ML20205H499

From kanterella
Jump to navigation Jump to search
Forwards Requested Info on Design Baseline & Verification Program Status of post-mod Test Review.Util in Process of Establishing More Formal Restart Test Program to Better Address All Required Restart Testing
ML20205H499
Person / Time
Site: Sequoyah  
Issue date: 03/23/1987
From: Gridley R
TENNESSEE VALLEY AUTHORITY
To: Ebneter S
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM), Office of Nuclear Reactor Regulation
References
NUDOCS 8704010079
Download: ML20205H499 (25)


Text

.

TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 374ot SN 157B Lookout Place MAR 281987 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Office of Nuclear Reactor Regulation Washington, D.C. 20555 Attention:

Mr. Stewart Ebneter In the Matter of

)

Docket Nos. 50-327 Tennessee Valley Authority

)

50-328 SEQUOYAH NUCLEAR PLANT (SQN) UNIT 1 - STATUS OF POSTMODIFICATION TEST (PMT)

REVIEW During the NRC/TVA Restart and Stello Plan Key Issues Schedular Review Meeting of February 5-6, 1987, a presentation was made on the Design Baseline and Verification Program (DBVP) review of PMTs performed at SQN. After the presentation, NRC staff members requested that a submittal be prepared by TVA to address the disposition of the PMTs determined to be inadequate by the PMT review. The requested information is provided in the enclosure.

I would like to point out that we are in the process of establishing a more formal restart test program at Sequoyah to better address all required restart testing. We are patterning our program to incorporate the better features of the Davis-Besse program. We will be willing to discuss additional details af ter the program development is complete (currently scheduled for mid-May).

We have also obtained the services of key members of the Davis-Besse team to help us implement this program in a conscientious, coherent fashion.

If you have any questions, please get in touch with M. R. Harding at 615/870-6422.

Very truly yours, TENNESSEE VALLEY AUTFORITY 1

R. Gridley, Director Nuclear Safety and Licensing Enclosure ec: See page 2 8704010079 870323 PDR ADOCK 05000327 4)

\\g An Equal Opportunity Employer i

. U.S. Nuclear Regulatory Comission ER 23 E cc (Enclosure):

Mr. G. G. Zech, Director TVA Projects U.S. Nuclear Regulatory Comission Region II 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323 Sequoyah Resident Inspector Sequoyah Nuclear Plant 2600 Igou Ferry Road Soddy Daisy, Tennessoa 37379 r

L I

l 1

J j

i 2

I.

i f

ENCLOSURE i

REQUESTED INFORNATION ON DBVP PNT REVIEW NRC/TVA RESTART AND STELLO PLAN KEY ISSUES SCHEDULAR REVIEW NEETING ON FEBRUARY 5-6, 1987 As requested in the subject meeting TVA has compiled the items from the DBVP PNT review which require additional data to satisfy-PNT. verification. The attached data represents the items to date for which the determination has I

been made that the Engineering Change Notice (ECN), Field Change Notice (FCN),

i or Workplan (WP) documented testing is inadequate. The data is presented in two groups: Table 1 contains the items for which other documented testing or I

operational activities have satisfactorily verified the functional operability for restart of the affected component, subsystem, or system, since the modification; Table 2 contains the items which were identified by the Division of Nuclear Engineering (DNE) as requiring retest.

By unit 2 restart, DNE will have reviewed all unit 2 and acommon ECN/FCN modification packages which were incomplete at, or initiated since, issuance of the unit 2 operating license and are associated.with the 37 systems or j

portions of systems necessary to mitigate the Final Safety Analysis Report 1

(FSAR) Chapter 15 postulated events.

As part of this review, all of the l

above-mentioned ECN/FCN packages which are to be implemented or partially implemented at unit 2 restart will have been reviewed to determine if the t

4 modifications were or will be adequately tested'to verify the functional operability for restart of the modified components, subsystems, and systems.

1 The review consists of an evaluation of the ECN/FCN documentation and the i

I implementing WP documentation to fully assess the scope of the implemented or proposed modification. The implementation documentation is then reviewed'to 1

evaluate the adequacy of the documented PNT.

If this review yields PNT l-inadequacies, the review is expanded to other plant programs in an attempt to locate sufficient documentation to satisfy the need for verification of i

functional operability for restart.

If the documentation review fails to disclose the existence of documented evidence which adequately confirms functional operability for restart after the modification activities, additional testing is specified and added to the

{'

punchlist as a restart prerequisite. These review results are also documented in the appropriate DBVP System Evaluation Reports (SYSTERs).

[

The PNT evaluation is accomplished through the implementation of the following i

DBVP elements:

Sequoyah Engineering Procedure (SQEP)-12. " Procedure for 4

Evaluating Engineering Change Notice and Field Change Notice Documents,"

p SQEP-14, " Assembly and Evaluation of Electrical Test Results." SQEP-51, l

" Procedure for Evaluation of Changes for Effect on Piping Vibrations and i

j Testing Requirements," and DBVP Directive DBVP-D-86-0006, " Evaluation of ECNs for Effect on Piping Vibration Functional Testing."

4 i

4 I

i f,_

. _, _ _ _ _ _ - _ _. _. _ _ _. _ _. ~, _. - _ _ _ _ _ _, _ _.

. In summary, the program described above causes every implemented or partially implemented (at restart) ECN and its associated WPs to be reviewed by each technical discipline (civil, electrical, mechanical, and nuclear), such that all applicable functional testing aspects are considered.

PMT review guidelines are used by the disciplines in their respective evaluation.

As part of the DBVP efforts, the DBVP System Engineer (SE) has the overall responsibility for the equipment in his assigned system.

In this capacity, the SE has the responsibility to ensure PMT is adequately addressed or identified as a restart prerequisite in the punchlist.

The SE's evaluations and conclusions are reviewed by an independent, equally qualified individual as part of the ECN checklist (SQEP-12) development and review process.

A further review is conducted by an independent reviewer, a Senior Level Engineer (SLE), and the DNE review board as part of the SYSTER review and approval process as described in SQEP-16, " Procedures for System Evaluation and Development of System Evaluation Report," and SQEP-31, "DNS Review Board."

By restart, the DBVP program will have reviewed all implemented and partially implemented (at restart) design changes completed between the issuance of the operating license and the implementation of SQEP-13. " Procedure for Transitional Design Control Process." The postmodification testing aspect of each of the changes is evaluated as an integral part of the DBVP process.

This process is adequately comprehensive to reveal all postmodification testing deficiencies in design changes implemented since issuance of the operating license.

The overall safety significance of the review findings to date is minimal.

