 Blower B Backup Fuse 20 N.A.

2MXN-F3D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A8 Blower B Backup Fuse 20 N.A.

i 2MXN-F4A Primary Bkr 25 45 0 75A Lighting Pnibd 2LR1

}

Backup Fuse 25 N.A.

i l

2HXN-F48 Primary Bkr 30 15 @ 90A S/G Compt 2C Fan i

Backup Fuse 30 N.A.

2MVLSF0034 l

2MXN-F4C l

Primary Bkr 25 45 0 75A Lighting Pnlbd 2LR2 i

Backup Fuse 25 N.A.

1 2MXN-F4D l

Primary Bkr 20 45 0 60A Ice Cond AHU 2A9 Blower 8-

]

Backup Fuse

.20 N.A.

2MXN-F4E

{

Primary Bkr 20 45 0 68A Ice Cond AHU 2A10 Blower.B-Backup Fuse 20 N.A.

i EL42109N

V W

j ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRA~IION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 1

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 1

2.

600 VAC-MCC (Continued) 2MXN-FSA Primary Bkr 20 45 @ 60A Incore Inst Drive No. 20 Backup Fuse 20 N.A.

I 2MXN-FSB Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2E Backup Fuse 20 N.A.

2MXN-FSC Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2F Backup Fuse 20 N.A.

i 2MXN-F50 Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2A2 2MXN-FIC Primary Bkr 60 110 @ 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 28 2MXN-F8B j

Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 28 l

Backup Fuse 20 N.A.

Pump 2B2 2MXN-F8C Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling t

Backup Fuse 50 N.A.

Defrost Htr 2B

]

EL42109N j

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 4 2HXN-F6A Primary Bkr 25 45 0 75A Lighting Pnibd 2LR4 Backup Fuse 25 N.A.

2MXN-F6B i

Primary Bkr 25 45 @ 75A Lighting Pnibd 2LR5 Backup Fuse 25 N.A.

2MXN-F6C Primary Bkr 20 45 0 60A Fuel Transfer Sys Reactor Backup Fuse 20 N.A.

Side Fdr 2MXN-F6D Primary Bkr 20 45 0 60A Ice Cond AHU 2A11 Blower B Backup Fuse 20 N.A.

2MXN-F7A Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR19 Backup Fuse 40 N.A.

2MXN-F7B i

Primary Bkr 30 45 0 90A Pzr Compt Fan A Alt FDR Backup Fuse 30 N.A.

2MVLSF0038 2MXN-F7C Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR20 Backup Fuse 40 N.A.

EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

l CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED i

2.

600 VAC-MCC (Continued) 2MXN-F70 j

Primary Bkr 20 45 @ 60A Ice Cond AHU 2A12 Blower B l

Backup Fuse 20 N.A.

2MXN-F7E Primary Bkr 20 45 @ 60A Ice Cond AHU 2A13 Blower B Backup Fuse 20 N.A.

1 2MXN-RID Primary Bkr 20 45 0 60A Ice Cond AHU 2B1 Blower B Backup Fuse 20 N.A.

2MXN-RIE Primary Bkr 20 45 @ 60A Ice Cond AHU 2B2 Blower B Backup Fuse 20 N.A.

2MXN-R1F Primary Bkr 30 45 @ 90A RCP 2A Oil Lift Pump No. 2 Backup Fuse 30 N.A.

2MXN-R2C Primary Bkr 30 45 @ 90A Reactor Cavity Manipulator Backup Fuse 30 N.A.

Crane 2MXN-R2F Primary Bkr 30 45 0 9QA RCP 28 Oil Lift Pump No. 2 Backup Fuse 30 N.A.

I EL42109N 4

I

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES l

i l

TRIP SETPOINT OR

RESPONSE

i CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-R3A Primary Bkr 20 45 @ 60A Ice.Cond AHU 283 Blower.B-Backup Fuse 20 N.A.

2MXN-R3B l

Primary Bkr 20 45 @ 60A Ice Cond AHU 284 Blower B l

Backup Fuse 20 N.A.

2MXN-R3C I

Primary Bkr 20 45 @ 60A Ice Cond AHU 285 Blower.B j

Backup Fuse 20 N.A.

I i

2MXN-R3D Primary Bkr 30' 45 @ 90A RCP 2C Oil Lift Pump No. 2-Backup Fuse 30 N.A.

j 2MXN-R4A l

Primary Bkr 50 110 @ 150A Ice Cond Bridge Crane j

Backup Fuse 50 N.A.

2MXN-R4B Primary Bkr 30 45 @ 90A RB Equip Hatch Holst No. 2 Backup Fuse 30 N.A.

