DOCKET NO.:
050-0325 UNIT: Brunswick 1 DATE: July 1988 COMPLETED BY: Frances Harrison OPERATIONS
SUMMARY
BRUNSWICK UNIT 1 Brunswick Unit 1 operated at a 60.45% capacity factor and a 73.15% availability factor for the month of July 1988. There were three power reductions and one off-line outage.
There are 1016 BWR and 160 PWR spent fuel bundles in the Brunswick Unit i fuel pool s
~ i f{,M 8808180167 880731 PDR ADOCK 05000324 R
PDC 3
. :=.- -
' C P & L 'C O,
PLANT PERFORMANCE DATA SYSTEM PAGE i
RUR DATE," 08/03/88 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIMf 10458:18 BRUNSWICK UNIT i DOCKET NO. 050-0325 COMPLETED BY FRANCES HARRISON TELFPHONE (919)457-2756 JULY 1988 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET)
(MUE-NET) 1 681 17
-12 2
416 18
-12 3
441 19
-13 4
489 20
-13 5
719 21
-14 6'
676 22 239 7
739 23 642 8
728 24 731 9
725 25 710 10 694 26 712 11 718 27 709 12 715 28 707 13 621 29 703 14
-15 30 701 15
-14 31 696 16'
-14 1.16 - 8~
.CP&L 'CO.
PLANT PERFORMANCE DATA SYSTEM PAGE i
RUA DATE '08/04/88 OPERATING DATA REPORT RPD36-000 RUN TIM $
15':17:34 BRUNSWICK UNIT i DOCKET NO. 050-0325 i
COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (919)457-2756 1.
UNIT NAME: BRUNSWICK UNIT i f0TES
- 2. REPORTING PERIOD: JULY 88 l
l 3.
LICENSED THERMAL POWER (MWT) 2436 l
l 4.
NAMEPLATE RATING (GROSS MWE) 867,0 i
1 5.
DESIGN ELECTRICAL RATING (NET MWE) 821.0 l
l 6.
MAX DEPENDABLE CAPACITY (GROSS MWE)' 8i5.0 l l
- 7. MAX DEPENDABLE CAPACITY (NET MWE) 790.0 4
8.
IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
- 9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE)
- 10. REASONS FOR RESTRICTION IF ANY:
THIS YR TO CUMUL MONTH DATE ATIVE
- 11. HOURS IN REPORTING PERIOD 744.00 5111.00 99695.00
- 12. NUMBER OF HOURS REACTOR CRITICAL 566.85 4234.52 65178.41
- 13. REACTOR RESERVE SHUTDOWN HRS
.00
.00 1647.10
- 14. HOURS GENERATOR ON LINE 544.27 4124.37 61992.00
- 15. UNIT RESERVE SHUTDOWN HOURS
.00
.00
.00
- 16. GROSS THERMAL ENERGY GEN. (MWH) 1165286.91 9553666.55 131533102.31
- 17. GROSS ELEC. ENERGY GEN. (MWH) 371000.00 3i29640.00 43239190.00
- 18. NET ELEC. ENERGY GENERATED (MWH) 355311.00 3026417.00 41571388.00
- 19. UNIT SERVICE FACTOR 73.15 80.70 62.18
- 20. UNIT AVAILABILITY FACTOR 73.15 80.70 i6:2.18
- 22. UNIT CAP. FACTOR (USING DER NET) 51.17 72.12 50.79
- 23. UNIT FORCED OUTAGE RATE
.00
.00 16.15
- 24. SHUTDOWNS SCHED. DVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH)
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION)- FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION i.16 - 9
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCXET NO.
050-0325 UNIT NAME B runswick 1 DATE August 1988 COMPLETED BY f rances _ Ha rri son REPORT MONTH July 1988 TELEPHONE 919- ?7-2756 I
l l
l l
l Method of I Licensee 1 i
i i
i i
i I Du ra t ion ll l
Shutting L Event i System l Componenti Cause & Corrective l
No. I Date i Type lifHours)
Reason 2 Down Reactor 3 Report No.1 Code 34 i Code 5 l
Action to Prevent Recu r rence I
i i
i 1
i i
i 188055 1880702 l F
I
.00 l
A 5
H I
l l Powe r reduct ion to pe rfo rm wa te r-1 I
I I
I i
1 l
l l
l box work on main condenser.
