ML20202G716

From kanterella
Jump to navigation Jump to search
Rev 22 to AR-402, PSA G Annunciator Response
ML20202G716
Person / Time
Site: Crystal River 
Issue date: 12/02/1997
From:
FLORIDA POWER CORP.
To:
Shared Package
ML20202G615 List:
References
AR-402, NUDOCS 9712100095
Download: ML20202G716 (88)


Text

-.-.

i Rev. 22 Effective Date 14 A N INFOR VlATION ONLY --

l ANNUNCIATOR RESPONSE AR-402 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 l

4 PSA G ANNUNCIATOR RESPONSE O

1

)

APPROVED BY: Interpretation Contact isnd h1/7?A (SIGNATURE ON FILE)

/ E[E!O,7 DATE:

INTERPRETATION CONTACT: Manager, Nuclear Plant Operations Support K

2 F.

PDR 4

. -.. -.:. u

l....

i r-1 TABLE oE_ CONTENTS i

SECTION PACE 9

1.0 PURP05E.................................................................

1 LD_RE FE ENCE5.............................................................. 1 2.1 DELEPEN13NG_KEEREtMIS............................................ 1 4

2. 2 DEVELOPfENTAL KEE8ENCES............................................ 1 l

2 3.0 PERSONNEL IW0CTRINATION................................................

2 4.0 INSTRUCTIONS............................................................

2 3 0 FOLLOW-UP__ ACTIONS.......................................................

2 ENCLOSURE 1

-Annunciator Response....................................

.......... 3 f

}

I i

b i

. /~'

-- V AR-402 Rev.l22 Page.'i

10 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the PSA-Y Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the PSA-Y Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms c > the PSA-Y Lampbox.

2.0 REFERENCES

2.1.

IMPLEMENTING. REFERENCES 2.1.1 AI-504, Guidelines for Reduced F.CS Inventory 2.1.2 OP-301, Reactor Coolant System 2.1.3 OP-402, Makeup and Purification System 2.1.4 OP-404, Decay Heat System 2.1.5 OP-406, Spent Fuel System 2.1.6 OP-418, Demineralized Water System 2.1.7 OP-407], Operation of Reactor Coolant Drain Tank 2.1.8 E0P, Emergency Operating Procedure 2.1.9 AP-470. Loss of Instrument Air 2.1.10 AP-1080, Refueling Canal Level Decrease 2.1.11 Technical Specifications 2.1.12 MAR 92-01-01-02, Demin Upgrade 2.1.13 MAR 92-02-02-01A, RC Orain Tank Level Setpoint Change 2.2 DEYELDfBENIAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217 Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 AR-402 Rev. 22 Page 1

k i

i 3.0 PrmuNdEL ININATIM i

i 3.1 The Annunciator System is powered frca VBDP-5 Breaker 28.

i 4.0 JNSTRUCTIONS l

4.1 Respond to alarms on the PSA-Y Lampbox as indicated on Enclosure 1, Annunciator Response.

1 LO FOLLOW-UP.. ACTIONS L

None e

i i

f r

1 b'

W

-i r

4 L

e r

AR-402 Rev. 22-Page 2 1

-'?__

[

t J

ENCLOSURE 1 O.

-(Page 1 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y 01-01 G-01-01 I

I STATION I

l AIR PRESS l

l LOW I

l EVENT POINT 0894 INDICATED CONDITION:

o STATION AIR PRESSURE IS <90 PSIG AS SENSED BY SA-13-PS l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o STATION AIR PRESSURE INDICATOR SA-4-PI OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS l

o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN DISCUSSION:

STATION AND INSTRUMENT AIR ARE CROSS TIED THROUGH IAV-30. CHECK INSTRUMENT AIR PRESSURE,.

REFERENCES:

DRAWING 208-051 SHEET SA-01 SENSING ELEMENT: SA-13-PS

'AR-402' Rev. 22 Page 3

. ~..

[HCLOSURE 1-(Page 2 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y 01-01 G-01-01 l

STATION l

AIR PRESS l

LOW

-l l

EVENT POINT 0918 INDICATED CONDIYION:

o IAV-30 CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE 40 PSIG OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 LOSS OF INSTRUMENT AIR o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS l.

o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN DISCUSSION:

IAV-30 WILL AUTOMATICALLY CLOSE WHEN INSTRUMENT AIR PRESSURE IS <80 PSIG AS SENSED BY IA-3-PS. THIS WILL ISOLATE INSTRUMENT AIR FROM STATION AIR.

WITH IAV-30 CLOSED INSTRUMENT AIR hGLL NOT FEED STATION AIR. BUT STATION AIR WILL FEED INSTRUMENT AIR THROUGH A CHECK VALVE AROUND IAV-30.

TO REOPEN IAV-30 ONCE INSTRUMENT AIR PRESSURE HAS BEEN RECOVERED THE IAV-30 CONTROL SWITCH MUST BE TAKEN TO THE CLOSED POSITION AND THEN BACK TO AUTO.-

REFERENCES:

DRAWING 208-037 SHEET IA-04 SENSING ELEMENT:11A-3-PS, 33-C VALVE POSITION LIMIT

-AR-402'

.Rev '22 Page 4

. ~

k MCLOSURE 1

' (

(Page 3 of 86) i PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 3

i IA/SA COMP TRIP i

EVENT POINT 0896 INDICATED CONDITION:

t o SAP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN INDICATING LIGHT ON WITH A RED FLAG ON SAP-1A CONTROL STATION 3

OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE SAP-1B RUNNING DISCUSSION:

A HIGH AIR DISCHARGE TEMPERATURE WILL TRIP THE AIR COMPRESSOR.

--TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

ORAWING 208-051~ SHEET SA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS

=

AR-402

-Rev. 22

.Page 5 i

... _ _, _. ~,. _ _. _,.

t mansusu O

(Page 4 of 86) e PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 I

l lA/SA COMP TRIP i

EVENT POINT 0902 4

INDICATED CONDITION:

o SAP-IB BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START 3

ITSITION 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM o CREEN INDICATING LIGHT ON WITH A RED FLAG CN SAP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE SAP-1A RUNNING DISCUSSION:

A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE AIR COMPRESSOR.

