TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0 (B)

SPECIAL PROGRAM

(

REPORT TYPE:

SEQUOYAH ELEMENT REVISION NUMBER: 2 TITLE:

SEISMIC INTERACTION DESIGN Design of Lighting Fixture Supports PAGE 1 0F 22 REASON FOR REVISION:

1.

Incorporated TVA line organization coments.

Ir:corpcrated TAS coments and added chronology and Section 10.0,

" Corrective Action."

PREPARATION PREPARED BY:

%.Lk1 nheha Qg SIGNATURE I DATE REVIEWS T, [ dEVIEW COMMITTE k

I2.- I9 -Elo SI6yURf DATE

,o t J W

ib/6'7 g

' 'I SIGNATURE DATE CONCURRENCES 7}. Q

/2 2-t.-84

\\

7

. No:

CEG-H: $ 2 M7 MM a.2S-%

g SRP:

w

/- 7-F7 gg SIGNATURE DATE SIGNATURE

  • DATE 85 gg APPROVED BY:

i k

[l

?

/'@'h N/A l

Og ECSP RANAG M DATE MANAGER OF NUCLEAR POWER DATE

. t a. a.

CONCURRENCE (FINAL REPORT ONLY)

  • SRP Secretary's signature denotes SRP concurrences are in files.

g TVA EMPLOYEE CONCERNS-REPORT NUMBER: 226.0(B).

SPECIAL PROGRAM ~

REVISION NUMBER: 2 a

PAGE 2 0F 22 1.

CHARACTERIZATION OF ISSUE (S):

Concern:

Issue:

WI-85-100-023 Lighting fixtures are not properly.

" Lighting fixtures at WBNP are designed to prevent them from not properly restrained and becoming:

caged to prevent them from.

o Free missiles becoming missiles or swinging o Swinging missiles-missiles during seismic events.

which might damage Category.I CI has no further information.

equipment during a seismic event.

Anonymous concern via letter."

2.

HAVE ISSUES BEEN IDENTIFIED IN ANOTHER SYSTEMATIC ANALYSIS? YES X NO Identified by Institute for Nuclear Power Operations (INPO) and Gilbert / Commonwealth (G/C)

Date See below l

Documentation Identifiers:

a.

INP0 Finding DC.3-2 in 1985 against WBN resulted in Significant Condition Report (SCR) WBN Civil Engineering Branch (CEB) 8537 and the subsequent SCR SQN CEB 8514 (12/24/85).

b.

Gilbert / Commonwealth (G/C) Report No. 2614 dated March 3, 1986, " Final Report - Technical Review of Sequoyah Nuclear Plant Modifications," Technical Issue No.11.

NOTE: The Gilbert / Commonwealth Technical Issue specifically addresses the swinging seismic interaction of a Category I(L) two. inch 0.D. pipe and a Category I valve. This Gilbert / Commonwealth Technical Issue will be resolved by closure of TVA generated SCR SQN Mechanical Engineering

-Branch (MEB) 8610 which will assess the horizontal movement i

(swinging) of seismic Category I(L) supported items i

(including lighting fixtures) and their effect on adjacent seismic Category I items.

Category I(L) items are defined in FSAR Section 3.2.1 as follows:

i

?

01160 - 12/18/86

E TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 3 0F 22 "Those components which are important to reactor operation but not essential to safe shutdown and isolation of the reactor and whose f ailure could not result in a release of substantial amounts of radioactivity, but are in close proximity to Category I components, have been seismically qualified to retain limited structural integrity during a SSE, if they have potential for compromising structures or components necessary to mitigate the [e]ffects of a design basis accident such as a LOCA or steam /feedwater line break."

3.

DOCUMENT NOS., TAG NOS., LOCATIONS OR OTHER SPECIFIC DESCRIPTIVE IDENTIFICATIONS STATED IN ELEMENT:

Lighting fixtures at WBN 4.

INTERVIEW FILES REVIEWED:

The interview files for concern WI-85-100-023 were reviewed on 10/08/86 as indicated by RFI SQN #622 (10/08/86). The file contains only the K-Form and Generic Applicability information.

5.

DOCUMENTS REVIEWED RELATED TO THE ELEMENT:

See Appendix A.

6.

WHAT REGULATIONS, LICENSING COMMITMENTS, DESIGN REQUIREMENTS OR OTHER APPLY OR CONTROL-IN THIS AREA?

See Appendix A.

7.

LIST REQUESTS FOR INFORMATION, MEETINGS, TELEPHONE CALLS, AND OTHER 4

DISCUSSIONS RELATED TO ELEMENT.

See Appendix A.

L 01160 - 12/18/86

c-TVA EMPLOYEE CONCERNS-REPORT NUMBER:- 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 t

PAGE 4 0F 22 8.

EVALUATION PROCESS:~

a.

Evaluated program to assure that lighting fixtures do not become seismic interaction items.

b.

Reviewed attachments to the two NRC letters from Youngblood to White (02/18/86) and (06/23/86) for possible additional relevant information.

c.

Obtained and reviewed design drawings for light fixtures.

d.

Reviewed selected calculations of light fixture restraints.

e.

Reviewed SQN program and results to date in resolving SCR SQN MEB 8610 and Gilbert / Commonwealth Technical Issue # 11.

9.