1 1

2MXN-R4C l

Primary Bkr 30 45 @ 90A S/G Compt 28 Fan Backup Fuse 30 N.A.

2MVLSF0035 i

EL42109N i

E ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING

. TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERE0 2.

600 VAC-MCC'(Continued) 2MXN-R4D Primary Bkr 20 45 @ 60A Ice Cond AHU 286 Blower B Backup Fuse 20 N.A.

l 2MXN-R4E Primary Bkr 30 45 @ 90A RCP 20 Oil Lift Pump No. 2 Backup Fuse 30 N.A.

2MXN-R50 Primary Bkr 175 200 0 525A Ice Cond Equip Pwr Pnlbd 2A Backup Fuse 175 N.A.

e 2HXN-R6A i

Primary Bkr 20 45 0 60A Ice Cond AHU 287 Blower B

]

Backup Fuse 20 N.A.

2MXN-R6B Primary Bkr 20 45 @ 60A Ice Cond AHU 288 Blower B Backup Fuse 20 N.A.

2MXN-R6C Primary Bkr 20 45 @ 60A Ice Cond AHU 289 Blower B Backup Fuse 20 N.A.

2MXN-R6D Primary Bkr 100 110 @ 300A Welding Fdr Backup Fuse 100 N.A.

EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

)

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME l

DEVICE NUMBER & LOCATION (AMPERES)

-(SECONOS)

SYSTEM POWERED i

2.

600 VAC-MCC (Continued) 2MXN-R7A j

Primary Bkr 20 45 @ 60A Ice Cond AHU 2810 Blower B l

Backup Fuse 20 N.A.

1 2MXN-R78 Primary Bkr 20 45 @ 60A Ice Cond AHU 2B11 Blower B-t Backup Fuse 20 N.A.

2MXN-R7C Primary Bkr 20 45 @ 60A Ice Cond AHU 2B12 Blower B Backup Fuse 20 N.A.

2MXN-R70 l

Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling

]

Backup Fuse 50 N.A.

Pump 2B l

2MXN-R80 i

Primary Bkr 20 45 0 60A Ice Cond AHU 2B13 Blower B l

Backup Fuse 20 N.A.

2MXN-R8E Primary Bkr 20 45 0 60A Ice Cond AHU 2B14 Blower B Backup Fuse 20 N.A.

l 2MXN-R8F i

Primary Bkr 20 45 @ 68A Ice Cond AHU 2B15 Blower B i

Backup Fuse 20 N.A.

EL42109N

(

e j

ATTACHMENT 1 (Continued) l UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

i TRIP SETPOINT OR

RESPONSE

1 CONT. RATING TIME l

DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED l

2.

600 VAC-MCC (Continued) i 2MXNA-1B i

Primary Bkr 40 45 0 120A Lighting Pnlbd 2LR10 Backup Fuse 40 N.A.

l SMXG-R3G Primary Bkr 20 45 9 60A Standby Makeup Pump to Backup Fuse 20 N.A.

Cont Sump Isol Viv 2NV1012C 2MXNA-1C Primary Bkr 40 45 9 120 A Lighting.Pnlbd 2LR11 Backup Fuse 40 N.A.

q 2MXNA-1E

]

Primary Bkr 30 45 @ 90A Lower Cont Aux Charcoal j

Backup Fuse 30 N.A.

Filter Fan 2B l

2MXNA-2B i

Primary Bkr 25 45 0 75A Lighting Pn1bd 2LR7 j

Backup Fuse 25 N.A.

2MXNA-2C Primary Bkr 25 45 9 75A Lighting Pnibd 2LR8 Backup Fuse 25 N.A.

i 2MXNA-20 Primary Bkr 20 45 9 60A Ice Cond AHU 2A14 Blower B Backup Fuse 20 N.A.

i EL42109N i

,i

)

m l

ATTACHMENT 1 (Continued) i j

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

}

3 TRIP SEIPOINT OR

RESPONSE

I CONT. RATING TIME i

DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSIEN POWERED 1

i 2.

600 VAC-MCC (Continued) j 2MXNA-2E l

Primary Bkr 20 45 @ 60A Ice Cond AHU 2A15 Blower B Backup Fuse 20

.N.A.

2MXNA-3A 1

Primary Bkr 20 45 @ 60A 2 Ton CROM Hdig Jib Crane

]

Backup Fuse 20 N.A.

2MXNA-3B Primary Bkr 30 45 0 90A

. Containment Air Compressor Backup Fuse 30 N.A.

SMXG R4F j

Primary Bkr 20 45 @ 60A Standby Makeup Pump to NC-Backup Fuse 20 N.A.