For the items listed in table 1, there is no significant operability concern since a later program test has demonstrated functional operability for restart. For the completed items listed in table 2, safety reviews were performed by the Plant Operations Review Staff (PORS) of the deficiencies identified by DNE.

To date, one Potentially Reportable Occurrence (PRO) report was generated as a result of the PORS review, and it was determined to be not reportable (PRO-1-87-041).

Another review is performed af ter the retest is completed to evaluate any test deficiencies for safety significance.

To date, no retest deficiencies have been identified which would indicate that the modification was improperly or incorrectly implemented. Two of the items yet to be retested have Significant Condition Reports (SCRs) generated on them.

SQN EEB 8515 was determined to not be reportable, and SQN NEB 8708 has not yet been issued by DNE.

l l

t I

rage r.o.

1 01/01/80 TABLE 1 POSTt10DIFICATION TESTING ECN RETEST Surit1ARY

[

CR OR RESULTS SYS DOC REASON FOR RETEST PROGRArt IDENTIFICATION (if available)

The following are program tests (St etc.), which fulfill the post-modification ratest requirements.

1 FCN TEhr1-10672 SI cates were given in WP.

No data sheets Located a copy of later SI ACCEPTABLE found for dates given for 38 of the performed and copy of data BBS 870219 012 anstruments anvolved.

sheets to show anstruments are I

within tolerance and can l

perform their safety function.

3A FCNTENr1-10672 SI dates were given in WP.

No data Located a copy of later SI ACCEPTABLE l

sheets found for dates given for 28 performed and copy cf data B28 870226 038 l

Instruments involved, sheets to show instruments are within tolerance and can perform thetr safety function.

33 2942 No test documentatson in WP-S1408.

Ualves were functionally HCCEPTABLE tested per SI-166.4 with later 828 870219 038 dates. Also SI-166.1.

I I

33 2918 No test documentation in WP-S1315.

Acceptable results obtained ACCEPTABLE during performance of B28 870219 008 SI-166.6.

M 2961 No test documentation in WP-S1573.

Acceptable results obtained ACCEPTABLE during performance of SI-166.1 B28 870219 008 and SI-166.3.

38 LS457 Records of WP-SSO3 did not contain Ualve Located SI-166.6 dated after ACCEPTABLE i

l Stroke Times or Documentataan.

the completion of work for B28 87021S 008 verification of stroke times.

I l

32 2S79 Valves modafaed under WP-S1385 were not Additional document search ACCEPTABLE functionally tested, revealed SI-166.6 was B28 870211 122 performed on valves modified under WP-51385 and documented l

I as having verafted stroke times acceptable. This information verified ECN 2973 completion.

32 LS274 WP-104BS documents that air valves 1836 &

Additional search obtained ACCEPTABLE 1935 were proven functional per SI-1Tt.2 copy of SI-1Tt.2 documented as B28 870211 122 performance of SI was not documented.

performed successfully.

rags ho.

e 01/01/80 TABLE 1 POSTnODIFICATION TESTING ECN RETEST SunnARY OR OR RESULTS SYS COC REASON FOR RETEST PROGRAn IDENTIFICATION (if available) 1 l

32 L6175 UP-11151 does not document setpoint change Calibration cards found for ACCEPTABLE to 80 PSIG on PS-32-62 and PS-32-88.

PS-32-62 & 88 respectively, B28 870211 122 verifgtng setpoint change to 80 PSIG. Testang of mods performed under tup 11151 are therefore acceptable.

't 3 2003 uP unavatlable.

Test results accepted per ACCEPTABLE SI-166.4.

B28 870205 094

  • t 3 58S8 WP-11227 references SI completion for SI data sheets (SI-166.1 and ACCEPTABLE follouang valves, no data sheets.

SI-166.4) found for subsequent 828 87020S 094 2-FCV 't3-2,-22,-75 testing:

2-FCu 't3-34 2-FCu-43-2,-22,-75 2-FCu 't3-11 2-FCu 't3-34 2-FCu 't3-11

't3 2S 12 Functional testing was not included in the SNPII No. 10 cable inspection ACCEPTABLE workplan.

cards were used as well as B28 870211 118 SI-207 SI-166.1, SI-166.*t and SI-86.

46 LS't90 Work plan testing did not show relau TDPB (WR) B-201496, nR R-302196, ACCEPTABLE packed up, feed pump turbine trapped on and (WR) B-132039/ (WR)

B28 870211 118 electronic overspeed or ventilation fan is B-21262't veraf ted performance, operable.

61 LSBSS SI-166.6 data sheet was not found for Subsequent SI-166.6 data sheet ACCEPTABLE 2FSu-61-SS, 110, 1S2, 194.

verafted performance.

828 870103 001 62 LS881 51-166.6 data sheet not found for Subsequent SI-166.6 data sheet ACCEPTABLE 2FCu-62-77.

verafted performence.

B28 870226 068 62 L6521 SI-166.6 data sheet not found for Subsequent S1-166.6 data sheet ACCEPTABLE 2-FCu-62-61.

verified performance.

828 870226 068 63 LESS2 SI-166.6 data sheet not found for Subsequent SI-166.6 data sheet ACCEPTABLE 2-FCu-63-71.

verified performance.

828 870226 11't 67 ISSO Work plan could not be located.

Test results verafted per ACCEPTABLE SI-166.1 and SI-166.3.

B28 870219 007 67 205't Functional testing not addressed or Functional testing accepted ACCEPTABLE performed in work plans.

per SI-166.21 and SI-166.1.

B28 870219 007 67 22S7 Functional testing not addressed or Functional testing accepted ACCEPTABLE performed in work plan.

per S!-166.21.

B28 870219 007

-.. _ _ -. _ ~ _ _ _.

Page No.

3 01/01/80 TABLE 1 POSTt10DIFICATION TESTING ECN RETEST SunnARY OR OR RESULTS SYS DOC REASON FOR RETEST PROGRAn IDEt4TIFICATION Cif available) 68 2278 Prerequisite work for preop W-1.2A Functionally tested under ACCEPTABLE completed and verified under WP-53Y1 with preop W-1.2A.

B28 870226 067 no functional test.

68 2611 nodsfied foxboro racks and added Functional testing ACCEPTABLE anstrumentation. No functional testing calibration, and loop B28 870226 067 completed.

verifications completed per ECN-L63S't WP-1175't R1 and Int-SS CC12.1.

68 2360 Instrument range changes completed per Instruments recalibrated and ACCEPTABLE WP-92Ti.

Documentation changes only, verified per SI-ISS. Int-68.

B20 870226 067 68 5159 Physical modification completed under Functional testing completed ACCEPTABLE WPS175, no evidence of functional testing per Int-68 R10.

B28 870226 067 in WP.