DISCUSSION, FINDINGS, AND CONCLUSIONS:

r Chronology:

+

e Start of construction to present:

Time period cited in concern 03/23/73:

Light fixture vertical support addressed by TVA in design criteria SQN-DC-V-13.11 07/25/78:

Light fixture horizontal movement addressed by TVA in design guide DG-C.l.6.3 l

Prior to 06/08/84:

Concern identified to TVA management 6

12/07/85:

K-form provided Sometime in INP0 WBN Audit Finding DC.3-2 regarding vertical 1985:

and horizontal issues on generic rod hung items 12/24/85:

Resultant SCR SQN CEB 8514 addressing vertical issue 03/03/86:

G/C Report No. 2614 addressing horizontal issue 03/03/86:

Resultant SCR SQN MEB 8610 01160 - 12/18/86 1

r TVA EMPLOYEE CONCERNS REPORT NUMBER:.226.0 (B)

SPECIAL PROGRAM REVISION N'JMBER: 2 PAGE 5 0F 22 Discussion:

Light Fixture Support Criteria NRC General Design Criterion 4 requires that Category I structures, systems, and. components be appropriately protected against dynamic effects, including the effects of missiles, pipe whipping, _and discharging fluids, that may result from equipment f ailures and from events and conditions outside the nuclear power unit.

SQN commitment to comply with this criterion is contained in FSAR Section 3.2, (App. A, 6.a).

Position C-2 of Regulatory Guide 1.29, " Seismic Design Classification," (App. A, 6.b) states that those portions of structures, systems, or. components that are non-Category I, i.e.,

I(L), but whose f ailure could reduce the functioning of a Category I item to an unacceptable safety level should be designed and constructed so that the Safe Shutdown Earthquake (SSE) would not cause such failure. SQN commitment to comply with this regulatory guide is contained in FSAR Section 3.2.1, (App. A, 6.a).

The design of-SQN electrical system is based, in part, on Standard IEEE-308-1971 ( App. A, 6.g) as stated in FSAR Section 8.1.5

( App. A, 6.a). This standard establishes and defines Class lE as the classification of electrical equipment required to achieve safe slotdown. Based on evaluation team discussions with TVA personnel (IOM #357 and #371) (App. A, 7.m and n) SQN was originally designed with three lighting systems:

o Normal Lighting - This system is powered from non-Class 1E power sources.

i o

Standby Lighting - This system is normally powered from non-Class 1E power sources and transfers to the on-site Class IE diesels upon failure of non-Class 1E sources.

o Emergency Lighting - This system is powered from the on-site Class lE vital battery boards and is activated by failure of the off-site sources and operates until transfer from the normal to standby system is completed when the diesels are fully functional.

This 125 Vdc system is designed for 2-hour operation.

l 01160 - 12/18/86 i

TVA EMPLOYEE CONCERNS REPORT NUMBER: ~ 226.0 (B)

.f SPECIAL PROGRAM i

REVISION NUMBER: 2 PAGE 6 0F 22 The structural' support of these three systems is described in SQN-DC-V-13.11 ( App. A, 6.c) and shown on drawing series 47A057 (App. A, 5.u).

NCR SQN MEB 8304, R2 (App. A, 5.v) indicates that TVA committed to the NRC on 10/23/79 to provide a fixed self-contained second emergency lighting system consisting of fluorescent or sealed beam units with an individual 8-hour minimum battery power supply in areas that must be manned for safe cold shutdown and for access and 4

egress-routes to and from all fire areas.

This commitment was made in response to NRC review of FSAR for 10 CFR Part 50, Appendix R requirements.

The structural support.for this system is not included in SQN-DC-V-13.11 (App. A, 6.c), but is shown on drawing 47N1410-1, R18 ( App. A, 5.u).

TVA design criteria for seismic support of original design lighting fixtures in Category I structures are contained in Civil Design Guide DG-C1.6.3 (App. A, 6.d), which states that a. literature j

survey of damage due to earthquakes finds lighting fixtures highly susceptible to failure. This is particularly true for

. pendant-mounted fluorescent and incandescent fixtures. The criteria conclude that, with certain stated exceptions, the incorporation of an auxiliary support cable as an integral part of the light fixture is the most effective approach for~ ensuring an appropriate degree of seismic vertical restraint. This support is

.a 1/16-inch flexible corrosion-resistant cable (MIL-C-5424).

Additional requirements are imposed for the first emergency lighting system to maintain the electrical power supply to the i

fixture during or after a seismic event. This is accomplished by a three-way lateral cable support system which keeps the fixture in a l

plumb position.

l I.

Design Guide DG-C-1.6.3 ( App. A, 6.d) further states that:

I "In the event of a lighting fixture failure due to i

seismic conditions, motion of the fixture in any direction will be limited to the length of free cable. Care must be taken to eliminate or i

otherwise protect any safety-related equipment within the range of motion afforded by the cable l

from impact by the fixture."

l 1

01160 - 12/18/86

m

~

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 f;

PAGE 7 0F 22 The evaluation team has reviewed these criteria in light of general engineering industry experience and determined that they are adequate.

The SQN design criteria, which predate the civil design guide, for l

support of original lighting fixtures in Category I structures are contained in SQN-DC-V-13.ll (App. A, 6.c), which forms the design commitment for SQN. The two sets of design criteria are very similar. With the exceptions noted later, after review of the i

47A057 (App. A,- 5.u) series lighting fixtures support drawing, the i

evaluation team determined that SQN-DC-V-13.11 (App. A, 6.c) criteria are adequate based on general engineering industry experience.

Criteria Application The implementation of the SQN design criteria is contained in the notes and details shown on the 47A057 (App. A, 5.u) series lighting l

fixture support drawing which is invoked by lighting plan and detail drawings such as 45N1410-1, 55N416-1, and 55N416.2 (App.. A, 5.u).