1 I
I I
I I
I l
I I
i i
i I
I I
I I
I I
I I
I i
1 I
I I
I 1
1 I
I I
I I
l' I
I I
I I
I I
I I
i 1
I I
I I
I I
I I-l l
l l
1 1
I i
i 1
I I
I I
I I
I I
I I
I 1
I I
I I
I I
I I
I I
I I
i I
I i
l i
I I
i 1
I I
I I
I I
I I
i l
l I
I i
1 I
I I
I I
I l
1 I
I I
I I
I I
I I
H I
I I
I I
I I
I i
i 1
I I
i 1
I I
I I
I I
I I
i 1
1 I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i i
i I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
l H
I I
i 1.
I I
I I
I I
I I
I l-1 I
I I
I I
I I
I I
I I
I I.
I I
I I
I I
I
-1 I
i l
i I
I I
I I
I I
l 1
I I
I i
1 I
I I
I H
I I
I l
I i
I I
i I
I I
I i
l l
I I
I I
i 1
l l
I I
I I
I I
l-1 I
I I
I I
'I I
I
(
l i
I I~
l i
I I
' I I
I I
I I
I I
I i
I 1
1 I
I l
i I
i i
l i
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i l
l l
l l
l-1 I
i l
I I
3 la 1
2 F - Admin 1 - Manual Exhibit G F - Forced A - Equip failure S - Sched B - Ma i n t o r te st G - Ope r e rro r 2 - Manual sc ram Instructions for Preparation C - Refueling
. H - Othe r 3 - Auto scram of Data Ent ry Sheet Licensee D - Regulatory restriction it - Continuations Event Report (LER) File E - Ope ra to r T ra i ning &
5 - Load Reductions (NUREG-0161)
License Examination 6 - Other 5
Exhibit 1 - Same Source r.
MSC/88-080 4
ii1iIIIIIiiIii1IiiIiIiIIIIIIIIIlIIiIlIIIi a
b 1
n n&
s e
ion o
e c
f tce ir6 n
o ail 1
r5 e
rLi e
a7 r
r 5k 8H2 er i
a F
c pt r
3i 9
s7 ivu a
ee) u 2
c8 C
p reR o
0 w 1 e5 tc e
PhE S
- s c4 cR r
SL 5 u iv n e
r
(
0 n e
a9 rt r
oy m
0 r u r1 rn o.
frt) a BJF9 oe fe tr1 S
Cv n
sno6 e
ni n E p1
&r OEEYE P
iol o e0 GiaR-1 NMTDN e
tn tt G
AA O so co tcatE t TNDDH ut ui iuDnR i E
EP a
ds br eU i b
ri hsoE( h ON LE i
m xn x
rs EI E
M c
en O
A wa 4
5 C
or Pt i,
Il1IlIIIIi IIlIlIIiIIIIIIIIl1IIIllIII t
s n
n e
so n5 m
ni o
a ot pe rmic md catu oo srad cue CC 1l snR S
Ii 1IilIIIlIIIiliIllIIIlIII 114I lIII aa i r N
uuotde O
m4 nntnah I
e aauoot T
te MMACLO C
8 sd U
8 yo D
9 sC E
1 123456 R
R ly iI1iilIIliIIilIIlil
(
IIiIIIIiI1IIIIIIi 3
.o E
u e
N W
J e
O s
t P
ntr r
eno o
D H
cep r
N T
i ve r
A N
LER e
O n r ire S
M l1 lIIIilIIIiIIiiiiIIiIIIIIIIIlIIIIIIiII N
3 meh W
T d pt O
R f
r AOO D
O ogo T
P nt U
E dic H
R ota FCH S
hte 5
tuR T
eh I
MSn N
w n n o o U
o it&t D
i
!l1iIIIIIilIiiIiIIIIIIiIIIIIIIIIIIIIIIlIi 2
.c a
i gn n
rni o
tim s
A sna a
et eix e
rs raE' R
ue r
li lIIIIiiIiiilIiIIl1II1' IIIIIIIIIIIIII f t yTe l
gr s
n i
o) a rnorn is roitoe tr 0
l atc ptel ai au 0
inuurL ro iH uif g e t
qa e e p Df
,lIliIIIIII1IIIIIIII EMHRO lIIIIlliIilIIIl4 1
e ABCDE p
F y
T 2
ll iiIIIiilI1iIIIii "
lIIIIIII1IIIIIIII lI l
e 5
t 0
a 7
d D
0 ad 8
.ce 0
l 8
rh 8
l' 1t l' IIiiiIliIIIiIlIiIIIiIIIIIlIIIIIIII oc 0
FS-6 8
.o 5
8 N
0
/
8 FS C
8 S
l1II1IIIIIiIIi1IIl1IIIlIIIiIIIIIlIIiIIIII 1
M y
,a..