~

TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM,

REFERENCES:

DRAWING 208-051 SHEET SA-02 V

SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 22 Page 6

---e.

+,

w----

een--

e~

, s

- =,

..,~---c.

m

,, -,>r

ENCLOSURE 1 (Page b of 86) l PSA-Y ANNUNCIATOR RESPONSE PSA Y-01-02 G-01-02 l

IA/SA COMP TRIP EVENT POINT 0908 INDICATED (ONDUT'Sh o IAP-1A 20.EAKER OPEN WITH CONTROL HANDLE IN THE FORMAL AFTER START POSITION REDONDANT INDICATION WHICil WILL VERIFY ALARM:

o (MLEN INDICATING LIGHT ON WITH A RED FLAG ON IAP-1A CPNTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE IAP-1B RUNNING DISCUSSION:

A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE AIR COMPRESSOR.

TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

4

REFERENCES:

DRAWING 206-037 SHEET IA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 22 Page 7

~

1 ENCLOSURE 1 (Page 6 of 86)

PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-02 G-01-02 lA/SA COMP I

TRIP EVENT POINT 0914 INDICATED CONDITION:

o IAP-IB BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN INDICATING LIGHT ON WITH A RED FLAG ON IAP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o ENSURE IAP-IA RUNNING DISCUSSION:-

A HIGH DISCHARGE AIR TEMPERATURE WILL TRIP THE_ AIR COMPRESSOR.

TURNING OFF THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

i

REFERENCES:

- DRAWING 208-037. SHEET IA-02 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS AR-402 Rev. 22 Page 8

?

,~-

e e

v -- +

m-r-

-m.,

e>, -,

-n-m-,

e

,-m-n

-e n-

.-,,.,y m,.

-4 f

ENCLOSURE 1 (Page 7 of 86)

PSA-Y ANNUNCIATOR RESPONSE PS$-Y-01-03 G-01-03 1A/8A COMP AUTO START EVENT POINT 0895 INDICATED CONDITION:

o SAP-3A BREAKER CLOSED WITH CONTROL HANDLE IN 1HE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED INDICATING LIGHT ON WITH A GREEN FLAG ON SAP-1A CONTROL STATION o STATION AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION:

INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30 ALL

-IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE.

STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208 951 SHEET SA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS, SA-8-PS AR-402 Rev. 22 Page 9

ENCLOSURE 1

()

(Page 8 of 86)

PSA-Y ANNUNCIA10R RESPONSE PSA-Y-01-03 G-01-03 lA/SA COMP AUTO START EVENT POINT 0901 INDICATED CONDITION:

o SAP-1B BREAKER CLOSED WITH CONTRCc HANDLE IN THE NORMAL AFTER STOP POSITION

()

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED INDICATING LIGHT ON WITH A GREEN FLAG ON SAP-1B CONTROL STATION o STATION AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR A VAL 1D ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION:

INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE, STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-051 SHEET SA-02

)

SENSING ELEMENT: CONTPOL SWITCH AND BREAKER CONTACTS, SA-8-PS AR-402 Rev. 22 Page 10

4 ENCLOSURE 1 O

(Page 9 of 86)

PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-03 G-01-03 lA/SA COMP AUTO START V

EVENT POINT 0907 INDICATED CONDITION:

o IAP-1A BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED INDICATING LIGHT ON WITH A GREEN FLAG IAP-1A CONTROL STATION i~

o INSTRUMENT AIR PRESSURE <95 PSIG OPERATOR ACTIONS FOR /, VALID ALARM o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION:

INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30 ALL IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE.

STARTING THE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEER IA-01 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS, IA-13-PS.

AR-402 Rev. 22 Page 11

,q QCLOSURE 1

\\

)

(Page 10 of 86)

~ ~ ~ ~

PSA-Y ANNUNCIATOR RESPONSE PSA-Y-01-03 G-01-03 1A/SA COMP AUTO START EVENT POINT 0913 INDICATED CONuu l0N:

o IAP-1B BREAKER CLOSED WITH CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED INDICATING LIGHT ON WITH A GREEN FLAG ON IAP-1B CONTROL STATION o INSTRUMENT AIR PRESSURE <95 PSIG OPERATOR ALTIONS FOR A VALID ALARM:

o VERIFY PROPER INSTRUMENT AND STATION PRESSURES o RESTART OUTSIDE AIR COMPRESSORS DISCUSSION:

INSTRUMENT AND STATION AIR ARE NORMALLY TIED TOGETHER VIA IAV-30, ALL IN HOUSE AIR COMPRESSORS SHOULD HAVE STARTED ON THIS LOW PRESSURE.

STARTING 'lHE COMPRESSOR LOCALLY WILL ALSO GIVE THIS ALARM.

REFERENCES:

DRAWING 208-037 SHEET IA-02 SENSING ELEMENT: CONTROL SWITCH AND BREAKER CONTACTS, IA-13-PS AR-402 Rev. 22 Page.12

ENCLOSURE 1 O

(Page 11 of 86)

PSA-C ANNUNCIATOR RESPONSE PSA-Y-01-06 G-01-06 i

RC DRAIN TANK LEVEL HIGH/ LOW EVENT POINT 1592 INDICATED CONDITION:

o RC DRAIN TANK LEVEL IS >I14.48" AS SENSED BY WD-23-LS1 i

f REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o RC DRAIN TANK INDICATION, WD-2:-LI-1 OPERATOR ACTIONS FOR A VALID ALARM:

o PUMP RC DRAIN TANK PER OP-407]

l I

DISCUSSION:

RC PUMP SEAL LEAK 0FF, PORV, RC SAFETY VALVES ARE ALL INPUTS TO THE RC DRAIN TANK.