Individual lighting fixtures in nuclear industry f acilities are typically light weight, generally 50 pounds or less and rarely exceeding 100 pounds. These weights are confirmed by SQN-DC-V-13.11 ( App. A, 6.c) Section 4.0, which indicates weights in the 20 to 35 pound range.

L Smaller and lighter fixtures have one auxiliary cable support'at 1

the fixture stem while larger and heavier fixtures generally have more than one stem with auxiliary cable supports at each stem. The minimum breaking strength of the cable is specified to be 480 pounds. The cable is generally attached to a single expansion j

anchor either 1/4-or 3/8-inch in diameter.

Specification G-32 (App. A, 5.t) indicates allowable tension working loads of 500 and L

700 pounds and shear working loads of 300 and 500 pounds. Thus the evaluation team concludes that the light fixtures are properly designed with adequate vertical support to withstand a seismic event. The evaluation team has reviewed this drawing series and concludes that it is technically adequate, subject to one observation which is similar to that for SQN-DC-V-12.ll (App. A, 6.c).

This observation is that Figure 5.0-1 of the design criteria SQN-DC-V-13.ll (App. A, 6.c) and the principal detail for emergency lighting fixtures on 47A057-21, R3 (App. A, 5.u) correctly illustrate application of Section 5.0 criteria.

I l

01160 - 12/18/86

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0 (B).

E SPECIAL PROGRAM REVISION NUMBER: 2 f-PAGE 8 0F-22 However, the details in Figure '4.7-1 for the emergency light and the alternate detail shown on 47A057-21 (App. A, 5.u) and the emergency l light detail shown on 47A057-6, R5 do not agree with the text of Section 5.0 and with Figure 5.0-1.

The evaluation team reviewed drawings 47N1410-1, R18, 55N416-1, R18, and 55N416-2, R19 (App. A, 5.u) and noted that they refer to a battery pack emergency light system that differs from the types described in either the SQN design criteria or drawing 47A057, as discussed earlier. This battery pack emergency lighting system is not required to withstand a SSE, as indicated by general note 5 of drawing 47N1410-1, but must be restrained from becoming a hazard to Category I systems during or following a SSE. These restraint

- details are shown as detail A of drawing 47N1410-1 and the evaluation team deems them to be adequate for the purpose.

Seismic Interaction Program The discussion below is not specifically about the support of lighting fixtures.

It does, however, relate to the development of TVA's seismic interaction program and the subsequent addressing of lighting fixtures as a component of that program.

In early 1986, Gilbert / Commonwealth (G/C) conducted a technical review of the SQN main and auxiliary feedwater systems modifications between issue of operating license and June 1985.

G/C Report 2614 (03/03/86) (App. A, 5.a) describes the approach, methodology, results, and conclusions of the technical review.

Technical Issue No.11 of that report is titled " Seismic Interactions" and describes a condition where a 2-inch 0.D.

Category I(L) primary makeup water supply piping system was located near tubing supplying air to the auxiliary feedwater bypass valve 2-LCV-3-148A. This piping is not seismically restrained to prevent lateral displacement and the striking of the air supply line. G/C found no documentation to demonstrate that this interaction would r

not impair the auxiliary feedwater system safety functions.

G/C also found that INP0 Finding DC.3-2 (1985) (App. A, 5.z) for WBN identified a proximity issue regarding displacement of Category I(L) piping systems as a potentially generic concern. This INP0 finding and the resultant SCR SQN CEB 8514 (App. A, 5.v) address the position retention (falldown) but not the displacement (swinging) of a Category I(L) system. The TVA action plan to resolve G/C Issue No.11 resulted in the generation of SCR SQN MEB 8610 ( App. A, 5.v).

(

l 01160 - 12/18/86

=

g-TVA EMPLOYEE CONCERIIS-REPORT NUMBER: ' 226.0 (B)

SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 9 0F 22 During 02/12-03/14/86, the NRC -staff. conducted a special inspection' to examine design control practices for SQN. The main focus of this inspection was on the findings of the G/C technical review and additional items. The inspection results are contained in NRC I&E -

Inspection Reports 50-327/86-27 and 50-328/86-27 transmitted by NRC letter from Taylor to White (04/22/86) (App. A, 5.b).

The NRC concluded that _the G/C review was thorough and appropriate in technical depth within the selected review scope and that the technical and generic issues identified appear to be valid.

G/C Technical Issue No.11 indicated that a proximity issue was identified with regard to the displacement of.. Category I(L) piping WBN (App. A, 5.z) generic concern by INP0 Finding DC.3-2 in 1985 for as a potentially

. This finding resulted in SCR SQN CEB 8514 (12/24/85 and 02/28/86) (App. A, 5.v).

The INP0 finding states:

"An engineering evaluation has not been performed to justify the design criteria of seismically supported.nonsafety (IL) [I(L)]

systems. The present design criteria for IL

[I(L)] rod hangers is not adhered to consistently.

Some IL [I(L)] support designs do not consider all seismic loadings."

The INP0 finding contained the following as supporting facts:

o Undocumented development of vertical load criteria for piping support rod hangers 4

o Inconsistent factors of safety not meeting design criteria for piping supports o

Undocumented development of flexibility criteria for HVAC duct rod hangers o

The potential for rod hanger supported pipe displacing and impacting other nearby components / systems is not addressed

<igid supports are interspersed with rod hangers in HVAC I(L) o duct systems.