I 68 5873 WP's included signatures for verification.

Testing included SI-70, ACCEPTABLE but did not reveal testing results for RID SI-70.2, and Int-68.

B28 870226 067 performance.

Calibration cards from recent work were found in plant records.

68 SS71 Testing per WP was adequate however, test Lator records located show ACCEPTABLE records could not be located for stroke performance of S1-166.6, which B28 870226 067 time testing.

vertfled stroke time testing of the valves.

68 FCN Tera 1-10672 WP referenced SI data sheets could not be Located later SI data sheets ACCEPTABLE found for 76 of the instruments involved.

to show instruments are within B20 870226 067 tolerance and function properly.

68 LS536 Workplan testing was adequate, but Reca11bration of 2-PT-68-68 ACCEPTABLE deficiency was noted.

The head dafference was accomplished and B2S 870121 052 resulting from the relocation of documented per ratest 2-PT-68-68 was not included in the resolution package RIt1S calabration.

S53-870119-891.

Review of this package showed no further testing is necessary.

68 LSS37 WP-9483 stated that RTD*s were verified Additional information was ACCEPTABLE functional, but did not state how this was obtained from chart recorder B20 870226 067 verified.

traces for affected RTD's.

Examination of the traces reveal the affected RTD's measures temperature in the range of 100F to 120F, thus demonstrate continuity thru RTO circuitru.

s

-.- ~

r eges F.o.

01/01/80 TABLE 1 POSTP10DIFICATION TESTIrJG ECr4 RETEST SUT1T1ARY OR OR RESULTS SYS DOC REASON FOR RETEST PROGRAt1 IDEt4TIFICATION (if available) 68 L5662 WP-10224 dad not reference any test Calorimetric data sheets were ACCEPTABLE documents which vertfy operability of the found, which show the B28 870226 067 affected RID's.

temperature of the affected RTD's as measured in the racks. Also, the equivalent volts & ohms are shown for the temperatures measured.

68 L6't07 Results of SI-166.6 are not provided in Copy of results of performed ACCEPTABLE WP-11BO7, although performance of SI-166.6 SI-166.6 was found and B28 870226 067 as verafted as acceptable by sagnatures in attached to ECF4 review. Stroke the WP.

times were found to be acceptable.

SI-166.4 results were located, which verify the local & remote stroke time and valve position lights are acceptable.

68 L64SS WP-11865 revealed onig 2 tests were Later results of stroke test ACCEPTABLE performed, a functional test and a stroke

( S I-166.*t ) for affected valve B28 870226 067 time test per SI-166.'t.

Only the results indicate local & remote stroke cf the functional test were vertfaed times are acceptable.

acceptable by the cognizant engineer.

70 1690 Functional testing of valves did not SI-166.'t performed at a later ACCEPTABLE anclude stroke time.

data shows valve stroke times B28 870218 006

& verifles operability.

70 2890 no functaonal test performed after SI-2't7.1008 verifles valve ACCEPTABLE modafacataan, operabilitu.

B28 870218 006 l

72?

2961 Documentation of functional & SI-166.6 Later functional & SI-166.6 ACCEPTABLE testing was not found, testing was performed.

828 870211 119 Pt L65't 3 SI-166.'t data sheets were not found.

Later SI-166.*t was performed ACCEPTABLE and is acceptable.

B28 870211 120 1

77 2603 F4o WP's or functional test could be found SI-166.'t was performed later ACCEPTABLE I

an thzs ECN.

to demonstrate the functional B28 870117 *t72

(

operability of valves after modification.

l 77 LSatS7 no functional test documentation could be SI-166.6 and SI-166.1 was ACCEPTABLE found to verify stroke time, at time of WP performed later on valves in B20 870117 472 performance.

UP-9503.

This later testing demonstrated the functional operab111tu and stroke tames of valves.

Page No.

S 01/01/80 TABLE 1 POSTnODIFICATION TESTING ECN RETEST SunnARY OR OR RESULTS SYS DOC REASON FOR RETEST PROGRAM IDENTIFICATION (if available) 77 LS881 No functional test dnenmentation could be SI-166.1 was performed later ACCEPTABLE found to verify stroke time, at tame of WP on the valve lasted for SYS 77 828 870117 472 performance.

in WP-11000 R1.

This later testing verafted the functional operabality and stroke times of the valve.

77 L6487 No functional test documentation could be SI-166.1 was performed later ACCEPTABLE found verafgang stroke time, at time of WP on valve listed in WP-11807 B28 870117 472 performance.

for SYS 77.

This later testing demonstrated the functaonal operability and stroke times of the valve.

82 1745 No WP or functional tests could be found DPSO-Snt-1-DG, performed after ACCEPTABLE an thas ECN.

implemanataan of ECN L1745, B28 861231 160 and attached to SOEP-14 review of same, has tested all of the affected relays satisfactorily.

82 1930 No WP's could be found for review.

Sance ECN L1930 was ACCEPTABLE implemented, the affected B28 861231 160 protectava relays have been functaonally tested semi-snnualig by DPSO-Sn!-1-DG/A-A,18-B,2A-A, 2B-B.

Latost Data Sheets of the above tests are attached to SOEP-14 review of ECN 1930.

82 2106 WP's and/or testing relevant to system 82 Control circuit for affected ACCEPTABLE could not be found.

62 X relays was modified later B28 861231 160 by ECN LS016. WP-10813. That ECN contained a functional test proving the MODS implemented in ECN 2106 are operable. Testing of the NODS in the ECN 2106 are acceptable.

82 FCR -E140S No testang was found for this FCR.

TUA-188, which was performed ACCEPTABLE after FCR -E1409, documents B28 861231 160 satisfactory testing.

82 LS160 WP-8374 specifies calibration and document Later tests under SI-170.1, ACCEPTABLE changes for vendor setpoint changes and 170.2, 170.3, & 170.4 in B28 661231 160 performance of SI-7.

This testing does conjunction with Int-82, for not specafically cover testing of the each diesel generator, anstruments affected by the setpoint demonstrate the instruments &

associated loops are operable cha nges.

& calabrated.

l Page t.o.

6 01/01/80 TABLE 1 POSTnODIFICATION TESTING ECF4 RETEST SunnARY OR OR RESULTS SYS DOC REASON FOR RETEST PROGRAM IDENTIFICATION Cif available)

C7 L6SS2 WP references S1-166.1 completion date for A later documented SI-166.1 ACCEPTABLE 2-FSU-87-7,0.

No SI-166.1 documentation for 2-FSu-87-7,8 is B28 870211 121 could be found.

acceptable.