INCREASING RCDT LEVELS MAY INDICATE LEAKING PRIMARY RELIEF VALVES OR DEGRADING RC PUMP SEALS

REFERENCES:

DRAWING 208-060 SHEET WD-19 SENSING El,EMENT: WD-23-LS1 AR-402 Rev. 22 Page 13

LNCLOSURE 1 (Page 12 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-06 G-01-06 RC DRAIN TANK LEVEL HIGH/ LOW EVENT POINT 1593 INDICATED tsNDITION:

o RC DRAIN TANK LEVEL IS <90.16" AS SENSED BY WD-23-L51 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RC DRAIN TANK INDICATION, WD-23-LI-1 OPERATOR ACTIONS FOR x VALID ALARM:

o RESTORE RC DRAIN TANK LEVEL PER OP-407J DISCUSSION:

RC DRAIN TANK PUMP WILL TRIP IF RC DRAIN TANK IS <91.20" as sensed by WD-23-L52 i

REFERENCES:

DRAWING 208-060 SHEET WD-19 SENSING ELEMENT: WD-23-L51 AR-402 Rev. 22 Page 14

ERCLOSURE 1 Og'Q (Page 13 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 i

I l

AC INVENTORY LOW t

EVENT POINT 0081 INDICATED CONDITION:

o RCS LEVEL 15 <129' AS SENSED BY RC-201-L5 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS LEVEL INDICATION, RC-201-LII RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REAGOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 o SEFER TO AI-504 DISCUSSION.

DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR 57 3 0F CAVITATION l'

REFERENCES:

DRAWING 208-047 SHEET RC-27 l \\

SENSING ELEMENT: RC-201-L5

AR-402L Rev. 22 Page 15 L

ENCLOSURE 1 (Page 34 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC INVENTORY LOW EVENT POINT 0794 INDICATED CONDITION:

l o RCS LEVEL IS <146'-5.8" AS SENSED BY RC-163B-LS1A REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS LEVEL INDICATION, RC-201-LI1, RC-201-LI2, RC-202-LI o 1.0 CAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 o REFER TO AI-504 DISCUSSION:

DL' RING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

DRAWING 208-047 SHEET RC-27 SENSING ELEMENT: RC-1938-LS1A AR-402 Rev. 22 Page 16

ENCLOSURE 1 (Page 15 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC INVENTORY LOW EVENT POINT 0795 INDICATED CONDITION:

l o RCS LEVEL IS <146'-5.8" AS SENSED BY RC-164B-LS1A REDUNDANT INDICATION WHICtl WILL VERIFY ALARM:

o RCS LEVEL INDICATION, RC-201-LI1, RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE RCS LEVEL PER OP-301, OP-402, AND/OR OP-404 o REFER TO AI-504 DISCUSSION:

DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

DRAWING 208-047~ SHEET RC-27

,_s SENSING ELEMENT: RC-164B-LS1A AR-402 Rev. 22 Page 17

ENCLOSURE 1 (Page 16 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 I

RC INVENTORY LOW EVENT POINT 1684 INDICATED CONDITION:

o RCS LEVEL IS <129' AS SENSED BY RC-202-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS LEVEL INDICATION, RC-201-LI1, RC-201-LI2, RC-202-LI o 3 CAL RCS LEVEL IN REACTOR BUILDING OPERATOR ACTIONS FOR A VALID ALARM:

o RESTORE RCS LEVEL PER OP-301, OP-402 AND/OR OP-404 o REFER TO AI-504 DISCUSSION:

DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

DRAWING'208-047 SHEET RC-27 h

SENSING ELEMENT: RC-202-LS AR-402 Rev. 22 Page 18

ENCLOSURE _1 r

f (Page 17 of 86)

'(

PSA-G ANNUNCIATOR RESPONSE PSA-Y-01-08 G-01-08 RC 1

INVENTORY LOW EVENT POINT 2046 t

INDICATED CONDITION:

l

~o RCS LEVEL IS <I46'-5.8" AS SENSED BY RC-163A-LS1A REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RCS LEVEL INDICATION, RC-201-LI1, RC-201-LI2, RC-202-LI o LOCAL RCS LEVEL IN REACTOR BUILDING OPERATT 6 :0NS FOR A VALID ALARM:

o RE$isE 4..S LEVEL PER OP-301, OP-402 AND/OR OP-404 o REFER TO AI-504 DISCUSSION:

DURING PERIODS OF LOW RCS LEVEL MONITOR THE OPERATING DECAY HEAT PUMP FOR SIGNS OF CAVITATION

REFERENCES:

DRAWING 208-047 SHEET RC-27 SENSING ELEMENT: RC-163A-LSIA AR-402 Rev. 22 Page 19

- ~-

~ _

ENCLOSURE 1 og Q

(Page 18 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y 02-01 G-02-01 9

I I

INSTRUMENT l

AIR PRESS LOW l

l-1 I

I EVENT POINT 0906 1

INDICATED CONDITION:-

o INSTRUMENT AIR PRESSURE IS <90 PSIG AS SENSED BY IA-18-PS l (

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o INSTRUMENT AIR PRESSURE INDICATOR IA-4-PI OPERATOR ACTIONS FOR A VALID ALARM:

o REFER T0 AP-470 o ENSURE IN HOUSE AIR COMPRESSORS ARE RUNNING o START OUTSIDE AIR COMPRESSORS l

o ENSURE SAV-647 BACKUP AIR SUPPLY PRESSURE REDUCING VALVE OPEN i

DISCUSSION:

INSTRUMENT AIR PRESSURE <90' PSIG WILL-ALSO DE-ENERGIZE IADR-2. -THE DRIER-MUST BE RESET LOCALLY WHEN INSTRUMENT AIR PRESSURE IS RESTORED.