Distribution of horizontal loads in a seismic event is not modeled consistently with actual structural behavior

(

01160 - 12/18/86

( -..

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)~

.SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 10 0F 22 Further Relevant Document Review The evaluation team reviewed the attachments to NRC letters from

' Youngblood to White (02/18/86 and 06/23/86) (App. A, 5.c and d) for issues or information, relevant to this report, that are not included in the concern statement itself. No such issue or information was-found in the February 1986 letter; however, on pages 131-133 of the attachment to the June 1986 letter, it became apparent to the evaluation team that the term " caged" used in the concern relates to prevention of the light bulbs or tubes from f alling out of the fixtures -as a result of a seismic event. This associated issue does not appear to have been subjected to a documented review by TVA.

However, the evaluation team's generic conclusion is that because light bulbs and tubes have brittle glass and light mass (usually one pound or less), they do not generally present a significant safety hazard that might compromise the function of adjacent Category I equipment, which is of greater ruggedness and mass. According to criteria developed by the evaluation team for other nuclear power plant facilities, the item being struck will not generally be adversely affected if the size or mass of the striking item is less than or equal to that of the item being struck.

Exceptions for this conclusion might be found in areas such as over the main control room semi-horizontal panels where plant operators or panel switches or buttons might be impacted. During the evaluation team walkdown during the week of 06/24/86 for evaluation of Element Report 224.5(B), it was noted that there was a grate or grid for diffusing light between the tubes or bulbs and the control panels which will mitigate any falling tubes' or bulbs. Thus the evaluation team considers this associated issue to be of no safety significance.

TVA Evaluation of SCR SQN MEB 8610 Inspection criteria for rod hung Category I(L) items are established in TVA memo from Handy to SQN Files (04/22/86)

(App. A, 5.k).

This memo, which has been checked, reviewed, and approved by TVA, establishes a maximum horizontal displacement of

+ 6 inches for such pipes, conduits, HVAC ducts, and cable trays and a maximum horizontal displacement of + 10 inches or + 30 degrees swing angle, whichever is less, for pendant-mounted light fixtures.

.(-

01160 - 12/18/86

y

.TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 f

PAGE 11 0F 22 Evaluation team discussion with TVA personnel (IOM #326, App. A, 7.k) indicated that there are no calculations or other documentation for these criteria which are based on informal studies ~ of ground motion displacements at rock-based sites within the TVA service territory plus consideration of building movements during an SSE. TVA personnel committed to providing such documentation in IOM #326 (10/01/86, App. A,_7.k).

On the basis of evaluation team discussions with TVA personnel as documented in IOM #326 (App. A, 7.k), new Engineering Change Notices will address seismic interaction concerns as a part of the seismic review process.

These new evaluations will be similar to, and compatible with, those completed under SCR SQN MEB 8610 (App.aa,5.v).

This seismic review with CEB-DI-121.03, R1 (App. A, 6.f) process will be in accordance

,E" Seismic Design, Review and Control." The CEB seismic evaluation for seismic interaction will include the following elements:

}

~

Ensure equipment and systems will not have unacceptable o

impact-from existing rod hung Category I(L) items o

Ensure that new rod hung Category I(L) items will not impact existing Category I fragile items in an unacceptable manner These two elements are currently expected to be based on design consultation ana walkdown information and evaluation. As these elements are currently based on verbal instruction TVA personnel understand that there is a need to formally document this

-instruction by revision of CEB-DI-121.03.

A walkdown of the auxiliary building was conducted (March 8 and 9, 1986 and documented by TVA memo.from Estes to Brown, 06/05/86, App. A, 5.n) to identify possible interactions between Category I(L) supported components and safety-related components which could result in degrading a safety system.

This TVA walkdown of the auxiliary building identified 204 possible interactions of which 98 were reviewed by CEB. The remainder were justified by Electrical Engineering Branch (EEB) and MEB.

l Approximately 20 interactions involved lighting fixtures or stems.

TVA concluded that 10 interactions - none involving lighting -

required field work.

TVA determined that one of these ten interactions (one pipe potentially interacting with two separate air line solenoid valves) was due to seismic interaction considerations and that the remainder were due to other considerations.

(

0116D - 12/18/86

(

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226,0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 12 0F 22 A second walkdown of the control building, diesel generator building, additional diesel generator building, Emergency Raw Cooling Water (ERCW) pumping station and the annulus areas of both Units 1 and 2 reactor buildings was conducted on 04/26-27/86, as documented by TVA memo from Estes to Brown (06/11/86) (App. A, 5.o), for similar purposes and with similar methodology as the first walkdown.

This TVA walkdown identified 90 possible interactions of which 49 were reviewed by CEB.

The remainder were justified by EEB and MEB.

There were two interactions involving lighting fixtures and/or stems. TVA concluded that two interactions - none involving lighting - required field work for reasons other than seismic interactions.

The first walkdown was surveyed by the TVA Quality Surveillance Group (on 04/18-22/86 and documented by TVA memo from Andrews to Wilson, 05/14/86) ( App. A, 5.i), to assess the adequacy of the walkdown prccedures and walkdowns performed by Division of Nuclear Engineering (DNE) in the auxiliary building. The weaknesses listed by this memo appear to the evaluation team to have been satisfactorily resolved based on review of the walkdown package.

Technical Instruction TI-98, R0 (04/25/86) (App. A, 5.s) and a similar predecessor document were used to perform the walkdowns.