90 2650 Functional testing signed off/ approved in Functaonal test data added for ACCEPTABLE WP.

acceptability B28 870204 001 SI-83 SI-205.

SO 2773 Functional testing signed off/ approved in Functional test data added for ACCEPTABLE WP-10466 Rt.

acceptability B28 870204 001 SI-685.2 SI-687.2 t

1 SI-205.2.

90 2775 Functional testing signed off/ approved in Functional test data added for ACCEPTABLE WP-10tSS Rt.

acceptabilatu, SI-686.2.

B28 870204 001 SO 2780 Functional testang signed off/ approved in Functional test data added for ACCEPTABLE work plan.

No functional testing called acceptability, SI-685.2.

B28 870204 001 for.

SO S385 Retest of radiation monitors was not ECN LS385 affected radiation ACCEPTABLE performed under ECN LS385.

monitors were functionally B28 87020'i 001 tested under WP-10SO1 and 11095 per ECN's LS770 and S194, after implementation of ECN LS385. Test results were satisfactory.

90 SSS2 WP did not include any functional or SI Review of scheduled SI's ACCEPTABLE I

test for ECN 5932 affected radiation performed on affected B20 87020'i 001 l

contters.

radiation monitors after teptementation of ECN LSSS2 has shown they were adequately tested.

SS 28S0 Change of FCU-70-85 & FCU-70-l'13 valve A later response time test ACCEPTABLE relay from K607 to K630.

No functaonal data sheet (Data sheet 828 870226 113 i

test adentafaed in WP.

InI-SS-RT-630A) is acceptable.

A later SI-217.1008 data sheet for FCU-70-OS is acceptable.

SS 5536 Relocation of 2-PT-68-68 & panel 2-L-360 Later recalibration of ACCEPTABLE did not show adequate documentation of 2-Pt-68-68 per Int-68 shows 828 870226 113 recal.

repeatabalatu and verifies calibration.

Page t.o.

7 01/01/80 Te8LE 1 POSTttODIFICATION TESTING ECN RETEST Surtr1ARY OR OR RESULTS SYS DCC REASON FCR RETEST PROGRAr1 IDENTIFICATION (if available)

SS SS37 Remove & replace terminal blocks with WP verified functionality but ACCEPTABLE hardware splicing on TE.

not how chart recorder B28 870226 113 readings taken was deemed sufficient for program acceptance.

SS ESS4 Response test of 2 PDT-30-42 & 43 did not The chart recording of ACCEPTABLE have sagnatures.

2-PDT-30-43 shows an B20 870226 113 acceptable response time verification.

SS FCN-TEPst10645 No WP was written for this FCN. No SI-227.1, performed later, ACCEPTABLE functional test was mentioned in the FCN.

functionally tested this B28 870226 113 modification.

SS L6339 S1-90.82 mas signed off an WP as being SI-SO.82 performed later is ACCEPTABLE complete.

.42 documentation found.

sufficient vertfacation.

828 870226 113 SS LESCO No WP was written for the ECN.

SNP field verification per ACCEPTABLE I

10CFRSO.49 verifies location B20 870226 113 I

and SI-686.2 veriftes channel calibration.

2C2 LS363 There is no reference to SI-26 in ECN &

SI-26 has been performed at 18 ACCEPTABLE WP. Functional test on 6.S KU S)tUte board months intervals. The latest B20 870219 006 28-B onig was successfully ccepleted.

SI-26 test results were provided to support successful verification of operability as modified.

SI-26.1A l

SI-26.18 i

SI-26.eA l

SI-26.2B

Page t 3/Siu7 HEE _2 POSTNODIFICATION TESTING ECW OR RETEST SumWARY OR SYJ Poq !

Engn_m roR EKIEST FROGRAN IPlaIlnC_AILos gEsuLIS 111 m ilablsl The following are specific Retest Sessaries performed or to be performed for post-modification fasctional l

verificaties.

i I

L6298 Relocated Pressure Trensmitters Calibration per SI-98.2 and response were not tested for response time.

time testing per SI-247.199 wia INI-99 response time tests RT9.8 & 9.11.

3A LSS63 No documentation verifying sere Perform visual inspection of sense leakage testing en added test lines, fittings, and imelation valves connecties in the sense times, for leakage and document the results.

t 3A L6533 Level transmitter cables were not Perform SI-94.4 Lest to ensure no Completed satisfactorily tested for damage af ter sut,sergence damage was done to the level B25 '87#196828 protecties was added.

Transmitter cables.

3A L6692 Replaced solemeid valves were Perform INI-99RT-681A for Train A valves l

met tested for response time.

and IMI-99RT-6 SIB for Train B valves.

34 FCW-TEmn Me retest specified. Awaiting Later, if required.

19651, AEB Punch list resolution.

38 2S95 Replaced handswitches were not Perform a test to verify new handewitches Completed satisfactorily functiemally tested.

are functiem41.

B25 '878106832 3B 2774 Stroke time results are set Perform SI-166.3 for replaced NOW under acceptable per SI-166.3 for mermal operating pressure and temperature.

replaced NOV.

38 LSII4

-Aum. Feedwater Peep breaker Perform fasctiemal testing for modified Completed satisfactorily monitoring circuite were met Aux. Feedwater Pump breaker monitoring 825 '8701219S7 functionally tested af ter circuits.

B25 '878121956 modificaties.

325 '878121841 3B LSS91 Fametiemal testing of several Perform functiemal retest em Westinghouse Completed satisfactorily Westinghemse W-2 switches was not W-2 switches.

B25 '878199834 perfereed after modified switches were reinstalled.

f

+

  • "'M

l Page 2 3/5/87 ECN Gk RETEST

SUMMARY

OR gys f0C e REASON [OR RETEST PROGRAM IDENTIFICATION RESULTS 11{ aveij able) 3B LS823 Functional testing was incomplete Functionally ratested the pressure Completed satisfactorily for several pressure switches after switches.

B25 '870106031 E.O. replacement.

3b L5683 Modified pressure switches and Calibrate modified pressure switches and associated sense lines were not leak test sense lines at normal operating tested.

conditions.

3B L6444 Replaced Transmitters were not Perform leak test and IMI-3 test for leak checked at normal operating replaced Transmitters at normal conditions, operating conditions.

33 LS769 Portions of the AFW piping have The chemical feed line installed in the been identified for surveillance auxiliary feedwater line shall be due to acceptable but marginal observed for branch line resonance during l

vibration levels measured during recirculation and low flow modes of l

preop testing. Moved a chemical operation. The test shall be conducted feed line connection into this before or during Unit startup.

i vibration problem boundary. This creates some uncertainty as to the I

response of the branch line during operation.