-9 tI LI!
tl
i UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
050-0325 UNIT NAME B runswi ck I DATE AuquSt l988 COMPLETED BY f rances Harrison REPORT MONTH July 1988 TELEPHONE 919-457-2756 l
l l
l l
l Method of l Licensee I i
l i
I I
l l Du ra t ioni l
Shutting
.I Event l System l Component!
Cause & Corrective I
i No. I Date l Type lifHourst IReason 2lDown Reactor 3 Report No.1 Code 4 l Code 5 Action to Prevent Recu rrence l
I i
1 1
I I
I i
1 188057 1880710 l S
I
.00 1
B 1
5 I
I l
! Rod imp rovement.
1 I
I i
1 I
I I
1 1
I 1*
I I
I I
I I
I I
I I
I i
1 1
I I
I I
I I
I I
I ll l
1 1
I I
I I
I I
I I
I I
I I
I I
I I
I I
i i
l i
l I
i i
i I
I i
l i
I I
I I
I I
i l
i I
I i
i i
I i
i I
i i
i l
i l
i I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
' t i
1 1
I i
I I
I I-
'l i
i 1
l l
l l
l l
l 1
-l' 1
I i
l I
i I
I i
i i
1-1 I
I I
l i
I I
I I
I I
I I
I I
i 1
1 I
I I
I I
l 1
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
1 I
I I
I I
i 1
-1 I
I
.I-1 I
I I
I I
i I
I I
I I
l-1 I
I I
I I
I I
I-1 I
l I
l i
I I
I I
I I
I l-1 I
I I
' l i
I I
I I
I i
1 1
I
'l l
I I
I I
l l
.1 I
I I
I l'
l
-l l
l l
I I
I I
l l'
l.
l-
- 1 I
I I
I I
I I
I I
I I
I I
I I
i 1
1 I
.I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I
'l I
'l i
I I
I I
i 1
2 3
4 F - Forced A - Equip failure
'F - Admin 1 - Manual Exhibit G
'S - Sched 8 - Maint or test G - Ope r e rro r 2 - Manual sc ram Instructions for Preparation C - Refueling-H - Other 3 - Auto scram of Data Entry Sheet Licensee D - Regulatory restriction 4 - Continuations Event Report (LER) File E - Ope ra to r T ra ini ng &
5 - Load Reductions (NUREG-0161)
Licortse Examinatiott 6 - Other 5
Exhibit 1 - Sa me Sou rce e,
9 MSC/88-osO e
s r
UNIT SHUTDCWNS AND POWER REDUCTICMS DOCKET NO.
050-0325 UNIT NAME B runswi ck 1 DATE _ August 1988 COMPLETED BY F rance1_1ta rri son REPORT MONTH July 1988 TELEPHONE 919-457-2756 I
l l
l l
l Method of I Licensee l l
l l
l l
lDurationi i
Shutting Event l
System l Componenti Cause & Corrective i
1.
No. I Date Tvoe 1 (Hours) l Reason 2 Down Reactor 3 Report No.
Code 4 I Code 5 At:t ion to Prevent Recu rrence i
I i
I i
i 188059 1880713 i S
li 199.73 I A
1 1 1-88-017 I
l l
Unit shut down due to failure l
of HPCI valve 1-E41-FOO1.