This instruction was reviewed and approved by Plant Operations Review Committee (PORC) as documented by Unreviewed Safety Question Determination (USQD) for TI-98, R0 (04/25/86) (App. A, 5.s) in response to directions in TVA memo from Andrews to Abercrombie (04/18/86) ( App. A, 5.j) that walkdowns or surveys of safety-related matters must be performed by PORC-reviewed instructions pending an approval programmatic instruction.

The evaluation team reviewed TI-98 and concluded that it was adequate for its stated scope.

During review of the walkdown instruction and resultant documentation the evaluation team noted that portions of the auxiliary building and the containment vessel portion of the reactor buildings were excluded from the scope of the walkdowns.

TVA's Action Pian to resolve G/C technical Issue No. 11 (02/24/86)

(App. A, 5.a) committed to list, walkdown, and evaluate all Seismic I(L) systems for SQN. This committment was confirmed in IOM #416 (11/19/86) (App. A, 7.p).

01160 - 12/18/86

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0 (B)

SPECIAL PROGRAM REVISION NUMBER: 2 i

PAGE 13 0F 22 The evaluation team notes the lack of a document describing the complete program for controlling this seismic interaction activity.

The technical instruction will effectively implement the walkdown activities of this program. The TVA memo from Handy to SQN files (04/22/86) (App. A, 5.k) contains adequate threshold criteria for subsequent evaluations when its basis is adequately documented. The division of responsibilities between disciplines is defined in CEB-DI 121.03, R1, (App. A, 6.f).

Such a program might include thresholds of fragility / ductility / flexibility to provide additional criteria for interaction resolution.

The walkdowns and evaluations performed to date and those that are required to complete this effort will resolve near-term issues and furnish an adequate baseline for future evaluations as additional plant modifications are made. Recognition of this future need is alluded to in item c. of block 5e in SCR SQN MEB 8610 (App. A, 5.v), which states:

" Corrective action will be readdressed to the

' post-modification walkdown phase' rather than to the ' design phase,' and will be included in the acceptance criteria of the post-modification walkdown."

TVA personnel committed to revise CEB-DI-12.1.03 to provide a complete program in IOM #416 (11/19/86) ( App. A, 7.p).

The walkdown results are indicated on a marked set of plant drawings and a computerized listing attached to the two TVA memos from Estes to Brown.

The documentation of the EEB and MEB evaluations appears to be principally the interaction resolution contained in the computerized listings ( App. A, 5.n and o) while that for the CEB is calculation CEB CAS 214, R1 ( App. A, 5.w).

I The evaluation team reviewed both the computerized listings of potential seismic interactions and the calculations and noted the following:

o Many interactions are resolved by the notation that the nenrod-hung item is nondivisional, nontrained, etc.

This is acceptable since r.either item in the interaction is clearly required for safe plant operation or shutdown.

t 01160 - 12/18/86

o r.:

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0 (B)

~

'SPECIAL PROGRAM REVISION NUMBER: 2 l

PAGE 14 0F 22 o

The evaluation team reviewed a copy of the CEB calculation (CEB-CAS-214) for lichting fixtures ~and other items included within the scope of $CR SQN MEB 8610 ( App. A, 5.v).

The calculation was reviewed for its assumptions, collection of data, logic, analysis, and conclusions. This calculation is based on photographs of the interaction, the interaction the design criteria description in the computerized listing,(04/22/86) in the TVA memo from Handy to.SQN files (App. A, 5.k), and other data gathered during the.walkdowns.

The evaluation team considers the calculation to be generally adequate;- however, additional written justification is needed in some areas to permit another engineer who did not participate in the original walkdowns to arrive at the same conclusions. During the discussions with TVA personnel (App.

A, 7.p) it became apparent that enhanced understanding may be obtained by. viewing the original color photographs. During these discussions TVA personnel committed to have a supervisor re-review calculation CEB-CAS-214 in light of the above and any necessary changes to the calculations will be made at the time of additional walkdown evaluations.

The evaluation team considers the TVA action plan response to G/C Issue No. 11 and corrective action / action required to prevent recurrence portions of SCR SQN MEB 8610 generally adequate in concept. However, some deficiencies and discrepancies exist.in TVA evaluations and design-documents regarding prevention of lighting _

fixtures from becoming swinging missiles (seismic interaction) and the application of the lighting design criteria. TVA personnel committed to correct these deficiencies and discrepancies, as described in the findings below, in IOM #399 (ll/14/J6)

( App. A, 7.o) and IOM #416 (11/19/86) (App. A, 7.p).

V Findings:

a.

The TVA design of light fixtures provides for adequate vertical support to withstand a seismic event and prevent their becoming free missiles that might damage Category I equipment. The TVA design of light fixtures, per se, does not, in general, provide adequate horizontal support during and after a seismic event to prevent their becoming swinging missiles that might damage adjacent Category I equipment.

However, this design oversight has been documented on SCR SQN MEB 8610 (App. A, 5.v) and is being addressed.

1 01160 - 12/18/86

Qm.

,(,

i TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 i

PAGE 15 0F 22 b.

The evaluation team noted that there is no document which describes the complete program for controlling the seismic interaction design activity. Technical Instruction TI-98, R0 (App. A, 5.s) will effectively implement the walkdown activities of this program when amended to address all plant areas. The TVA_ memo from Handy to SQN files (04/22/86)-

(App. A, 5.k) provides adequate threshold criteria for subsequent evaluations. The division of responsibilities between disciplines is ' defined in CEB-DI 121.03, R1, (App. A, 6.f).