35 L5642 Replaced pressure regulating valves Piping vibration qualification testing Completed satisfactorily downstream of the auxiliary feed shall be performed after installation of B25 '870218802 pumps with cavitating venturies.

the cavitating venturies under ECN LS842.

This change is in the vibration This test was conducted as post problem boundary discussed under modification test PMT-53.

ECM L5769.

l 26 L5063 Inadeguate hydrostatic test Retest at the required pressure and pressure (188 peig test vs 225 for the required duration.

peig required).

33 L5443 FS-30-20J and -207 need to be Performance of IMI-134 will prove Completed satisfactorily calsbrated to verify "20 FPS DECR-adequacy.

B25 *070121042 metpoint.

l 32 L5452 Functional operability of dampers Perform Function.1 Operability Test.

not verafied.

33 2945 N. documentation available which Test is to be performed to verify same.

verifies fan capacity, operability l

or a lack of excessive vibration, during operation.

l l

I

i l

l Page 3 3/5/tI7 ECW OR RETEST

SUMMARY

OR FJ Dic e REASON Eng ggyrsT PRocRAff IPD!TIEKATION RESUI.TH 11f eyailehlal 3J LS37d We documentation of vibration Equipment operation is to be observed for monitoring following replacement potential vibration problem.

of fan drive motors.

3d LS872 No documaatation of vibration Equipment operation is to be observed for semitoring following addition of vibration.

ventilation system.

l l

3d LS422 W. documentation to verify replace-Dampers are to be tested to verify same.

I ment dampers were tested.

30A LS124 runctional operability of Perform Funct. 0.-er. Test.

Completed satisfactority 9-FCV-77-119 was not verified.

B2S '079129021 30A L5591 Functional operability of Perform Fametiem41 Operability Test Completed satisfactorily liS 146A, -157A, -19th &

of Westinghouse switches.

B2S '87a112006 IstB was not performed.

3JA L6554 Response time test signatures are Perform ti.e response time test and Completed satisfactorily missing and a leak test was met perform leak test.

B25 '878121046 performed.

31 2945 Fametiomal operability was not Perform fan fmactiemal test and shown for fan meter and fan CFM/ RPM test.

capacity was not checked.

31 L5599 We documentation showing vibration Equipment operation is to be observed monitoring following addition of for vibration.

pesformeJ.

weatilaties system, was 31 L5745 We docuneatation of vibration Pump operati a in to t,e observed for nomitering fellowing replacement wibraties.

of meterm for chilled water circulating pumps, is available.

3th LS274 The fail-safe posities was not Perform functional test and verify the worified om FCO-31 A -leSA,B -le6A,B fail-safe posities.

and FSV-3tA - 195A,B - 196A,B.

Page 4 3/5/8F ECm oe RETEST summary OR SYS Reg g

.grasos um gevesT Pmx: Raji ige 8IIEJCATIG!!

gggulIS fit ayaildlat 31A S274 Replaced seee dampers with betterfly Perform less of centrol air test (failed v41 wee.

Freep test TVA-le verified positten test).

functiemal adequacy, except butter-fly valve fail safe operaties open a sudden and/or gradual Rosa of centrol air was met checked.

31C L5591 MS-31C-3934 & 3384 were met Perform continuity check en handewitch Ceepleted satisfactorily fonctiemally tested.

pins.

325 '878189937 31C FCR:

We functiemal test data Functiemal test PS-31C-768, -798 -775 EPP-258, available.

-885 -433 -458 -483 and 588 IPP-192 31 FCR-IPP-We test of PS-31C -768,798,775, Calibraties and functiemal test.

192 885,433,458,483 and 588.

31a L5156 Air handling maits met Perform NR SA-126807, -126809, -126818, functiemally tested.

.-126811 them NR SA-126805, -t h,

I

-126888.

33A LSS91 Be continuity check em Perform continuity test om Pine *D" Completed satisfactorily 2-RS-314-7A, 38A.

to "E" and

  • F" to "H.*

325 '870189837 32 L5444 centret air lines met leak teeted Leak test in to be performed en affected after installaties of pressure lines.

regulators.

l l

43 2083 Weed stroke time testing for Perform SI-166.4 for 2-FCV-43-33.(Remove Completed satisfactorily 2-FCV-43-33.

2-FCV-43-33 irem WP) 328 '878205894 l

43 3889 We Famet, test for 2-FCV-43-58, WP 12257 provides functiemal test.

-61, & -(p4.

Alse 2-FCV-43-55.

E L549e se fumetiemal test for 2-PS-3-t385, Fametiemal test of Aes. Feedwater Puey Completed satisfactorily 2-MS-E-543, ~549.

Reen Ventilation Fan required.

325 '878284807 l

M L6584 Emened out meter replaced, Cycle valve twice at sermal operating met tested.

conditiene and perform 50 VATS.

61 L5881 All states of operating lights met Verify semiter light and travel light addressed.

status.

Page 5 31's/tfl ECW UR RETEST SUNNARY OR SYs Doc e REASON [OR RETMT PRocRAN IDMTIf1GTION RM%TS. fit availshls!.

61 L6287 Monitor lights en valves Perform functional test to verify monitor 2-FCV-61-97, 122, 192 & 194 met lights.

worified.

62 L5114 Charging pump breaker control Functiemal test charging pump breaker Completed satisfactorily circuits incompletely tested.

control skis.

B25 '879121851 62 L5591 Incomplete testing of six Functiomal test GJP 12268).

Completed satisfactorily Westinghouse hand switches.

B25 '878126947 I

I 62 L6195 Documentation of motor operability Perform SNI 2-62-5, S1 48 to werfify I

not available.

operability.

62 L6343 Incomplete functional test of Verify Normal start-up af ter lube oil Centrifugal Charging Pump Control pressere inhibited start-up, at low press, Logic.

and operation in by pass mode.

l l

62 L6544 Need EI-166.4 for 2-FCV-62-99.

Perform SI-166.4.

I 62 L6462 Portions of the CVCS letdown line The testing to be performed mader PNT-32 L64/1 apstream and downstream of the adequately adJtesses the problem.

PWT-32

[

L5724 let down heat exchanger have been will be performed for a full cycle of identdfied for vibration testing operation or until the problem is umJer PNT-32.

The objective of the identified and corrected.

test is to identify the source of vibration which has caused a branch line failure and a snubber failure.

l ECM's L6471 and L6462 adJed a tie-back type supports to reduce vibrations en the branch line which ECM L*124 changed support.

5 had failed.

design to accommodate higher leads.

i 62 L5329 Added a langer to reactor coolant The fix implemented by ECM L5329 has Completed satisfactorily pumps RCPg3 seal water line, proven to be effective in eliminating B25 *879218062 which failed during operation, to the resonance of the seal water line, eliminate a resemance.

