Amend 26 to License NPF-18,changing Tech Specs to Incorporate Instruments for Suppression Pool Water Level & Water Temp Monitoring at Remote Shutdown Panel
ML20206Q643
Person / Time
Site: LaSalle 
(NPF-18-A-026, NPF-18-A-26)
Issue date: 08/29/1986
From: Adensam E
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20206Q648 List:
References
NUDOCS 8609050119
Download: ML20206Q643 (5)


Text

UNITED STATES

[

k NUCLEAR REGULATORY COMMISSION r,

.y waswiscrow, p. c. rosss

%*****/

COMMONWEALTH EDISON COMPANY DOCKET NO. 50-374 LA SALLE COUNTY STATION, !! NIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 26 License No. NPF-18 1.

The Nuclear Reaulatory Commission (the Commission or the NRC) has found that:

A.

The application for amendment filed by the Commonwealth Edison Company (the licensee), dated July 3, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's reculations set forth in 10 CFR Chapter I; R.

The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Commission; C.

There is reasonable assurance: (1) that the activities authorized by this amendment can be conducted without endangerino the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's renulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

l 2.

Accordinoly, the license ie. amended by changes to the Technical Specifica-tions as indicated in the enclosure to this license amendment and paragraph l

2.C.(2) of the Facility Operatino License Nn. NPF-18 is hereby amended to read as follows:

i (2) Technical Specifications and Environmental Protection Plan 1

i The Technical Snecifications contained in Appendix A, as revised through Amendment No. 26, and the Environmental Protection Plan contained in Appendix R, are hereby incorporated in the license. The licensee shall 4

operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

8609050119 860829 I

PDR ADOCK 05000374 PDR l

p i

-. - _ _. ~

. ~

3.

This amendment is effective upon startup following the first refueling.

l FOR THE NitCLEAR REGUL'ATORY. COMMISSION Eu Elinor G. Adensam, Director BWR Pro,iect Directorate No. 3 Division of RWR Licensing

Enclosure:

Chanaes to the Technical Spicifications Date of Issuance: August 29, 1986

b.

ENCLOSURE TO LICENSE AMENDMENT NO. 26 FACILITY OPERATING LICENSE NO. NPF-18 DOCKET NO. 50-374 Replace the following pages of the Apcendix "A" Technical Specifications with the enclosed paces. The revised paces are identified by Amendment number and contain a vertical line indicating the area of chance.

REMOVE INSERT 3/4 3-67 3/4 3-67 3/4 3-68 3/4 3-68 4

. ~,, _.,

_,_,,,__.y

~~

TABLE 3.3.7.4-1 REMOTE SHUTDOWN MONITORING INSTRUMENTATION MINIMUM INSTRUMENTS INSTRUMENT OPERABLE 1.

Reactor Vessel Pressure 1

i 2.

Reactor Vessel Water Level 1

3.

RHR Flow 1

4.

RHR Service Water Flow 1

5.

RHR Service Water Temperature 1

6.

RCIC Flow 1

7.

RCIC Turbine Speed 1

8.

Suppression Pool Water Level 1

9.

Suppression Pool Water Temperature 1

i 1

i i

i LA SALLE - UNIT 2 3/4 3-67 Amendment No. 26 l

TABLE 4.3.7.4-1

  • +

REMOTE SHUTDOWN MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS CHANNEL CHANNEL INSTRUMENT CHECK ~

CALIBRATION 1.

Reactor Vessel Pressure M

R 2.

Reactor Vessel Water Level M

R 3.

RHR Flow M

R 4.

RHR Service Water Flow M

R 5.

RHR Service Water Temperature M

R 6.

RCIC Flow M

R 7.

RCIC Turbine Speed M

R 8.

Suppression Pool Water Level M

R 9.

Suppression Pool Water Temperature M

R 8

'l LA SALLE - UNIT 2 3/4 3-68 Amendment No. 26