I I
l l
l l
l l
.l i
I l'
i i
i V
i i
i i
i i
I ll l
i I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
i I
I I
I i
l i
i l
i I
I I
I I
I I
I I
i 1
1 1
I I
I I
I I
I I
l l
l l
8 I
I I
I l
1 1
I I
I I
I I
I I
I I
I I
I
'l l
i I
I I
I I
I I
I I
I I
I I
I I
i I
I I
I I
I I
I I
I I
i 1;
I I
I I
I I
I I
I 11 I
I I
i 1
1 I
I i
I i
H I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i 1
I i
I I
I I
I i
1 1
I I
I I
l I
I I
I I
I I
I I
I I
I I
I i
1 1
I i
l I
i I
I I
I I
I I
I I
I I
I I
I I
I-1 I
I I
I I
I I
I I
I I
l.
I I
I i
i l
i i
I i
l i
I I
l 1.
I I
I I
l I
I i
I I
I I.
I I
I I
I I
I I
I I
i l
I 4
I I
i I
I I
I 1
l l
I I
h l
I I
I I
I I
I I
I H
I I
I i
l 1
I i
1 1
I I
I I
i l
i l
1
.I I
I I
I I
I I
I I
I i
I l
l 1
1 I
i
~
1
. 2 3
4 F - Forced A - Equ ip fa i lu re F - Admin 1 - Manual Exhibit C S - Sched 8 - Maint or test G - Oper error 2 - Manual sc ram instructions for Preparation C - Refueling H - Other 3 - Auto scram of Data Entry Sheet Licensee D,- Regulatory restriction' 4 - Continuations Event Report (LER) File E - Ope ra tor T ra ini ng &
5 - Load Reductions (NUREC-0161)
License Examination..
6 - Other 5
Exhibit 1 - Same Source
, w.
G MSC/88-080' e
DOCKET NO.: 050-0324 UNIT: Brunswick 2 DATE: August 1988 COMPLETED BY: Frances 'arrison I
)
OPERATIONS
SUMMARY
I BRUNSWICK UNIT 2 I
i Unit 2 operated at a 64.98% capacity factor and a 71.47% availability factor for July 1988. There were three power reductions and one off-line outage.
There are 940 BWR and 144 PWR spent fuel bundles in the Brunswick Unit 2 fuel pool.
NOTE:
Corrected copy of April 1988 Report, Unit'2, on the number of reactor critical hours for the month and year-to-date is attached.
l
CP&L CO.
PLANT PERFORMANCE DATA SYSTEM PAGE 2
RUN.DATE 08/03/88 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIME 10i58:18 BRUNSWICK UNIT 2 DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON TELEPHONE (919)457-2756 JULY 1988 DAY AVG. DAILY POWER LEVEL DAY AVG. DAIL.Y POWER LEVEL (MWE-NET)
(MWE-NET) 1 776 17 593 2
721 18 764 3
720 19 767 4
726 20 767 5
738 21 767 6
777 22 603 7
777 23
-15 8
776 24
-13 9
757 25
-12 10 774 26
-12 11 773 27
-12 12 772 28
-13 13 772 29
-15 14 775 30
-16 15 409 31 29 16 691
-l 1.16 _...
.CP&L'CO,.
PLANT PERFORMANCE DATA SYSTEM PAGE 2
.RUR'DATE 08/04/88 OPERATING DATA REPORT RPD36-000 RUN TIME 15?.17:34 BRUNSWICK UNIT 2 DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (919)457-2756 1.
UNIT NAME: DRUNSWICK UNIT 2 l NOTES l
- 2. REPORTING PERIOD: JULY 88 l
l
- 3. LICENSED THERMAL POWER (MWT). 2436 i
I 4.
NAMEPLATE RATING (GROSS MWE)' 867.0 i
1 5.
DESIGN ELECTRICAL RATING (NET MWE). 821.0 l
l
- 6. MAX DEPENDABLE CAPACITY (GROSS MWE) 815.0 l l
- 7. MAX DEPENDABLE CAPACITY (NET MWE) 790.0 8.
IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
i
-9.
POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE)-
- 10. REASONS FOR RESTRICTION IF ANY:
THIS YR TO CUMUL MONTH DATE ATIVE ii. HOURS IN REPORTING PERIOD 744.00 5111.00 111719.00
- 12. NUMBER OF HOURS REACTOR CRITICAL 536.61 2027.99 69152.49
- 13. REACTOR RESERVE SHUTDOWN HRS
.00
.00
.00
- 14. HOURS GENERATOR ON LINE 531.72 1770.97 65017.15
- 15. UNIT. RESERVE SHUTDOWN HOURS
.00
.00
.00
- 16. GROSS THERMAL ENERGY GEN. (MWH) 12i5057.31 3095000.30 133180787.39
- 17. GROSS ELEC. ENERGY GEN. (MWH) 398215.00 1279205.00 43020876.00
- 18. NET ELEC. ENERGY GENERATED (MWH) 381941.00 1208992.00 41201579.00
- 19. UNIT SERVICE FACTOR-71.47 34.65 58.20
'20. UNIT AVAILABILITY FACTOR 71.47 34.65 58.20 21 '. UNIT CAP. FACTOR (USING MDC NET) 64.98 29.94 46.68
- 22. UNIT CAP. FACTOR (USING DER NET) 62.53 28.81.
44.92
- 23. UNIT FORCED OUTAGE RATE
.00' 14.65 13.80
- 24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):
- 25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OFfSTART UP 1
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACHIEVED INITIAL CRITICALITY l
INITIAL ELECTRICITY l
COMMERCIAL OPERATION L
1.16 - 9 r
,l
,i
\\
II IIIIIIiIiIIIIIII1IIIII1iIII l
llIIII s
a e
n v
ns os e
l on a
ie c
v tce ir6 n
ail 28 r5 e
e rLi e
7 r
n a
F c
8 Js7 2
er i
pt r
4k 9
vu t
ee) u 2c1 ic u
reR o
3iQw t t5 te o
PhE S
- s s c4 cR r
SL Qn u n -
e r
(
o 5 u g a9 rt d
oy m
rn n
frt) a 0 r u r1 BAF9 oe a
tr1 S
Cv sno6 e
t n E p1
&r n
o e0 OEEYE P
e GiaR-1 NMTBN e
m tt G
AA O so e
tcatE t
TNDDH ut v
iuDnR i
E EP a
o.
itrvN CI EL o
pg hsoE( i h
ON LE i
mn xn x
ii EI E
M c
t O
A ds 4
5 C
oe Rt Ii m1IIIIIIIIIIIIII1IIIII1lIIIIIIIIIIIII t
s n
n e
so n5 m
ni o
a ot pe rmic md catu oo sr ad CC cue ll snR IiIiI1IIIIIIIIlIIIIIiIIIIIilIIIIIIIlIIiII aa i r S
N uuotde O
m4 nntnah I
e aauoot T
te MMACLO C
8 sd U
8 yo D
9 SC E
1 123456 R
R ly iliIIIIIIIIlIIIIIIIIIIIIJ III IIlII ii1 w
3 o
E u
e N W
J e
O s
t P
ntr r
~
eno o
D H
iLER e
cep r
s N
T ve r
A NO n r ire S
M li h1IIIIIIIIiiIIII1II1iIIIIIiIIIIiIIIII N
3 meh W
T d pt O
R r r AOO D
O ogo r
T P
nt U
E dic H
R ota FGH S
hte 5
tuR T
eh MSn I
N w
n n U
o o o D
i i llllilIIIIIiIIIlII1I1II1iII1IIiIIIIIIIIII t&t 2
c a gn i
n rni o
tim s
B sna a
et eix e
rs raE R
ue r
lil1iiIIIIIlIIIIII1IiIIiiII11IIIIIIIII1iI l t yTe w
gr s n
i-o) arno rn is
- foitoe tr 0
l atc ptel ai au 0
i nuurL ro uH uirge D(
qaeep lI liI1IIIII1IIIIiIII1IIIIi1l11IIIIIIi1I
- EMRRO l
1
- - - ~-
ep S
ABCDE y
T 2 -
i1 liRiIiIII11IIIIIII1I1III1i11IIIIIIIiI l
e 2
t 0
a 7 d
D 0 ed 8
ce 0
8 rh 8
i1Il'IIiIII1IIIiIIII1I1III1ii1IIIIIII1I oc 0
ilI FS
. 7 8
o 2 8
N 0
/
8 FS C
w 8
S 1llI1IIIIiIII1iIIiIIIIIIiIII1IIiIIiIiiIlI 1
M
?