63 L5114 Incamplete testing of SI pump breaker Simulate

  • Trip".

Verify trouble light.

t'empleted satisfactorily clearing function.

Show HS can clear condition.

b25 *076121851 63 L5591 Lack proof of continuity Functional test. (WP 12268).

Completed satisfactorily em Westinghouse SW's B25 '879129947 2-HS-18A, -15A.

I Paq. 6 3/5/u7 ECW OR RETEST

SUMMARY

OR Ei DOC !

EEASON EDE BII_E*iI tR_o_cg s I g NI1ricATIng ESULIH lit anumblet -

63 L5717 Leak test required on bellows of Leak test 2-LT-63-68, -81, -82, -89.

cold leg accommlator level transmitters.

63 L6245 Wom-werified testing of Functiemal test 2-FCV-63-175 motor 2-FCV-63-175 meter operator.

operater.

63 L6315 Werk plans are partially implemented. Fasctiemal test fuse circuits at energized operating conditions.

63 L6487 Bad limit switches on 2-FCV-63-84.

Stroke time test for 2-FCV-63-84 completed satisfactorily Per S.I.-166.4.

828 '878226114 63 L6533 Imadequate loop & stroke time test Calibrate loop 2-LT-63-179 per of 2-LT-63-179.

S.I.-282 perform stroke time test per S.I.-247.1SS.

63 L6556 Imadequate stroke time test of Stroke time test 2-FCV-63-84 per Completed satiufactorily 2-FCV-63-84.

S.I.-166.4.

B25 '879121953 65 L5124 Flow switch setpoints were Verify flew switches activate at Completed satisfactorily L5125 mot verified.

setpoint.

825 '879121958 65 L537I No stroke time test for Stroke time test 8-FCV-65-24, e-FCV-65-43 l

9-FCV-65-24, -43.

per INI-99.

I 65 L5591 No functional testing of W-2 Continuity test W-2 handswitch pine Ifandewitches 8-HS-65-23A, -42A.

through Cannes commectors.

65 L6536 We stroke time tests for FCV-65-4, Stroke time test FCV-65-4, FCV-65-5 per Completed satisfactorily FCV-65-5, INI-99, S.I.-247.1SdB.A, 247.1998.

325 '87s284068 65 6536 No response time testing was SI-247.18e A&R and INI-99 (RT-612 A&B)

Completed satisfactorily accomplished for 2-FCV-65-4 and S are acceptable retests for response time B28 '878219911 after actuator replacements.

criteria.

?--

w

=

y

P49 7 3/5/u?

ECW UP RETEST

SUMMARY

OR SYS Mxl !

REASON MR pfTEST fpOGRAM I MMIlflG TigN EGiULTU Jif areilsidet 65 6749 Circuits associated with replaced Additional teste commist of leading the meer emergized KAZ actuators did met have fase fed circuits to as practical, to functiemal tests specified.

lead conditions as demonstrate fase adequacy.

67 2117 Valves 1 and 2 FCV-67-65 and 63 Restroke valves with remote and local Completed satisfactorily were met verified functiemal at switch operation and verify correct B28 '8782190J7 both the remote and local panels as

  • STOP" fonction of HS-67-65B AND 688.

to their *STOP* functions.

67 U-2 Decamentation could met be found to Recalibraties was stipulated as retest, Completed satisfactorily 2u?9 and support the retest of all equipment per IMI-67; however, documents were found B25 '879186030 U-l modified.

which provide acceptable test results.

5397 67 5114 Functiem41 testing did met Petest stipulated to simulate trip and Completed satisfactority encompass the reases for the start signals with indicaties and reset B25 '870129343 modification to the ERCW Baeakers.

capability to prevent *leck-up*.

67 5298 ERCW pumping station transformers Retest stipulated to test for correct.

(*S* Train) met adequately tested phase relation per SUEP-14 sowiew for phase rotaties, after guidelines.

roterminaties.

67 5591 A smactiemal test for continuity Retest stipulated to perform continuity Completed satisfactorily met performed after the testa en switch wiring and commectors.

B25 '878109032 was rewiring of switch " mated commectors."

67 L5235 SI-566 ERCW flow test revealed The system flow is to 1,e re-balanced.

insufficient fle to Electric Board Rees A/C Condenser (Cooler),

which w,as erroneously considered acceptable.

1 l

l

I l

Page 8 3/5/87 ECM OR RETEST SUNNARY OR SYS ME i REASON IDG RETEST PROGRA_3 1RENTIU CATION RgSipE Uf myMlahlst 67 L6218 Repaired or replaced pipe and a Surveillance program shall be established L6463 walve body because of wall thiaming prior to startup within the probles L6541 by cavitation eresion.

Based on bomadary, which considers the following:

this evidence a piping vibration l

problem boundary has been Wall thiaming of pipe and valves.

I identified downstream of the CCS I

heat exchanger measles to the Support integrity, j

discharge header, including branch commections within three restraints a.

loose fasteners.

of the process time.

The vibration b.

fatigue cracks (wisual) i I

levels have not been severe enough c.

anchorage to cause fatigue failures on the l

process pipe, however, branch line terminal commections to the process Branch lines.

line are vulnerable to fatigue

failures, a.

resonance check b.

ND weld examinations inside firut isolation valve.

67 L6814 A small diameter meter hearing ERCW motor bearsag cooling line shall be cooling line was changed out on the observed for baamch line resonance during ERCW pumps, which requires limited normal operation.

testing.

l The post modificaties test, PMT-97, I

does met specify vibration testing in the scoping document.

l 67 L5235 Nodifies supply and retura piping If completed, the supply and retura lines l

to the main control room A/C muits will require post modification piping A & B.

The piping has been vibration qualification.

i l

partially installed but has not been commected to the process.

i 1

67 L5de9 Throttling valves in the ERCW Valves identified in reference meno with a NEMO mystem have been analyzed for potential for cavitation shall be B2S '86 cavitaties based on computation of observed in operation for sounds which 199618

.a

" cavitation i nd ex.*

The valves indicate severity of cavitation.

which have a potential for develo ped. Maintamance records should be cawitation moder operatiemal flow

. reviewed for indications of cavitation.

conditions are identified in the C'witation could

. referenced sese.

a develop er increase due to replacenest of carbon steel piping with stainless steel under ECM L5899, because of a higher pressere drop across the valve.

ECN work met accomplished yet.

I i

L.__

l Page 9 MM7 ECM OR Rt*TsST SUMM AEY OR

'YS DOC e REASON mR REI M FROCRM LDOITIElf3T!on nEsur.yg jif gyail a ter.