REFERENCES:

DRAWING 208-037 SHEET IA-01 SENSING ELEMENT: IA-18-PS AR-402 Rev. 22 Page 20

ENCLOSURE 1 (Page 19 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 IA/SA COMP q

DISCH TEMP HIGH EVENT POINT 0898 l

INDICATED CONDITION:

o SAP-1A DISCHARGE TEMPERATURE IS >375* F AS SENSED BY SA-11-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LGCAL DISCHARGE TEMPERATURES ARE HIGH o SAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o START STANDBY COMPRESSORS.

o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

DISCUSSION:

l-IF DISCHARGE AIR TEMPERATURE REACHES 400* THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS l

i

REFERENCES:

DRAWING 208-051 SHEET SA-01

\\

SENSING ELEMENT: SA-11-TS AR-402 Rev. 22 Page 21-L-

t ENCLOSURE 1-

. ~]_

(Page 20 of 86)

.f s

=PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 1A/SA COMP DISCH TEMP HIGH EVENT POINT 0899 INDICATED CONDITION:

o SAP-1A AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY SA-5-TS REDUNDANT INDICATION WHICH WILL VERIFY: ALARM:

o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM:

o START STANDBY COMPRESSORS.

o' CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR, o VERIFY PROPER SC FLOW-TO AFTERC00LER DISCUSSION:

HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY.-IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 20$-051 SHEET.SA-01

,,g..

f

(_f SENSING ELEMENT: SA-5-TS AR-402 Rev. 22 Page 22

s ENCLOSURE 1

,3-

-(Page 21 of 86)

PSA-G ANNUNCIATOR RESPONSE lPSA-Y-02-02 G-02-C2 IA/SA COMP DISCH TEMP HIGH EVENT POINT 0904 INDICATED CONDITION:

o SAP-1B DISCHARGE ItiMPERATURE IS >375' F AS SENSED BY SA-12-TS A

.lj REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

4-o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM:

o START STANDBY COMPRESSORS, o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

DISCUSSION:

IF DISCHARGE AIR TEMPERATURE REACHES.400* THE COMPRESSOR WILL TRIP HIGH' DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051~~ SHEET SA-02

/^}

-(f

. l SENSING ELEMENT: SA-12-TS AR-402.

Rev 22 Page 23

,a w

w

w.. + -,,

4 ENCLOSURE 1 (Page 22 of-86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0905 INDICATED CONDITION:

o SAP-1B AFTER COOLER DISCHARGE TEMPERATURE IS >120* F AS SENSED BY SA-6-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM:

o START STANDBY COMPRESSORS.

o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

o VERIFY PROPER SC FLOW TO AFTERC00LER DISCUSSION:

HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-051 SHEET SA-02 b'v SENSING ELEMENT: SA-6-TS AR-402 Rev. 22 Page 24

_ _ ~ _

s ENCLOSURE 1~

(Page 23=of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02,

IA/SA COMP DISCH TEMP HIGH EVENT POINT 0910 INDICATED CONDITION:

o IAP-1A DISCHARGE TEMPERATURE IS >350' F AS SENSED BY IA-16-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DISCHARGE TEMPERATURES ARE HIGH l

OPERATOR ACTIONS FOR A VALID ALARM:-

o START STANDBY COMPRESSORS.

o CONSIDERATION-SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

i DISCUSSION:'

I-IF. DISCHARGE. AIR TEMPERATURE REACHES 375*,- AS SENSED BY IA-14-TS THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR'IS RUNNING LOADED CONTINUOUSLY. IF. AIR COMPRESSORS DO NOT ~ UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-01 SENSING ELEMENT: IA-16-TS l

AR-402.

Rev.'22 Page 25 t

ENCLOSURE 1 O-

(Page 24 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02 G-02-02 lA/SA COMP DISCH TEMP HIGH EVENT POINT 0911 INDICATED CONDITION:

o IAP-1A AFTER COOLER DISCHARGE TEMPERATURE IS >120" F AS SENSED BY IA-6-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

.o LOCAL DISCHARGE TEMPERATURES ARE HIGH OPERATOR ACTIONS FOR A VALID ALARM:

o START STANDBY COMPRESSORS.

o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

o VER'FY PROPER SC FLOW TO AFTERC00LER F.:

DISCUSSION:

HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED-CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-01 b

SENSING ELEMENT: IA-6-TS AR-402 Rev. 22 Page 26

~

J MCLOSURE 1

,y (Page 25 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-02 G-02-02 lA/SA COMP DiSCH TEMP HIGH EVENT POINT 0916 INDICATED CONDITION:

o IAP-1B DISCHARCE TEMPERATURE IS >350' F AS SENSED BY 1A-17-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DISCHARCE TEMPERATURES ARE HIGH OPERATOR ACTIONS-FOR A VALID ALARM:

o START STANDBY COMPRESSORS.

o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

DISCUSSION:

IF DISCHARGE AIR TEMPERAT'URE REACHES 375', AS SENSED BY IA-15-TS THE COMPRESSOR WILL TRIP HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY. IF AIR COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

REFERENCES:

DRAWING 208-037 SHEET IA-02 g

SENSING = ELEMENT: IA-17-TS AR-402 Rev. 22 Page 27

ENCLOSURE 1 m

V (Page 26 of 86)

. L,1 PSA-G ANNUNCIATOR RESK)NSE-PSA-Y-02-02 G-02-02 lA/SA' COMP DISCH TEMP HIGH EVENT POINT 0917 INDICATED CONDITION:

o IAP-1B AFTER COOLER DISCHARGE TEMPERATURE IS >120' F AS SENSED BY IA-7-TS 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o LOCAL DISCHARGE TEMPERATURES ARE HIGH l

l OPERATOR ACTIONS FOR A VALID ALARM:

l o START STANDBY COMPRESSORS.

o CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE COMPRESSOR.

o VERIFY PROPER SC FLOW-TO AFTERC00LER

~

l DISCUSSION:

(

HIGH DISCHARGE TEMPERATURES INDICATE AN AIR COMPRESSOR IS RUNNING LOADED CONTINUOUSLY, IF AIR-COMPRESSORS DO NOT UNLOAD CHECK AIR SYSTEMS FOR LEAKS

