April 7, 1987~

4

't Docket No. 50-508-

- Mr. D. W. Mazur, Managing Director Washington'Public Power Supply System Post Office Box 968 3000 George Washington Way Richland, Washington 99352

Dear Mr.! azur:

t M

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATI0i1 - WNP-3 S0IL

~

STRUCTURE INTERACTION ISSUE

~

In conducting our review'of your submittals pertaining to the WNP-3 Soil' Structure Interaction-Deconvolutian issue,'we find that we need the additional information identified in the enclosure to continue our review.

  • In order for us to maintain our review schedule, your response.is requested within,90 days of your receipt of this letter.

The reporting and/or recordkeeping requirements contained in this letter affect.

fewer than ten respondents; therefore, OBM clearance.is not required under P.

L.96-511.

1 Please contact us if you have any question concerning this request.

Sincerely, Orisleal M W Robert S. Lee, Project Manager-PWR Project Directorate No. 7-Division of PWR-Licensing-B

Enclosure:

As stated cc: See next page on-4/2f/87 4/ /87 i

8704090204 870407 PDR ADOCK 05000508 A

PDR

. s Mr. D. V. Mazur WPPSS Nuclear Project No. 3 Washington Public Power Supply System (WNP-3)

CC*

Mr. Charles B. Brinkman, Manager Mr. G. C. Sorensen, Manager Washington Nuclear Operations Regulatory Programs Combustion Engineering, Inc.

Washington Public Power Supply 7910 Woodment Avenue Sutie 1310 System Bethesda, Maryland 20814 Post Office Box 968 3000 George Washington Way Nicholas S. Reynolds, Esq.

Richland, Washington 99352 DeBevoise & Liberman 1200 Seventeenth Street Washington, DC 20036 G. E. Doupe, Esq.

Washington Public Power Supply System 3000 George Washington Way Richland, Washington 99352 Mr. Curtis Eschels, Chairman Energy Facility Site Evaluation Council Mail Stop PY-11 Olympia, Washington 98505

~

Mr. Douglas Coleman 4

Washington Public Power Supply System P. O. Box 1223 Elma,. Washington 98541 Mr. William Ang Region Inspector /WPPSS 3/5 U.S. Nuclear Regulatory Commission 1450 Maria Lane - Suite 210 Walnut Creek, California 94596 Regional Administrator, Region V U.S. Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, California 94596 Mr. Eugene Rosolie, Director Coalition for Safe Power 408 Southwest Second Avenue Portland, Oregon 97204

-.,,...~

ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION - WNP-3 1.

With respect to deconvolution calculations:

a.

Provide plots of the response spectra at the foundation level and at plant grade together with comparisons with the design input.

b.

Provide comparisons of peak shear strains computed by SHAKE with available rock stiffness and camping data.

2.

With respect to the finite element calculations:

a.

Provide calculations from the finite element static calculations used to generate the embedment spring stiffness in the horizontal and vertical directions.

b.

Provide comparisons of the base and the sidewall interaction springs in the horizontal, vertical and rocking modes, c.

Provide computer models and output used for both NASTRAN and IMAGES-3D analyses, d.

Provide analyses to demonstrate that proper sidewall interaction springs can be obtained by fixing nodes along the basemat.

e.

Provide justification for the sidewall damping magnitudes which was used.

f.

Provide justification for the use of static analyses in place of frequency dependent sidewall interaction coefficients.

g.

Provide comparisons of sidewall interaction coefficients with available analytical approaches.

h.

Provide verification procedures used for IMAGE-30 code.

3.

With respect to the half-space seismic models:

a.

Provida a comparison of the finite element finite boundary calculations with the half-space approach.

b.

Provide descriptions of the computer program used to compute the seismic response.

c.

Provide the computer output used to generate the floor response spectra.

~~^

i g.

.1

'D' DISTRIBUTION.

1-

-E 6 NRC PDR

'PBD17 Reading-F. Miraglia 0GC Bethesda J. Partlow-BGrimes-ACRS'(10)'

'EJordan T. Michels-t Jean Lee GWKnighton Robert S. Lee