J 68 27/1 Valves set (mmetiemally tested Test valves per SI-166.41 after due to De t a c iency DN-13.

resoluties of DN-8 concerning In IC-60-396.

68 S114 Functiemal testing did not Retest stipulated to a.im lata trip and Completed satisfactorily encompass the r ea s s t.

for the start. signal with proper indication and B2S '87012 048 l

modificatsen to the pressurizer reset capability to preven; " A r.ek -u p*.

l Heater Backup Croup Br eakas s.

I 68 -

% 91 We functional continaity teatiaq Retest stipesatc.d to cycle hawls' aitches Completed satisfactosi;y I

w.a. c.mpleted on 2-1:S-68-341 A (s and veri fy coat s a ai ty per SI-2f -24.

b25 *0701120J0 1

1 341 D.

LC

$773 Perfere retest to detean..-

Betes

  • ef valves 2-PCV-6u.L34 and 340A camme/fim action of valve 4%tter per SCTP-14 direcRe. - and mLilizima the discovered daring PMT-54.

AMS system deortismal.fter calitt tion per SI-3eJ.

~

68 ^ LS8%

LT-68-335 was met futetionally Test,coi yet stipe. acted. Onisties written S tisfcciary-based e..

4 tes.t<d ceneides.ag sampling regir.t.r g esampl ii.g

( pe ra t ismo.

DCR-2303 a,p.ewal of LcTI-23da, o pera t s e as.

wvstt a to relocate transmitter to B;5 *87el20045

~

e iginal location. Testing a b eired, if

.st. relocated.

V 48 iW3 se f ar.-a s ema l testing of the Re t e s t L"' i nd t ow accelerseettra yer Acesstic Monitoring System (AMS)

S.I.-30@ m.>cify correct gai>.

after accelerometers. wre relocated

& replace.

s.

~

6 L64%

2-PT-0.5-4 'w.s c.1;bre;ed &

Ret et stipulated to recalibrate per Completed sativtakterily tested will.r. t ceasid.rity SI-l W and IMI-60 accountisq for head

,* Head _errection* es

  • t.e ~'. -

correcties and measuring entput at rack. _

B25 '870121040

-8.ccasacy.*

68 L6181 s Me fonction.1 worificatsee of Retest stipulated to lift wires, measure Ceepleted satisfacterity 310 in n.e tra t i o n.' 9 22.

~

& record resiatar.cw c I verii, !.gger t w.

'ts/ ele 9Jtu w i. ew p terminated f or 2-TE,

indicaties in the an 3.

68 L6221 Documentation of f unctiemal Retest required per SOEP-14 M si. ier i fi-testisq ef the leeps and their.

cation do.ementation.

calabraties costa met 'e a located

+"

e g

ar

~

'P--

Page is "s/5/81 ECW OR RETEST

SUMMARY

CR SYS g$ !

gtAStm FOR RfTIEI EMMEM IDluTIfl[ATJON R QULIG 11{ m ihlle) t 68 L6347 Incomplete testing of 2-PT Recalibrate transmitter accounting for 342C after component replacement.

cable losses from rack 2-L-!!B per S.I.-92 measuring output at rack, instead of transmitter.

63 L6533 Incomplete functional testing after Retest stipulated to calibrate and test Completed satisfactorily installation of new RTD and PT per SI-94.1 and loop test per SI-70 B28 '879226867 cables.

sect. 7.9 68 L2633 Determine if power supplys 2-PX Measure the voltage at 2-PT-68-322, -323, and TENM-322, -323, -334, and -349 have been

-334, and -349 to verify the maximum 19651 A&B modified per TEMM 19651 A&B to pro-voltage is 52 t,1 VDC per SI-1-81924.

vide a maximum voltage at 2-PT 322, -323, -334, and -348 of 52

  • 1 VDC.

78 L2788 No system flow balance af ter addi-The system flow is to be re-balanced.

I tion of sample cooling loop to the Component Cooling System.

79 L5591 Westinghouse W-2 switches Functionally test W-2 switches Completed satisfactorily were not functionally tested modified under this ECM to demonstrate B25 '879199017 after re-installation, operability after installation.

7e L5731 Valves affected by this ECN Functionally verify valve operation.

Completed satisfactorily B25 '879196029 MODS were not functionally I

tested.

l 70 L6292 Functional test of new level Actuate CCS surge tank low level switches not properly performed.

switch (ma nic a ll y, or by changing tank level) to verify switch operates to close CDWE CCS supply and return valves.

70 L6374 Alarms associated with pressure Verify alarm at setpoint.

P switches replaced under this ECM were not tested.

72 L5114 Functional test of Containment Functional test subject breaker (s) by Completed satiufactority Spray pump breakers did not simulated trip & close signal to illuminate B25 '878129022 encompass the reason for the white trouble light and verify light can modification under this ECN.

be cleared by placing control handewitch in *stop* position.

72 L5591 Westinghouse W-2 switches Functionally test hand switches to prove Acceptable.

HS-72-27A and ISA were not continuity after inutallation.

B25 '87012e946 functionally tested after installation.

72 L6697 Performance of SI-166.6 not Perform & document results of SI-166.6 documented, as required by on 2-FCV-72-28 & 23.

workplan.

Page !!

3/5/87 ECW OR RETEST

SUMMARY

OR SYG Doc e REAsow rog REIESI EgoGRAM ]D M IlflfAIlON RESUtsTS H I avellall d 74 L2595 Unit 2 handewitches for RHR Place handswitch in "stop* position and Completed satisfactor&Iy pump were not verified as verify it spring returns to

  • auto."

B25 '879285826

. spring seturn to " auto.*

f 74 L2828 Functional operability of mini-Operate RHR pumps or yumper across flow valves 2-FCV-74-12 & 24 not terminals to simulate pump running a nd verified after NODS to control verify valves open.

REll review indicates that ECM L6797 will encompass testing

- c i rcu i t ry.

4 required for ECN L2828, when implemented.

j Therefore, after implementation and testing under L6797, requirements for a

testing, if approved, will cover tunting for L2028.

74 L2873 Functional test was not Simulate a safety injection signal and Completed satisfactorily performed to verify that verify that both valves go fully open and B25 '878166833 valves FCV-74-16 & 28 rsmain remain so af ter Si signal is removed.

in emergency mode after reset of SI signal.

-g 74 L5114 Additional testing required to Rack out breaker to " test" position, Completed satisfactorily "

verify uupply breaker for RHR simulate a trip signal in the RHR pump B25 '879121854 pump does not " lock open" with trip circuit, apply a start signal from no indication of.this condition.

handewitch. Verify white trouble light comes on, and can be cleared by taking handswitch to stop position.