!~

REFERENCES:

DRAWING'208-037 SHEET IA-02 SENSING ELEMENT: IA-17-TS AR-402 P.ev. 22 Page 28

ENCLOSURE 1 O

(Page 27 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 IA/SA COMP MOTOR OVERLOAD EVENT POINT 0897 INDICATED CONDITION:

o SAP-1A MOTOR AMPS >115% RATED LOAD F

A t j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SAP-1A HIGH MOTOR AMPS o SAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION:

ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTIGATE MOTOR AND BREAKER OPERATION IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-051 SHEET SA-01

,V SENSING ELEMENT: 49 GVERLOAD RELAY

-AR-402 Rev. 22 Page 29

ENCLOSURE 1

('s y)-

-(Page 28 of 86)-

PSA-G ANNUNCIATOR RESPONSE

-PSA-Y-02-03 G-02-03 IA/SA COMP MOTOR OVERLOAD-EVENT POINT 0903 INDICATED CONDITION:

o SAP-1B MOTOR AMPS >115% RATED LOAD R'DUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SAP-1B HIGH MOTOR AMPS o SAP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER-OPERATION DISCUSSION:

ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTIGATE MOTOR AND BREAKER

. OPERATION.-

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-051 SHEET SA-02 C\\

-()

SENSING ELEMENT: 49 OVERLOAD RELAY

-AR-402 Rev. 22 Page 30-

4 ENCLOSURE 1

'r~')s -

(_,

(Page 29 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 IA/SA COMP MOTOR OVERLOAD EVENT POINT 0909 INDICATED CONDITION:

o IAP-IA MOTOR AMPS >115% RATED LOAD

[j

(

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o IAP-1A HIGH MOTOR AMPS o IAP-1A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PROPER INSTRUMENT AND STATION AIR PRESSURE o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION:

-ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTIGATE MOTOR AND BREAKER OPERATION.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-037 SHEET IA-01 m

/

\\

-L/

SENSING ELEMENT: 49 OVERLOAD RELAY AR-402:

Rev. 22 Psge 31

-.. -.. ~

9 ENCLOSURE 1

.p (Page 30 of C6)

(j "SA-G ANNUNCIATOR RESPONSE PSA-Y-02-03 G-02-03 4

1A/SA COMP MOTOR OVERLOAD EVENT POINT 0915 INDICATED CONDITION:

o IAP-1B MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o IAP-18 HIGH MOTOR AMPS o IAP-1B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PROPtR INSTRUMENT AND STATION AIR PRESSURE j-o INSPECT AIR COMPRESSOR FOR PROPER OPERATION DISCUSSION:

ELECTRICIANS SHOULD BE INSTRUCTED TO INVESTIGATE MOTOR AND BREAKER OPERATION, IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

f l

REFERENCES:

DRAWING 208-C37 SHEET IA-02 l

SENSING ELEMENT: 49 OVERLOAD RELAY

' AR-402 Rev. 22 Page 32

9 ENCLOSURE 1-(Page 31 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-02-08 G-02-08 ANNUNCIATOR l

OROUND i

P-EVENT POINT 0196 INDICATED CONDITION:

o POSITIVE OR NEGATIVE GROUND INDICATION IN ANNUNCIATOR GROUND CABINET REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT ELECTRICIANS FOR GROUND TROUBLESHOOTING DISCUSSION:

THIS ALARM INDICATES THERE IS A GROUND IN SOME DC ALARM CIRCUIT. NOTES SHOULD BE MADE OF ALARMS OR OPERATIONS THAT OCCURRED THE SAME TIME THE GROUND CAME IN TO ASSIST THE ELECTRICIANS IN FINDING THE GROUND.

J 4

REFERENCES:

DWG D1011-121 SENSING ELEMENT: ANNUNCIATOR PROCESSOR AR-402 Rev. 22 Page 33 T

a-E w

~

es '

ENCLOSURE 1

/

(Page 32 of-86)

.(

-PSA-G ANNUNCIATOR RESPONSE PSA-Y-03-01 G-03 _

l l

I I

SUBCOOLING J

l MARGIN l

l LOW I

I I

l I

I EVENT POINT 1954-INDICATED CONDITION:

o SUBC00 LING MARGIN IS <30' F AND THE REACTOR 15 TRIPPED REDUNDANT INDICATION WHICH WILL VERFY ALARM:

o.5ATURATION MONITOR METERS RC4-TI4, RC4-TIS o RCS - HIGH TEMPERATURE AND/OR LOW PRESSURE o SPDS MONITORS OPERATOR ACTIONS FOR A VALID ALARM:

o TAKE PROMPT AND APPROPRIATE ACTIONS IN ACCORDANCE WITH REQUIREMENTS OF THE E0P DISCUSSION:

THIS ALARM INDICATES A POSSIBLE SATURATED CONDITION IN THE RCS.

REFERENCES:

.EC-.209-047 RC-12, 205-047 SH. RC 11 SENSING ELEMENT:

RC3A-PT AR-402

'Rev. 22 Page 34

a b

1 ENCLOSURE =1 O-(Page 33 of 86)

PSA-G ANNUNCIATOR-RESPONSE PSA-Y-03-01 G-03-01

~n I

I SUBC00 LING I

1 MARGIN I

I Low I

I j

l I

1 EVENT POINT 1955 INDICATED CONDITION:

o SUBC00 LING MARGIN IS <30' F AND THE REACTOR IS TRIPPED i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SATURATION MONITOR METERS, RC4-TI4, RC4-TIS o RCS - HIGH TEMPERATURE AND/OR LOW PRESSURE o SPDS MONITORS OPERATOR ACTIONS FOR A VALID ALARM:

o TAKE PROMPT AND APPROPRIATE ACTIONS IN ACCORDANCE WITH REQUIREMENTS OF l

THE E0P DISCUSSION:

THIS ALARM INDICATES A POSSIBLE SATURATED CONDITION IN THE RCS.

l

REFERENCES:

SENSING ELEMENT:

AR-402.