In addition, the CEB seismic review process for future reviews is to be in accordance with a future revision of CEB-DI-121.03, R1 (App. A, 7.o) and includes an evaluation for adverse impact of rod hung items as indicated by IOM #326 (10/01/86) (App. A, 7.k).

However, this evaluation is currently in the form of verbal instructions which TVA personnel have committed to properly document.

c.

Plant walkdowns and. subsequent technical evaluations by TVA to resolve SCR SQN MEB 8610 (App. A, 5.v) excluded portions of the auxiliary building and the containment vessel portion of the reactor building which were contaminated or required dress-out.

Evaluations of these areas are necessary to determine the need for any potential hardware fixes. TVA personnel committed to perform a walkdown and evaluation of these areas in IOM #416 (11/19/86) (App. A, 7.p).

d.

The technical basis for the inspection criteria established in TVA memo from Handy to SQN Files (04/22/86) has not been documented.

TVA personnel committed to providing such documentation in IOM #326 (10/01/86) (App. A, 7.k).

e.

The evaluation team considers calculation CEB-CAS-214, R1 generally adequate; however, additional written justification is needed in some areas to permit another engineer who did not participate in the original walkdowns to arrive at the same conclusions.

TVA personnel committed to re-review the calculation based on the above and make any necessary changes (App. A, 7.p).

f.

Figure 5.0-1 of the design criteria SQN-0C-V-13.11 (App. A, 5.r) correctly illustrates the criteria application of Sectio'n 5.0; however, the details in Figure 4.7-1 for the emergency light do not agree with the text of Section 5.0.

(

01160 - 12/18/86

r t

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0 (B)

SPECIAL PROGRAM REVISION NUMBER: 2 b

PAGE 16 0F 22 g.

The principal detail for emergency lighting fixtures on 47A057-21, R3 (App. A, 5.u) correctly illustrates the application of design criteria SQN-DC-V-13.ll, Section 5.0

( App. A, 5.r).

However, the alternate detail shown on 47A057-21 and the emergency light detail shown on 47A057-6, R5 do not agree with the text of Section 5.0.

==

Conclusions:==

The evaluation team concludes the issue of light fixtures not being properly designed to prevent them from becoming free missiles is not a valid issue since TVA has provided a design that is adequate to keep the light within an arc radius of the length of the cable support. However, the evaluation team concludes that the issue of light fixtures not being properly designed to prevent them from becoming swinging missiles is a valid issue which has been recognized as indicated by TVA in its action plan response to G/C Issue No. 11 and the generation of SCR SQN MEB 8610.

The evaluation team considers the TVA action plan response to G/C Issue No. 11 and corrective action / action required to prevent recurrence portions of SCR SQN MEB 8610 generally adequate in concept.

However, some deficiencies and discrepancies exist in TVA evaluations and design documents regarding prevention of lighting fixtures from becoming swinging missiles (seismic interaction) and the application of the lighting design criteria. TVA personnel committed to correct these deficiencies and discrepancies, as described in the findings above, in IOM #399 (11/14/86)

( App. A, 7.o) and IOM #416 (11/19/86) ( App. A, 7.p).

10. CORRECTIVE ACTIONS:

A TVA transmittal (App. A, 5.aa) submits a corrective action plan (CAP) which will eliminate the discrepancies between the various design drawings and design criteria; provide a complete program to describe and control the seismic interaction evaluations for current and future design activities; and provide a technical basis for the internal TVA memo from Handy to SQN files (04/22/86)

(App. A, 5.k).

In addition, this CAP will provide for an evaluation of areas of the plant previously excluded.

This evaluation will use an appropriate technical program followed by evaluation via calculation revision to CEB CAS 214, Rl.

This calculation revision will include a re-review for adequacy of written technical justification of the existing revision and as described in findings above, in IOM #399 (11/14/86) (App. A, 7.o) and IOM #416 (11/19/86) (App. A, 7.p).

The evaluation team concludes that the stated CAP is an acceptable resolution of the concern that should also preclude recurrence of findings.

01160 - 12/18/86

TVA EMPLOYEE CONCERNS REPORT NUMBER:

226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 17 0F 22 APPENDIX A

'5.

DOCUMENTS REVIEWED RELATED TO THE ELEMENT:

a.

Gilbert / Commonwealth's " Final Report Technical Review 'of SNP Modifications for TVA," G/C Report No. 2614, Technical Issue Data Sheet No.11 (03/03/86) b.

Letter from J. M. Taylor, NRC, Director of Office of Inspection and Enforcement to S. A. White, TVA, Manager of Nuclear Power.

Subject:

"NRC Reports 50-327/86-27 and 50-328/86-27," [L44 860506 542], (04/22/86) c.

Letter from B. J. Youngblood, NRC, Director PWR Project Directorate #4, NRR to S. A. White, TVA, Manager of Nuclear Power,'

Subject:

" Concerns Regarding TVA Nuclear Program,"

[L44. 860226'001], (02/18/86) d.

Letter frcm B. J. Youngblood, NRC, Director PWR Project

- Directorate #4, NRR to S. A. White, TVA, Manager of Nuclear Power,

Subject:

" Transcript of Interview...," [none],

(06/23/86) e.

TVA SQN memo from J. P. Vineyard, Project Manager to H. B.

Rankin, Manager Design Services.

Subject:

" Routing of Safety Related Conduits, Cable Trays, Piping and Instrument Lines in Nonseismic Designated Areas in Category I Structures," [B25 851205 004], (12/05/85) f.

TVA SQN memo from H. B. Rankin, Manger Design Services to J.