Pump Seals Isol Valve 2NV1013C 2MXNA-3C i

Primary Bkr 20 45 @ 60A NC Pump Motor Drain Tank i

Backup Fuse 20 N.A.

Pump No. 2 I

2MXNA-30 i

Primary Bkr 20 45 @ 60A Ice Cond Equip Access Door 28 Backup Fuse 20 N.A.

1 1

SMXD-3E i

Primary Bkr 15 45 9 46A Unit 2 Personnel Lock

)

Backup Fuse 15 H.A.

EL42109N

d ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES t

l l

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECON05)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

SMXV-2F Primary Bkr 15 45 0 45A Unit 2 Emergency Personnel Lock Backup Fuse 15 N.A.

I 2VLB-2A Primary Bkr 200 250 @ 600A Alt. Source VL Backup Fuse 200 N.A.

Unit 2A 2VLB-28 1

Primary Bkr 200 250 0 600A Alt. Source VL l

Backup Fuse 200 N.A.

Unit 28 2VLB-2C j

Primary Bkr 200 250 0 600A Alt. Source VL Backup Fuse 200 N.A.

Unit 2C 4

2VLB-20 4

l Primary Bkr 200 250 9 600A Alt. Source VL i

Backup Fuse 200 N.A.

Unit 20 i

2VRB-2A l

Primary Bkr 100 110 @ 300A Alt. Source VR j

Backup Fuse 100 N.A.

Unit 2A 2VRB-28 j

Primary Bkr 100 110 @ 300A Alt. Source VR j

Backup Fuse 100 N.A.

Unit 2B EL42109N

ATTACHNENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2VRB-2C Primary Bkr 100 110 0 300A Alt. Source VR Backup Fuse 100 N.A.

Unit 2C 2VRB-20 Primary Bkr 100 110 0 300A Alt. Source VR Backup Fuse 100 N.A.

Unit 2D 2VTB-2A Primary Bkr 20 45 0 60A Alt. Source VT Backup Fuse 20 N/A Unit 2A 2VTB-28 Primary Bkr 20 45 0 60A Alt. Source VT Backup Fuse 20 N.A.

Unit 2B 3.

600 VAC-Press Htr Pwr Pnls Backup Press Htr Pwr Pal 2A-1A Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

1, 2, & 22 Backup Press Htr Pwr Pal 2A-18 Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

5, 6, & 27 EL42109N

ATTACHNENT 1 (Continued)

UNIT 2 CONTAIMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SE1 POINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2A-1C Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90

.N.A.

9, 10, & 32 Backup Press Htr Pwr Pnl 2A-2C Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

11,.12, & 35-Backup Press Htr Pwr Pn1 2A-2D Primary Bkr 90

.110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

13, 14, & 37 l

Backup Press Htr Pwr Pol 2A-2E Frimary Bkr 90 110 9 270A Pressurizer Heaters l

Backup Fuse 90 N.A.

17, 18, & 42 1

Backup Press Htr Pwr Pn1 2B-1A Primary Bkr 90 110 9 270A Pressurizer Heaters 4

Backup Fuse 90 N.A.

21, 47, & 48 l

I l

EL42109N

~._

M j

i ATTACHMENT 1 (Continued)

^

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

TRIP SEIPOINT OR

RESPONSE

CONT. RATING TIME 4

OEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERE0 3.

600 VAC-Press Htr Pwr Pnis (Continued) i Backup Press Htr Pwr Pn1 28-1B Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

26, 53, & 54 i

Backup Press Htr Pwr i

Pnl 2C-1C j

Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

24, 51, & 52 i

i Backup Press Htr Pwr Pn1 2C-ID Primary Bkr 90 110 0 270A Pressurizer Heaters i

Backup Fuse 90 N.A.

29, 57, & 58 I

Backup Press Htr Pwr l

Pal 2C-2C Primary Bkr 90 110 0 270A Pressurizer Heaters l

Backup Fuse 90 N.A.

34, 63, & 64 Backup Press Htr Pwr Pn1 2C-20 j

Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

39, 69, & 70 e

EL42109N

ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2C-2E Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

44, 75, & 76 Backup Press Htr Pwr Pn1 28-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

31, 59, & 60 Backup Press Htr Pwr Pnl 2B-2C Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

36, 65, & 66 Backup Press Htr Pwr Pnl 28-20 Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

41, 71, & 72 Backup Press Htr Pwr Pnl 28-2E Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

46, 77, & 78 EL42109N

ATTACittENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnls (Continued)

Backup Press Htr Pwr Pnl 2C-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

7, 8, & 30 Backup Press Htr Pwr Pnl 2C-1B Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

19, 20,.& 45

)

Backup Press Htr Pwr Pn1 20-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

3, 4, & 25-Backup Press Htr Pwr Pn1 2D-1B Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

15, 16, & 40 Backup Press Htr Pwr Pn1 2D-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters Backup Fuse 90 N.A.

