Amend 81 to License DPR-6,revising Tech Specs Re Reload I1 Fuel MAPLHGR Limits & Min Critical Power Ratio to Support Fuel Reloading
ML20205F600
Person / Time
Site: Big Rock Point File:Consumers Energy icon.png
Issue date: 11/01/1985
From: Zwolinski J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20205F597 List:
References
NUDOCS 8511120318
Download: ML20205F600 (5)


Text

[fo%9'o UNITED STATES

^g

[

g NUCLEAR REGULATORY COMMISSION D

-E WASHINGTON, D. C. 20555

%,...../

CONSUMERS POWER COMPANY 00_CKET NO. 50-155 BIG ROCK POINT PLANT APEPPPFNT TO IACILITY OPERATING LICENSE Amendment No. 81 License No. DPR-6 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for arendment by Consumers Power Ccmpany (the licer.see) dated Aucust 16, 1985 as revised September 24, 1985 complies with the standards and re Atoraic Energy Act of 1954, as amended (quirerents of thethe Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activjties authorized by this amendrent can be conducted without endangering the health and safety of the public; and (ii) that such activities will be conducted in compli-o ance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health ar.d safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable recuirerents have been satisfied.

O 8511120318 851101 PDR ADOCK 05000155 P

PDR

1 1

. 2.

Accordingly, the license is arended by changes to the Technical Specifications as indicated in the ettechment to this license amendment and Paragraphs 2.C.(2) of Facility Operating License No. DPR-6 are hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A es revised through Amendment No.81, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGUL ATOPY COMPISSION I

l k

u John. Zwolinski, Chief Opera no Peactors Branch #5 Division of Licensing

Attachment:

Changes to the Technicel Specifications o

'Date of Issuance: November 1,1985 i

1 I

l l

i t

1 L

't ATTACHMENT TO LICENSE AMENDMEhT f:0. 81 FACILITY OPERATING LICENSE NO. DPR-6 DOCKET NO. 50-1EF Revise Appendix A Technicel frecifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and contain marginal lines indicating the area of change.

REMOVE INSERT 5-9a 5-9a 5-9h 5-9b O

m..

F 4

TABLE 1 Reload G Reload s

Reloads Including Reload G3/G4/H1/

Reload F & Modified F G13/G14 GIU H2/H3/H4 Il Minimus Critical Power Ratio at Normal Operating 1.59 1.59 1.59 1.59 1.61 Conditions

  • Minimua Bundle Dryout Time ** Figure 1 MaximumHeatFluxag Overpower Btu /h-Ft 500,000 395,000 407.000 392,900 392,900 Maximum SteadyyState Heat T1ux, Btu /h-ft 410,000 324,000 333,600 322.100 322.100 Maximus Average Planar Linear H:st Generation Rate.

Steady State, kW/Fe***

Table 2 Table 2 Table 2 Tabla 2 Table 2 Maximus Bundle Power, MW, Fig. 2 x 0.95 Fig. 2 Fig. 2 Fig. 2 Fig. 2 Stability Criterion: Max.

Measured Zero-to-Peak Flux Amplitude, Percent cf Average Operating Flux 20 20 20 20 20 Maximus Steady-State Power Level, MW 240

,240 240 240 240 g

Maximus Value of Average C:re Power Density 46 46 46 46 46 e 240 MW,, kW/L Nominal Reactor Pressure During Steady-State Power 1,335 1.335 1.335 1.335 1.335 Operation, Psig Minimus Recirculation 6

0 0

6 6

Flow Rate Lb/h 6 x 10 6 x 10 6 x 10 6 x 10 6 x 10 Rate of Change of Reactor Power During Power Operation Contrni rod withdrawal during power operation shall be such that the average rate of change of reactor power is less than 50 MW per minute when power is less than 120 MW '

per minute when power is $etween 120 MW, and 200 MW, and 10 MW Pe ices than 20 MW tinutewhenpowIrisbetween200MW,and240MW,.

t

  • The bundle Minimum Critical Power Ratio (MCPR), based on the Exxon Nuclear Corporation XN-2 Critical Power Correlation, must be above this value.

c*The actual dry out time for CE 9x9 fuel (based on the General Electric Dryout Correlation for Nonjet Pump Boiling Water Reactors. NEDE-20566) should be above the dryout time shown in Figure 1.

c**For operation with only one recirculation loop in service these limits shall be reduced by 5 percent for Reload F and Modified F and reduced by 20 percent for other fuel types.

5-9a Amendment No fl. 89.81.

i-s TABLE 2 MAPLHGR (KW/FT) LIMITS i

Planar Average Reload Reload Recon-Exposure Modi-Reload Reload Reload G3/G4/ Reload Reload stituted Reload

]

(MWD /STM) fled F F

G CIU H1 H2 H3/H4 G13/G14 11 j

j 0

7.21 7.0 6.77 6.92 200 9.5 9.4 7.28 360 7.62 7.65 1,000 7.95 7.8 7.56 7.56 7.81 1,630 3,810 7.57 3,900 7.65 7.95 5,000 9.9 9.7

.j 6,440 7.28 i

6,620 7.50 7.48 7.48 7.48 7.89 l

10,000 9.9 9.7 7.17 12,880 j

13.520 7.49 8.00 13,610 7.56 j

15,000 9.8 9.6 7.89 l

19,050 7.11 i

20,000 8.7 8.6 f

20.320 7.56 7.56 7.56 t

20,870 7.78 7.76 i

24,580 6.84 i

25,000 8.4 8.3 i

26,400 7.32 7.32 7.32 7.19 l

26,760 7.64 28,210 6.08 o

30,000 7.4 7.3 6.0 6.97 31.210 6.73 6.73 6.73 32,000 7.0 6.9 6.0 33,020 7.12 6.81 33,380 6.69 6.69 6.69 t

j 34,000 6.5 6.5 i

6.0 34,470 5.73 6.73 36,000 6.2 6.1 6.0 36,290 5.73 l

38,000 6.0 40,000 6.0 41,400 6.0

,i

[

I I

e I

i 5-9b Anendment No. fl. $2.81,

.