P. Vineyard, Project Mana

Subject:

"SCR SQN NEB 8516 Rev.

0," [S01 860102 805]ger.,(01/03/86) 9 TVA SQN Memo from J. P. Vineyard, Project Manager to H. B.

Rankin, Manager Design Services.

Subject:

"SCR SQN NEB 8516 R0," [B25 860107 011], (01/07/86) h.

TVA SQN memo from J. C. Key, Mechanical Lead Engineer to C.

N. Johnson, Civil Lead Engineer.

Subject:

"SCR 8610 Walkdown Civil Involvement," [825 860408 002], (04/08/86) 1.

TVA SQN memo from W. E. Andrews to D. W. Wilson.

Subject:

"Walkdowns conducted by DNE," [S08 860502 814], (05/14/86) j.

TVA SQN memo from W. E. Andrews, Site Quality Manager to H.

L. Abercrombie, Site Director.

Subject:

" Conduct of Plant Walkdowns and Surveys," [S08 860418 811], (04/18/86)

(

0116D - 12/18/86

TVA EMPLOYEE CONCERNS' REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 p

PAGE 18 0F 22 APPENDIX A (cont'd) k.

TVA SQN nemo from K. D. Handy, Mechanical Engineer to SQN Files..

Subject:

"SCR SQN NEB 8515 - Rod Hung Category I(L)

System Interaction Limits with Safety Related Targets -

Duality Design Information," [B25 860422 008], (04/22/86) 1.

TVA SQN memo from C. N. Johnson, Civil Lead Engineer to J. C. Key, Mechanical Lead Engineer.

Subject:

"SNP-SCR 8610

- Walkdown Civil Involvement," [825 860516 021], (05/16/86) m.

TVA SQN memo from D. W. Wilson, Project Engineer to H. L. Abercrombie, Site Director.

Subject:

"SNP - Seismic Dead Load Supports Used for Class lE Electrical Conduit Installation," [B25 860603 013], (06/03/86) n.

TVA SQN memo from W. E. Estes, Mechanical Engineer to W. H. Brown,' Mechanical Engineer.

Subject:

" Report of Results of March 8-9, 1986 Walkdown of the Auxiliary Building for Interactions," [825 860606 003], (06/05/86) o TVA SQN computerized "Walkdown Report for Seismic Safety Interfaces SQEP Mechanical Section No.1" for the Au/iliary Building attached to [B25 860606 003],

(04/17/86) o.

TVA SQN memo from W. E. Estes, Mechanical Engineer to W. H. Brown, Mechanical Engineer.

Subject:

" Report of Results of April 26-27, 1986 Walkdown of the Ul and U2 Annulus, Control and Diesel Generator Buildings, and the ERCW Intake Pumping Station," [B25 860610 001], (06/11/86) o TVA SQN computerized "Walkdown Report for Identifying Interactions in the Control and Diesel Generating Buildings, ERCW Pump Station and U1 and U2 Annulus,"

attached to [B25 860610 001), (04/26-27/86) p.

TVA SQN DIM from C. N. Johnson, Civil Lead Engineer to SQN CEB files.

Subject:

"Sequoyah Nuclear Plant - Design Input Memeraudum for Location and Design of Piping and Supplemental Steel in lategory I Structures - Design Criteria, SQN-DC-V-24.1," preliminary (10/03/86) q.

TVA Memo from J. C. Key, SQN Mechanical Lead Engineer to N. A. Liakonis.

Subject:

" Auxiliary Building Piping Interaction Walkdown," [B25 861014 015], (10/14/86)

(

0116D - 12/18/86 s

r.

.,..--,,-,p

, _. ~,

r.

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 19 0F 22 APPENDIX A (cont'd) r.

TVA Design Criteria / Guides:

o TVA Design Criteria SQN-DC-V-13.11, R1, " Support of Lighting Fixtures in Category I Structures," (03/23/73) o TVA General Design Information, LG-C1.6.3, " Seismic Support of Lighting Fixtures in Category I Structures,"

(06/05/81) s.

TVA Procedures:

o TVA SQN Technical Instruction TI-98 R0, "Walkdown Procedure for Identifying Interactions in the Control and Diesel Generating Buildings, ERCW Pump Station and U1 and U2 Annulus," (04/25/86) o TVA SQN USQD for TI-98 R0, (04/25/86) t.

TVA Specification:

o TVA General Construction Specification No. G-32, Rev.11, " Bolt Anchors Set in Hardened Concrete,"

[B42 851216 500] (01/31/86).

u.

TVA Drawings:

I o

47A057, R10, " Mechanical Seismic Supports - Lighting Fixtures" o

45N1410-1, R18, " Lighting - Plans and Details -

Elev. 653.0" o

55N416-1, R18, " Lighting - Floor Elev. 732.0 - Plans and Details" o

55N416-2, R19, " Lighting - Floor Elev. 732.0 - P1ans and Details" v.

TVA Conditions Adverse to Quality (CAQ):

r o

NCR SQN MEB 8304, R2, [B44 860404 007] (04/04/86) o-SCR SQN CEB 8514, R0, [B41 851231021] and

[B41 860228 017], (12/24/85) and (02/28/86)

SCR SQN MEB 8610, R1, [B44 860611047] (06/11/86) o 01160 - 12/18/86

TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B) y SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 20 0F 22 APPENDIX A (cont'd) w.

TVA Calculation:

o CEB CAS 214, R1 " Evaluation of Walkdown Report for Seismic Safety Interferences," [B41860516 004]

(05/16/86) x.