74 LS$91 Handewitches were not functionally Vetify continuity through pin connectors Completed satisfactorily tested after they were returned to in Cannon plugs after handewitches were B25 '878199936 the circuit.

reinstalled.

74 L6665 Acceptability of motor maggers used Document the calibration dates of motor in WP 12975 should be documented.

maggers used in WP 12875.

accom-The source of the vibraton will be resolved 74 L5724 Support deuign changed to modate vibrational loads, which had by PNT-32, which will be conducted for a full been failing a snubber. The snubber operational cycle or until the problem is was replaced with a rigid rootsaint identified.

and a lateral restraint was added to stabilize an elbow.

The line segment upsLLean of the CVCS letdown heat exchanger was identified as a vibration problem boundary requiring surveillance. Observation testing did y)L establish the source.

Later, a fatigue crack developed on a branch.

line downstreas of the letdown heat exchanger.

=

t Page 12 l

3/5/07 ECM OR RETEST SUNNARY OR SYS Mt BEASON [OR ggIESI FROGRAM JMNT((ILATJON RESETH III availablst 74 L6483 Changed a butterfly valve position The change in a butterfly valve disc pos-from 68 degrees to a setting not less ition requires testing to verify the change.

than 76 degrees and no more than 79 in position reduceu or eliminates cavita-Lion problems. To provide this and to degrees.

This valve was a source of vibration problems encountered develop corrective action for SCR during preoperational testing.

This SONNEB8798, the following action shall be line segment has been identified as taken prior lo og during slaglue2 The a vibration problem boundary.

In lino segment in the vicinity of the flow addition, SCR SONNEB8780 has been control valve, downstream flow restrictor, written, which describes a condition crossover loops, and full flow bypasu shall which has not been tested or eval-be monitored for vibration. A surveillance uated where a potentially destructive walkdown shall be performed prior to start-cavitatio6 peobles could occur, up for indication of support damage and fastener loosening. Resulto shall be documented.

Inuervice inspection (ISI) recorde shall be reviewed for indications of cavitation. Maintenance records of the valve shall be reviewed for indications of cavitation.

J Perform SI-166.6 and record local stroke Completed satisfactorily 77 L6287 Original review showed local stroke times for containment isolation times for 2-LS-77-9 for 2-FCV-77-9.

825 *B7 ele 6834 system valves not performed.

77 L6525 Local test stroke times not Perform SI-166.6 and record local stroke Completed satisfactorily provided for limit switches time for 2-FCV-77-127.

B25 '87 ele 6935 2-LS-77-127, for 2-FCV-77-127.

77 L6529 Functional operation of valve Perform SI-166.6 and include local utroke Completed satisfactorily 2-FCV-77-18 is verified in both time data for 2-FCV-77-10.

B2S '878106037 normal and' accident conditions, but local stroke time was not included in performance of SI-166 per section 1.3.2 of SI-166.6.

77 L6SS6 Local stroke times for valves Perform SI-166.6 and include local utroke Completed natisfactorily 2-FCV-77-19 and 2-FCV-77-28 were time data for valves 2-FCV-77-19 and -29.

B25 '878106036 not included in FT.

82 LS364 Incomplete testing of relay Prove contacts on relay es/ay make Completed satiufactorily monitoring circuit.

during diesel start.

Actuate relay B25 *078115813 ES/AY and observe red light on.

4 Repeat stepu 1 & 2 for each diesel.

May be performed during SI-7.

b 1

Page 13 3/5/07 ECN OR RETEST

SUMMARY

OR syn toc e REAg!g roR RETEiT ERocRAN IPE!!TIFIC_ATION RFJ#LTii 111 Sydleblel.

breakers and verify 82 L5451 Auxiliary tube oil pumps added Verify trip ratings on to each diesel were insufficiently that each AC pump starts when associated

tested, breaker is cloued and stops whom breaker is opened.

Verify each DC grump starts when labe oil preusure drops to le PSI and stops when pressure increauen above setpoint in SI-179.

82 L5451 Diesel generator lube oil system System check is to be performed per MI-9644 post-modification tout not con-in conjunction with Diesel Surveillance ducted at operating conditions.

Testing.

82 SONEEB Required demonstration of DG in Complete Regulatory Guide 1.9 demonstration.

8515 accordance with RC 1.9 hau not been completed.

87 LS861 Static alsift problem with SOR After modification by SOR, and re-instal-L63S9 switchen was diucovered.

(IE lation, leak check all fittings and Bulletin 886-02) tubing reworked and perform sectious of SI-196 to calibrate each level switch aml verify operability.

9e L5567 Radiation monitor e-RM-90-lelC 0-RM-99-lelC functionally tested per SI-83.

Completed satisfactorily to be touted per SI-83, section B25 '870128944 j

5.8.3.

99 L6533 One cable and loop tout was not Calibrate 2-LT-63-179 per S.I. 292.

performed satisfactorily.

Perform respomue tino testisq en 2-LT-63-179 per S.I. 247.190.

2 201 L5047 Installed PT's did not have turne-Perform and document turne-ratio test ou 2e2 L5449 ratio verified. Ove rvol ta ge condi-PT's.

Perform step 5.3.2 of PMT-5 to tion exiuted during FT performed on prove ove r-vol ta ge alarms operate at propor boards 15-B,'2A-A, and 28-B.

set points.

291 L5305 FT performed does not show elapsed Test CCP starting time per pre-op test 292 time between closing of diesel gen.

TV A-13B (1).

emergency feeder breaker and closing of breaker for Centrifugal Charging Pump (CCP).

281 L5591 Westinghouse handewitches were FT handswitches installed to verify Completed satisfactorily 282 installed, but not functionally continuity througli the Cannon connectors.

B25 '878199035 tested, after modifications.

4 i

e 4 - -.

,e

Page 14 3/5/07 ECN OR RETEST

SUMMARY

OR SYS DOC 0 REA!0N FOR REIEST E_ROGRAM 1DM ilflCAT10M ECi%TG 111 availsblst 201 L6314 PMT did not test breaker's ability Perform test with worst case load.

202 to carry worut case load current.

201 L6315 Fuses replaced and slugs installed Functionally test fuses and slugs to prove Completed satisfactorily 202 were not functionally tested.

modifications will not adversely affect B2S '878129844 safety function of tlie system (s).

201 L6438 Functional Test performed after mod-Remove each added' fuse, one at. a time, 202 ification did not adequately test verify the associated ACR status l iglit fuse logic.

goes out.

249 LSS99 Electrical isolation of added fifth Verify electrical isolation of added fifth Completed natisfactorily vital battery was not verified.

vital battery.

SS3 '861215962 i

.