Rev. 22 Dage 35

J ENCLOSURE 1 (Page 34 of 86)

PSA-G ANP!UNCIATOR RESPONSE PSA-Y-04-01 lG-04-01 l

l SC PUMP

--l TRIP

~

l l

I EVENT POINT 0329 INDICATED CONDITION:

o SCP-IA BREAKER IS OPEN WITH THE CONTROL HANDLE IN fHE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT WITH A RED FLAG ON SCP-1A CONTROL STATION, OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE SCP-1B OPERATING o IF NO SC PUMPS _ARE OPERATING CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE.

DISCUSSION:

THE PUMP WILL TRIP IF EITHER:

SCV-1, SCP-1A SUCTION VALVE CLOSES DB

-SCV-3, SCP-1A DISCHARGE VALVE CLOSES A LOSS OF DC POWER TO SCV-3 WILL CAUSE SCV-3 TO CLOSE.

REFERENCES:

DRAWING 208-052 SHEET SC-01 SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 22 Page 36

ENCLOSURE 1 (j]

f (Page 35 of 86)

PSA-G ANNUNCJATOR RESPONSE PSA-Y-04-01 G-04-01 I

I SC PUMP TRIP l

l I

I I

I EVENT POINT 0332 INDICATED CONDITION:

o-SCP-1B BREAKER IS OPEN WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON SCP-1B CONTROL STATION.

OPERATOR ACTIONS FOR A VALIO ALARM:

o ENSURE SCP-1A OPERATING o IF NO SC PUMPS ARE OPERATING CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE.

DISCUSSION:

THE PUMP WILL TRIP IF EITHER:

SCV-2, SCP-1B SUCTION VALVE CLOSES Oft SCV-4, SCP-1B DISCHARGE VALVE CLOSES A LOSS OF DC POWER TO SCV-4 WILL CAUSE SCV-4 TO CLOSE.

REFERENCES:

DRAWING 208-052 SHEET SC-02 SENSING ELEMENT: CONTROL STAT (0N CONTACTS

-AR-402 Rev. 22 Page 37

ENCLOSURE 1 h- )-

(Page 36 of 86)

PSA-C ANNUNCIATOR RESPONSE PSA-Y-04-02 G-04-02 SC PUMP MOTOR OVERLOAD EVENT POINT 0327 f

INDICATED CONDITION:

o SCP-1A MOTOR AMPS >115% RATED LOAD l

REDUNDANT INDICATION WHICH WILL VERIFY-ALARM:

o SCP-1A HIGH MOTOR AMPS o SCP-IA TRIPS OPERATOR ACTIONS FOR A VALID ALARM:

o CONSIDERATION SHOULD BE GIVEN TO STARTING SCP-1B AND SECURING SCP-1A l

o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED.

I INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

. DRAWING 208-052 SHEET SC-01

-C/

SENSING ELEMENT:74 SCP-A OVERLOAD RELAY l

AR-402-'

Rev. 22 Page 38

.-~

a ENCLOSURE 1

{Q _

j (Page 37 of 861

'PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-02 G-04-02 SC PUMP MOTOR OVERL OAD 6

t i

EVENT POINT 0330 INDICATED CONDITION:

o SCP-18 MOTOR AMPS >115% RATED LOAD

, I'\\

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SCP-1B HIGH MOTOR AMPS o SCP-1B TRIPS OPERATOR-ACTIONS FOR A VALID ALARM:

o CONSIDERATION SHOULD BE GIVEN TO STARTING SCP-1A AND SECURING SCP-1B o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGE15 DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED.

-INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER-TRIP.

REFERENCES:

DRAWING 208-052 SHEET SC-02 SENSING ELEMENT:74 SCP-B OVERLOAD RELAY AR-402-Rev. 22 Page 39

)

1 t

ENCLOSURE 1-

, g( j (Page 38 of 86).

PSA-G ANNUNCIATOR RESPONSE

-PSA-Y-04-03 G-04-03 SC SYSTEM TROUBLE EVENT POINT 0333 INDICATED CONDITION:

o SC SURGE TANK LEVEL IS >11'6" AS SENSED BY SC-68-LS

- (A)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SC SURGE TANK LEVEL INDICATOR. SC-70-LI o LOCAL SC SURGE TANK SIGHT GLASS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE SC SURGE TANK AUTO FILL VALVE, SCV-146 CLOSED, IF NOT, CLOSE MANUAL ISOLATION VALVE, SCV-108 DISCUSSION:

. SC SURGE TANK AUTO FILL VALVE, SCV-146 OPENS AT 7.5' AND CLOSES AT 10'

REFERENCES:

DRAWING 208-052 SHEET SC-05 I,,,,/

SENSING ELEMENT:.SC-68-LS AR-402-;

Rev. 22.

Page 40

._ ~

ENCLOSURE 1

./

~(

(Page 39 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-03

-G-04-03 SC SYSTEM TROUBLE EVENT POINT 0334 INDICATED CONDITION:

o SC SURGE TANK LEVEL IS <6' AS SENSED BY SC-68-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o SC SURGE TANK LEVEL INDICATOR, SC-70-LI o LOCAL SC SURCE TANK SIGHT GLASS OPERATOR ACTIONS FOR A VALIO ALARM:

o ENSURE SC SURGE TANK AUTO FILL VALVE, 3CV-146 OPEN, IF NOT, MANUALLY l

OPEN SCV-146.

.o INSPECT SC SYSTEM FOR LEAKAGE INCLUDING THE TEMPORARY SAMPLE MANIFOLD

.BEHIND THE NA0 OFFICE.

DISCUSSION:

IF SC SURGE TANK LEVEL CANNOT BE RESTORED CONSIDERATION SHOULD BE GIVEN

.TO TRIPPING THE TURBINE.