23, 49, & 50 t

EL42109N

j l

i l

ATTACHMENT 1 (Continued) i i

UNIT 2 CONTAlletENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

l TRIP SLIPOINT OR RESPON5E i

CONT. RATING TIME j

DEVICE NUM ER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

3.

600 VAC-Press Htr Pwr Pn1s (Ccntinued)

Standby Shutdown Press htr 4

MCC SMXG-RSA i

Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

28, 55, & 56 Backup Press Htr Pwr Pn1 2D-2C i

Primary Bkr 90 110 0 270A Pressurizer Heaters Backup Fuse 90 N.A.

33, 61, & 62-i*

Backup Press Htr Pwr i

Pal 2D-20 i

Primary Bkr 90 110 0 270A Pressurizer Heaters l

Backup Fuse 90 N.A.

38, 67, & 68 l

Backup Press Htr Pwr i

Pn1 2D-2E l

Primary Bkr 90 110 9 270A Pressurizer Heaters Backup Fuse 90 N.A.

43, 73, & 74-t

)

4.

120 VAC-Panelboards j

2KM-19

)

Primary Bkr 20 35 9 60A RCP 2A Space Htr j

Backup Fuse 20 N.A.

e i

l l

EL42109N 1

M ATTACHMENT 1 (Continued) i UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONOS)

SYSTEM POWEREO l

4.

120 VAC-Pane 1 boards (Continued) 2KM-20 Primary Bkr 20 35 0 60A RCP 2C Space Htr 4

Backup Fuse 20 N.A.

I 2KN-30

i Primary Bkr 20 35 @ 60A Cont Spray Sys Rh

]

Backup Bkr 20 N.A.

Trans 2 NSMT-5410 2KN-29 Primary Bkr 20 35 @ 60A Cont Spray Sys Rh j

Backup Bkr 20 N.A.

Trans 2 NSMT-5400 2KN-19 Primary Bkr 20 35 @ 60A RCP 28 Space Htr Backup Fuse 20 N.A.

2KN-20 Primary Bkr 20 35 @ 60A RCP 20 Space Htr Backup Fuse 20 N.A.

2KM-29 Primary Bkr 30 45 @ 90A Unit 2 i

Backup Fuse 30 N.A.

Incore Inst Oehun #1

)

2KN-27 l

Primary Bkr 20 35 @ 60A fuel Handling Control Backup Fuse 20 N.A.

Console EL42109N l

ATTACMENT 1 (Continued)

UNIT 2 CONTAlletENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP StIPOINT OR RE5Km5E CONT. RATING TIME DEVICE NUpBER & LOCATION (AMPERES)

(SECONDS)

SYSTEN POWERED 4.

120 VAC-Panelboards (Continued) l l

2KN-25 Primary Bkr 30 45 9 90A Unit 2 Incore Inst Backup Fuse 30 N.A.

Dehum #2 l

S.

240 VAC-Heat Trace l

IEHT MI CB1 Primary Bkr 30 50 9 90A Trace Heat Pnl Bd Backup Fuse 30 N.A.

IENTNIAZ IENT NI CB2 Primary Bkr 30 50 9 90A Trace Heat Pnl Bd Backup Fuse 30 N.A.

IENTNIB2 6.

250 VDC-Lighting RB Deadlight Pnlbd 2DLD #1 Primary Bkr 20 40 9 60A Ltg Pnl Nos. 2LR1 & 2LR2 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #3 Primary Bkr 20 40 9 60A Ltg Pnl Nos. 2LR4, 2LRS, &

Backup Fuse 20 N.A.

2LR6 i

EL42109N

l ATTACHMENT 1 (Continued)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 6.

250 VDC-Lighting (Continued)

RB Deadlight Pnibd 2DLD 14 Primary Bkr 20 40 0 60A Ltg Pn1 Nos. 2LR7, 2LR8, &

Backup Fuse 20 N.A.

2LR9 RB Deadlight Pnlbd 2DLD M6 Primary Bkr 20 40 @ 60A Ltg Pn1 Nos. 2LR12 Backup Fuse 20 N.A.

RB Deadlight Pnibd 2DLD #7 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR16 Backup Fuse 20 N.A.

RB Deadlight Pnibd 2DLD #9 Primary Bkr 20 40 @ 60A Ltg Pn1 Nos. 2LR18 & 2LR17 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #5 Primary Bkr 20 40 @ 60A Ltg Pn1 Nos. 2LR10, 2LR11 Backup Fuse 20 N.A.

s EL42109N

.