M
?
,?
l ll' w
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
050-0325 UNIT NAME Brunswick 2 DATE Auqust 1988 COMPLETED BY Frances Ha rri sof._
919-157-2756 REPORT MONTH July 1988 TELEPHONE 4
1 j
i i
l 1.
Method or l Licensee I,
l 1
l l
l l
l Du ra t ioni i
Shutting l Event System l Componenti Cause & Corrective l
l No. I Date i Type 1 (Hours) IReason 2lDown Reactor 31 Report No.
Code 4 1 Code 5 i
Action to Prevent Recu rrence 1-1 i
i i
i i
l i
188033 1 880715 i F
1
.00 l
A I
5 I
I l
I Reduce power due to tuv condensor l I
I i
1 l
l l
l l
l vacuum (2A circuisting water pump I 1
- 1 l
l 1
1 I
l l
l tripped due to clogged i nta ke I
l l
l 1
I l
l I
I sc reen).
I i
l I
I I
I I
I I
I l
l l
1 1
I I
I I
I I
I I
I I
I I
I I
I i
l l
1 1
I I
I I
I I
I I
I I
i I
I i
l I
I I
I i
I i
I l
i I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I l
I I
I I
I I
i 1
1 I
I I
i 1
1 I
i l
i I
I I
i I
I I
I A
I I
i 1
1 1
1 1
I l
i 1
1 I
I I
I I
I I
I t
i I
I I
I I
I i
l I
1 i
l i
I i
i i
i l
i I
I I
I I
I i
ll l
l t
i I
I I
I I
I l
l 1
1 I
I I
I I
I I
l l
l 1
1 I
I I
I i
l I
I I
I i
i i
i l
i i
i l
i l
i I
I i
l i
I I
I I
I l
i I
I I
I I
I I
l i
I I
I I
I i
1 l-1 I
I I
I I
I I
I I
I I
I I
I I
I i
1 1
I i
1 I
I I
I I
I I
1 1
I i
i i
l I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i 1
1 1
I I
I I
I I
I I
I I
I I
I I
I I
I i
1-1 I
I I
I I
I I
I I
I I
I I
I I
i 1
2 3
4 F - F o rced A - Equ ip fa i l u re F - Admin 1 - Manual Exhibit C S - Sched B - Maint or test C - Ope r e rro r 2 - Manual sc ram Instructions for Preparation C - Refueling H - O the r 3 - Auto scram or Data Entry Sheet Licensee D - Regulatory restriction 4 - Continuations Event Report (LER) File E - Ope ra to r T ra i n ing &
5 - Load Reductions (NUREG-0161)
License Examination 6 - Other 5
Exhibit 1 - Same Source MSC/88-060 o
O
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
050-0325 UNIT NAME Brunswick 2 DATE _ August 1988 COMPLETED BY f rances.Ha rri son REPORT MONTH July 1988 TELEPHONE 919-457-2756 l
l l
l l
l Method of l Licensee l l
l 1
l l
l l Du ra t ion !
