ML20205M312

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 860119-0313
ML20205M312
Person / Time
Site: Palisades Entergy icon.png
Issue date: 04/11/1986
From: Paperiello C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20205M307 List:
References
50-255-86-05, 50-255-86-5, NUDOCS 8604150172
Download: ML20205M312 (1)


Text

. .

l i

NOTICE OF V10_L,A_TI,0,N Consumers Power Company Docket No. 50-255 ,

1 l

As a result of the inspection conducted on January 19 through March 13, 1986, and in accordance with the " General Policy and Procedures for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1985), the following violation was identified:

l Palisades containment testing Technical Specification Surveillance Requirement 4.5.1.(a).2 and 3 state, in part, that Integrated Leak Rate Tests shall be perforned without any leak detection surveys or leak repairs insnediately prior to or during the test, except as noted below . . . . Major leak repairs, if necessary to permit the integrated leak rate test, shall be preceded by local leakage measurements. The local leakage differences, as a result of repair, shall be corrected to P tand added to the final integrated leak rate test 1 result to determine the subsequent retest schedule.  ;

Contrary to the above, the licensee has been performing containment isolation l

valve leak testing and isolation valve repair prior to Type A tests without l adding the local leak rate test differences to the final integrated leak rate i test results to determine the subsequent retest schedule.

l This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice of Violation, a written statement or explanation in reply, including for each violation:

(1) corrective action taken and tFe results achieved; (2) corrective action to be taken to avoid further vic h ions; and (3) the date when full compliance will be achieved. ConsideN tion may tee given to extending your response time l

for good cause shown.

l

. b 2 - -...... _- ....-

Carl. J//Paperfello, Director l Dated /~

Division of R(actor Safety

/

8604150172 860411 PDR ADOCK 05000255 G PDR

. - .