Ack Receipt of Util Requesting Relief from Action Statement Requirements of Tech Spec 3.4.6.1.Enforcement Discretion Granted for Two 8 H Periods for Repair of Containment Particulate & Gaseous Radioactivity Monitor Sys
ML20205T293
Person / Time
Site: North Anna  
Issue date: 10/28/1988
From: Ernst M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 8811140202
Download: ML20205T293 (1)


Text

_ _ _ _ _ _

Octob2r 28, 1988 Virginia Electric and Power Company 8

A h

vATTN: Mr. W. R. Cartwright, Vice President,

//

Nuclear Operations P. O. Box 26666 Richmond, VA 23261 Gentlemen:

SUBJECT:

ENFORCEMENT DISCRETION FOR NORTH ANNA POWER STATION UNITS 1 AND 2 DOCKET NOS 50-338 AND 50-339 This letter acknowledges your letter (serial no.88-706) of October 24, 1988, requesting relief from the action statement requirements of Technical Speci-fication (TS) 3.4.6.1.

In a telephone conversation between Mr. B. Wilson of my staff and Mr. G. Kane of your staff on October 21, 1988, you were informed that enforc' ment discretion was granted for two eight-hour periods during which the containment particulate and gaseous radioactivity mon. coring systems would be repaired on each plant.

After each eight-hour period for repair, if necessary, the Action Statement of the applicable TS would be complied with, it was our understanding that during tre repairs, several compensatory neasures would be in effect.

The measures consist of an increase in frequency of reactor coolant system (RCS) teak rate calculations to once per eight hours, and frequent monitoring of containment and RCS parameters which would include containment temperature and huidity, containment sump level and flow rate, and RCS makeup and letdown flow rates, i

If your understanding differs from the above, please contact us.

l Sincerely.

Original Signed by J. Philip Stohr /for Malcolm L. Ernst Acting Regional Administrator cc: 4. E. Kane, Station Manager tE. E. Hardwick, Manager - Nuclear Programs and Licensing Corrnonwealth of Virginia bec: M'[C Resident Inspector DRS Technical Assistant Docurent Control Desk is t g w$ wf z

~

ee,1, _ e1 _

/

gos Acockoscopps u

1 l

R'l ORP RII 10 R 1:QRP R I I.

A RII:DRP RII:0RP Ms20t b FCant7e11 ewik h a en:t lhetMV JSd hIr l

s 10/ 6/88 10/O,f88 10/ W88 go /

10/rz/88 10/4j/88 10$'88 A

- - - - - - - - -