I Shutting l Event l System 1 Componenti Cause & Corrective 1
l No. I Date l Type lifHours) 1 Reason 21Down Reactor 31 Report No.I Code 4 1 Code 5 l
Action to Prevent Recu rrence i
I i
i i
i i
l i
i l
i 188034 1880716 i F
l
.00 i
B l
5 l
l l
l Reduced powe r for PT-14.2.1, 1
I i
l l
l l
l l
l 1 Single Rod Scram Insertion i
I l
l l
l 1
l l
l l Timcs and Ci rculating Water I
l l
l l
l l
l l
t l Intake Traveling Screen Repa i r I
I i
l i
l 1
1 1
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i I
I I
I I
I I
I I
l I
I I
I I
I i
1 l
l l
l 1
1 I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
i l
l I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
l 1
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
l i
I I
I I
I I
I I
I I
I I
I I
I l
i 1
I I
I i
1 I
I I
I I
I I
i I
I I
I I
I I
I I
I I
I l
1 I
I I
I i
l 1
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
1 1
I I
I I
I I
I I
I I
I I
I I
I i
l i
l I
I i
i l
i I
I I
I I
I i
i 1
1 I
I i
1 1
I I
I I
I I
I I
I I
I I
I I
i 1
1 1
I I
I I
I i
1 1
1 1
I I
I I
I I
I I
i 1
i I
I I
I I
I I
I I
I I
I I
I I
I l
l l
l l
l l
1 l
l l
1 2
3 4
F - Forced A - Equip fa ilure F - Admin 1 - Manual Exhibit G S - Sched B - Maint or test G - Ope r e rro r 2 - Manual sc ram Instructions for Prepa ra tion C - Refueling H - Other 3 - Auto scram of Data Entry Sheet Licensee D - Regulatory restriction 4 - Continuations Event Report (LER) File E - Ope ra to r T ra i n ing &
5 - Load Recuctions (NUREG-0161)
License Examination 6 - Other 5
Exhibit 1 - Same Source MSC/88-080 O
w
S UNIT SHUTDOWNS AND PCNER REDUCTIONS DOCKET NO.
050-0325 UNIT NAME Brunswick 2 DATE August 1988 COMPLETED BY Frances Ha rrison REPORT MONTH July 1988 TELEPHONE 919-457-2756 l
l l
l l
l Method of l Licensee 1 l
l l'
i l
l IDu ra tioni l
Shutting l Event l System l Componenti Cause & Corrective l
l ~ No. I Date i Type 1 (Hours) l Reason 2 Down Reactor 3 Repo rt No.
Code 4 Code 5 Action to Prevent Recurrence i
I i
l i
i 188037 1880722 i S
il 212.28 l 8
ll 1
l l Maintenance outage to work on l
l I
l l
l l
l l
l l HPCI, resctor reci rculation, RHR, I i
. I i
l l
l l
I I
I and other ma intenance items.
I I
I I
I I
I I
I I
I I
I
'l i
i I
I I
I I
I i
1 I
1 1
I ll l
I I
I I
I I
I I
I I
I I
I I
I I
I I
I l
l l
1 1
I I
I I
I I
I I
I l
l I
1 1
I I
I I
I I
I I
I i
i I
I l
i I
I i
1 1
I I
I I
l i
i 1
1 I
I I
I i
l i
i i
I i
i l
I i
I
.I I
I I
l I
I I
I I
i 1
1 1
1 f
i 1
1 I
I I
I I
i
- 1 I
I
~l i
I I
I I
I
' I I
I I
I I
i 1
1 I
I l
i I
i 1.
I I
I I
I I
- 1 I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
i i
I I
l i
I I
I i
i i
I I
I I
I I
I I
I I
I I
I I
I I
I I
I i
1 1
1 I
I l
i I
I I
i i
i I
I I
I l
i I
I I
.I I
.I-1 I
i l
l l
1 I-1 I
I I
I I
I i
1 I
I I
I I
I I
I I
I I
-1 I
i l
I I
I I
I I
I I
I I
I I
I I
I l
I I
I I
I i
l I
i i
' I i
i I-1 I
I I
I I
i I
I I
.I i
l I
i l
l I
I 1
1 I
I I
l i
I I
I i
i I^
l i
I I
I I
I I
.I i
i l
I I
I I
I l
l 1
2 3
4 F - Forced A - Equ ip ra i t u re F - Admin 1 - Manual Exhibit C S - Sched B - Maint or test' G - Oper error 2 - Manual sc ram Instructions for Preparation
'C - Rerueling H - Othe r 3 - Auto scram or Data Entry Sheet Licensee D - Regulatory restriction 4 - Continuations Event Report (LER) File E - Ope ra to r T ra i ni ng &
5 - Load Reductions (NUREG-0161)
License Examination 6 - Other 5
Exhibit 1 - Same Source MSC/88-080 t
, -