TVA SQN ECN LC693, [B25 860617 527] (05/19/86) y.

TVA SQN work request nos. 107622, 107623 and 107627 dated 05/20/86, 03/09/86, and 03/09/86 respectively [ Interactions TPW/734/003; HVG/734/003; HVG/734/004]

z.

INP0 WBN 1985 Audit Finding DC.3-2 aa.

TVA ECEP-SQN Restart Program - Corrective Action Plan (CAP) for Element 226.0(B), TCAB-029 (12/12/86) 6.

WHAT REGULATIONS, LICENSING COMMITMENTS, DESIGN REQUIREMENTS OR OTHER APPLY OR CONTROL IN THIS AREA?

a.

SNP FSAR Update through Amendment 03 3.1 "Conformance with NRC General Design Criteria" 3.2 " Classification of Structures,-Systems and Components" 3.0 " Electric Power" b.

NRC Regulatory Guide 1.29 R1, " Seismic Design Classification," (8/73) c.

TVA Design Criteria SQN-DC-V-13 ll, R1, " Support of Lighting Fixtures in Category I Structures," (03/23/73) d.

TVA General Design Information, DG-C1.6.3, " Seismic Support of Lighting Fixtures in Category I Structures," (06/05/81) e.

TVA Policy Memorandum PM86-04(DNE) from W. C. Drotleff, Director of Nuclear Engineering to Those Listed.

Subject:

" Engineering Judgment," [B20 860424 001], (04/25/86) f.

TVA Design Interface Document CEB-DI 121.03, R1, " Seismic Design, Review, and Control," (05/16/86) g.

IEEE Standard Criteria for Class lE Power Systems for Nuclear Power Generating Stations, IEE Std 308-1971

(

01160 - 12/18/86 L -

p TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)~

SPECIAL PROGRAM REVISION NUMBER: 2 b

PAGE 21 0F 22 APPENDIX A (cont'd) 7.

LIST REQUESTS FOR INFORMATION, MEETINGS, TELEPHONE CALLS, AND OTHER DISCUSSIONS RELATED TO ELEMENT.

a.

RFI SQN #547 (09/24/86) b.

RFI SQN #590 (09/26/86) c.

RFI SQN #592 (09/26/86) d.

RFI SQN #596 (09/26/86) e.

RFI SQN #601 (09/30/86) f.

RFI SQN #622 (10/08/86) g.

RFI SQN #662 (10/27/86) h.

RFI SQN #700 (11/07/86)

(

i.

TVATransmittal#005, Item 30,(03/21/86) j.

TVA Transmittal #116 (09/22/86) k.

Telephone call from J. W. Benkert, Bechtel, to N. A. Liakonis anc J. K. Rochelle, TVA, IOM #326 (10/01/86).

1.

Telephone call from J. A. Utley, TVA, to J. W. Benkert, Bechtel, IOM #318 (10/20/86) m.

Telephone call from J. W. Benkert, Bechtel, to P. B. Nesbitt and C. Sudduth, TVA, IOM #357 (10/31/86) n.

Telephone call from J. W. Benkert, Bechtel, to C. Sudduth, TVA, IOM #371 (11/06/86)

[

o.

Telephone call from N. A. Liakonis, J. K. Rochelle, and W. H. Brown, TVA, to J. W. Benkert, Bechtel, IOM #399 (11/14/86) p.

Telephone call from N. A. Liako.1:s and J. K. Rochelle, TVA, to J. W. Benkert, Bechtel, 10!1 #416 (11/19/86) k 0116D - 12/18/86

r-TVA EMPLOYEE CONCERNS REPORT NUMBER: 226.0(B)

-SPECIAL PROGRAM REVISION NUMBER: 2 PAGE 22 0F 22 CATD LIST The following CATO forms are included as part of this report:

226.00 SQN 01 (12/11/86) 226.00.SQN 02 (12/11/86) 226.00SQN03(12/04/86)

(

t 01160 - 12/18/86

V

^

9 g

-y i g

+c f

' : ;)

9 tai 5

109 REFERENCE

- ECPS120J-ECPS121C TENNESSEE VALLEY AUTHORITY PAGE FREQUENCY

- REQUEST OFFICE OF NUCLEAR POWER RUN TIME - 12:57:19 ONP - ISSS - R11M EMPLOYEE CONCERN PROGRAM SYSTEM (ECPS)

RUN DATE - 12/02/86 LIST OF EMPLOYEE CONCERN INFORMATION CATEGORY: EN DES PROCESS & OUTPUT SUBCATEGORY: 22600 THO-0VER-ONE DESIGN S

GENERIC KEYHORD A H

APPL QTC/NSRS P

KEYHORD B CONCERN SUB R PLT BBSH INVESTIGATION S

CONCERN KEYHORD C IIUMBER CAT CAT D LOC FL9B REPORT R-DESCRIPTION KEYHORD D

)

HI 100-023 EN 22600 N HBH YYYY SR LIGHTING FIXTURES AT H5NP ARE NOT PR NONCONFORMANCE T50212 REPORT OPERLY RESTRAINED AND CAGED TO PREVE CORRECTIVE ACTION NT THEN FROM BECOMING MISSILES OR SH ELECTRICAL 3

INGING MISSILES DURING SEISMIC EVENT LIGHTNING S.

CI HAS NO FURTHER INFORMATION.

ANONYMOUS CONCERN VIA LETTER.

I 1 CONCERNS FOR CATEGORY EN SUBCATEGORY 22600

)

.}

}

)

)