SC SURGE TANK AUTO FILL VALVE, SCV-146 OPENS AT 7.5' AND CLOSES AT 10' l

.p

REFERENCES:

DRAWING 208-032' SHEET SC-05 x_.

SENSING ELEMENT: SC-68-LS AR-402'-

Rev. 22 Page 41 1.

m ENCLOSURE l' q:

(Page 40 of 86)

'"~

PSA-G ANNUNCIATOR RESPONSE

'PSA-Y-04-03 G-04-03 SC SYSTEM TROUBLE EVENT POINT 0335 INDICATED CONDITION:

o SC SYSTEM PRESSURE IS <50 PSIG AS SENSED BY SC-89-PS REDUNDANT INDICATION WHICH'WILL VERIFY ALARM:

o LOCAL SC SYSTEM PRESSURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE BACKUP SC PUMP AUTO STARTS o IF SC SYSTEM PRESSURE CANNOT BE RECOVERED THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE.

DISCUSSION:

STAND 8Y SC' PUMP SHOULD AUTO START WHEN SC SYSTEM PRESSURE IS <55 PSIG FOR

>10 SECONDS.

REFERENCES:

DRAWING 208-05e SHEETLSC-05

.( /

SENSING-ELEMENT: SC-89-PS AR-402 Rev. 22 Page 42

[ /;-

ENCLOSURE 1

]

(Page 41 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-04 G-04-04 SC PUMP AUTO START EVENT POINT 0328 INDICATED CONDITION:

o SCP-1A BREAKER CLO5ED AND CONTROL STATION IS IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON SCP-1A CONTROL STATION l

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PUMP DISCHARCE VALVE OPENS, SCV-3 o VERIFY SC SYSTEM PRESSURE NORMAL o IF NORMAL SC SYSTEM OPERATION IS NOT POSSIBLE THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE.

DISCUSSION:

STANDBY SC PUMP.SHOULD AUTO START WHEN SC SYSTEM PRESSURE IS <55 PSIG FOR

>10 SECONDS.

REFERENCES:

DRAWING 208-052 SHEET SC-01 SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 22 Page 43 i

ENCLOSEE_1 (Page 42 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-04 G-04-04

^

SC PUMP AUTO START EVENT POINT 0331 INDICATED CONDITION:

o SCP-1B BREAKER CLOSED AND CONTROL STATION IS IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON SCP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE PUMP DISCHARGE VALVE OPENS, SCV-4 o VERIFY SC SYSTEM PRESSURE NORMAL o IF NORMAL SC SYSTEM OPERATION IS NOT POSSIBLE THEN CONSIDERATION SHOULD BE GIVEN TO TRIPPING THE MAIN TURBINE.

DISCUSSION:

STANDBY SC PUMP SHOULD AUTO START WHEN 5" SYSTEM PRESSURE IS <55 PS1G FOR

>IO SECONDS.

REFERENCES:

D'MWING 208-052 SHEET SC-02 SENSING ELEMENT: CONTROL STATION CONTACTS l

AR-402 Rev. 22

' age 44 m

i l

ENCLOSURE 1 O

(Page 43 of 86)

LJ PSA-G ANNL'NCIATOR RESPONSE PSA-Y-04-08 G-04-08 EVACUATION TONE GENERATOR FAILURE EVENT POINT 1907 INDICATED CONDITION:

o EVACUATION TONE GENERATOR 1 HAS FAILED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EMERCENCY EVACUATION ALARMS WILL NOT OPERATE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY ELECTRICIANS DISCUSSION:

THIS ALARM INDICATES NO EMERCENCY EVACUATION ALARMS ARE AVAILABLE REFE9ENCES:

DRAWING 208-064 SHEET ME-04

()

SENSING ELEMENT: TONE CEN #1 ANOX AR-402 Rev. 22 Page 45

ENCLOSURE 1 (Page 44 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-04-08 G-04-08 EVACUATION TONE GENERATOR FAILURE EVENT POINT 1918 INDICATED CONDITION:

o EVACUATION TONE GENERATOR 2 HAS FAILED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EMERGENCY EVACUATION ALARMS WILL NOT OPERATE OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY ELECTRICIANS DISCUSSION:

THIS ALARM INDICATES NO EMERGENCY EVACUATION ALARMS ARE AVAILABLE

REFERENCES:

DRAWING 8-064 SHEET ME-04 O

d SENSING ELEMENT: TONE GEN #2 AN0X AR-402 Rev. 22 Page 46

Q(LOSURE 1 (Page 45 cf 86)

PSA-C ANNUNCIATOR RESPONSE PSA-Y-05-01 6-05-01 bq j

1 I

I DW FROM CR 1 I

I WTR QUALITY l

l l

lMPURE I

I I

I i

l i

i EVENT POINT 0809 INDICATED CONDITION:

t o DEMIN WATER FROM CR-1 HAS ISOLATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DWV-346 IS CLOSED o DEMIN WATER SAMPLE PANEL INDICATES HIGH READINGS ON ONE OR MORE OF THE FOLLOWING:

SODIUM SILICA DISSOLVED OXYGEN ORGANIC CARBON CATION CONDUCTIVITY OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY CHEMISTRY o SUSPEND ALL UNNECESSARY DEMIN WATER USE I

DISCUSSION:

DEMIN WATER MAKEUP TO SW AND DC SURGE TANKS IS NOT ISOLATED BY DWV-346.

MAKEUP SUPPLY TO THE AUX BLDG DEMIN WATER TANK IS UNAVAILABLE AS LONG AS DWV-346 IS CLOSED. UNDER NORMAL USAGE THIS TANK VOLUME (AT NWL) WILL LAST MORE THAN AN HOUR, THEREFORE IF THERE IS A SIGNIFICANT PROBLEM WITH CR-1/2 DEMIN WATER CHEMISTRY CONSIDERATION SHOULD BE GIVEN TO LINING UP CR-4/5 DEMIN WATER TO THE CR-1/2 SYSTEM. THIS ALTERNATIVE MAY REQUIRE SEVERAL HOURS TO FLUSH.THE CROSS TIE LINE FROM CR-4/5.

DWV-346 CAN BE; MANUALLY OVERRIDDEN TO THE OPEN POSITION BY CHEMISTRY l /~'T -

REFERENCES:

l DRAWING 208-025 SHEET DW-07 SENSING ELEMENT:. 2X DW-32-CR AR-402-Rev. 22-Page 47

4 ENCLOSURE 1 O

(Page 4f of 86) v

. PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-02 G-05-02 DW TRANSFER PP TROUBLE EVENT POINT 1566 INDICATED CONDITION:

o WTP 6A OR WTP-6B BREAKER CLOSED WITH THEIR CONTROL STATIONS IN NORMAL AFTER STOP.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON THE WTP-6A OR WTP-6B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o CONTACT CR-1 & 2 TO ENSURE PROPER OPERATION OF WTP-6A OR WTP-6B DISCUSSION:

THE DEMIN WATER TRANSFER PUMPS WILL AUTO START IF THE RUNNING PUMP TRIPS AND THE STANDBY PUMP IS IN NORMAL AF1ER STOP.

THE STANDBY PUMP WILL At 50 AUTO START IF A LOW LEVEL IN WTT-1 CLEARS.

REFERENCES:

ORAWINC 208-063 SHEET WT-08 SENSING EL UENT:' CONTACTS IN THE CONTROL STATION AR-402 Rev. 22 Page 48

~... - -...

ENCLOSURE 1 (Page 47 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-02 C-05-02 I

I DW TRANSFER PP TROU8LE EVENT POINT 1569 INDICATED CONDITION:

o WTP-6A OR WTP-6B BREAKER OPEN WITH THEIR CONTROL STATIONS IN NORMAL AFTER START.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON THE WTP-6A OR WTP-6B CONTROL STATION o LOW LEVEL IN WTT-1, WT-32-LI2 OPERATOR ACTIONS FOR A '!ALID ALARM:

o CONTACT CR-1 & 2 TO ENSURE PROPER OPERATION OF WTP-6A OR WTP-6B o NOTIFY CR-1/2 IF PROBLEM IS WITH LOW TANK LEVEL DISCUSSION:

A LOW LEVEL IN CR-1/2 DEMIN WATER STORACE TANK WILL TRIP THE DEMIN WATER TRANSFER PUMP.

t a

REFERENCES:

DRAWING 208-063 SKEET WT-08

-()

SENSING ELEMENT: CONTACTS IN THE CONTROL STATION

-AR-402-Rev. 22 Page 49

ENCLOSURE 1 O'

(Page 48 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUXBLDGDW SYSTEM TROUBLE EVENT POINT 0244 INDICATED CONDITION:

o DWT-1 LEVEL IS <3 FT AS SENSED BY DW-15-LS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DWT-1 LOCAL LEVEL SIGHT CLASS OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE AUTOMATIC LEVEL CONTROL VALVE DWV-325 IS OPEN IF NOT, OPEN

-CONTROL VALVE BYPASS, DWV-329 o MINIMIZE DEMIN WATER USAGE IN PLANT DISCUSSION:

FILL WATER FOR THE DEMIN WATER STORAGE TANK IS SUPPLIED FROM UNITS 1 AND 2 DEMIN WATER TRANSFER PUMP.

REFERENCES:

DRAWING 208-025 SHEET DW-06 SENSING ELEMENT: DW-15-LS

-- AR-402 =

Rev. 22

-Page 50

=.

ENCLOSURE 1 (Page 49 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW i

SYSTEM TROUBLE EVENT POINT 0245 INDICATED CONDITION:

o DWP-1A/IB DISCHARGE PRESSURE IS <80 PSIG AS SENSED BY DW-6-PS2.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DWP-1A/IB LOCAL DISCHARGE PRESSURE INDICATION o STANDBY PUMP AUTO STARTS OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY DWT-1 LEVEL NORMAL.

o CHECK AUX BUILDING FOR DW LEAKS o ENSURE PROPER OPERATION OF DW PUMPS RECIRC VALVE, DWV-320 DISCUSSION:

IF DW PUMP RECIRC VALVE, DWV-320 IS OPEN CONSIDERATION SHOULD BE GIVEN TO ISOLATING THE VALVE BY CLOSING DWV-134

REFERENCES:

DRAWING 208-025 SHEET DW-06 l,

SENSING ELEMENT: DW 6-PS2 AR-402 Rev. 22

-Page 51.

L.

l i

ENCLOSURE 1 (Page 50 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA.-Y-05-03 G-05-03 1

AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0246 INDICATED CONDITION:

o DWT-1 LEVEL IS >7.5 FT AS SENSED BY DW-17-LS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DWT-1 LOCAL SIGHT CLASS OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY AUTO CONTROL VALVE, DWV-325 IS CLOSED IF NOT ISOLATE THE AUTO CONTROL VALVE AND IT'S BYPASS DISCUSSION:

DWT-1 MAY BE DRAINED TO THE AUX BUILDING SUMP VIA DWV-142 LOCATED ON 143' ELEVATION AUX BUILDING.

REFERENCES:

- DRAWING 208-025 SHEET DW-06 SENSING ELEMENT:-DW-17-LS AR-402 Rev. 22 Page 52

t D{ CLOSURE _1 I

(Pape 51 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDO DW SYSTEM TROUBLE EVENT POINT 0247 t

INDICATED CONDITION:

o DWFL-1 DIFFERENTIAL PRESSURE IS >25 PSID AS SENSED BY DW-9-DPS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o DWFL-1 LOCAL PRESSURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o BYPASS AND CHANGE DWFL-1 PER OP-418.

DISCUSSION:

REFERENCES:

DRAWING 208-025 SHEET DW-06

'V SENSING ELEMENT: 'DW-9-DPS AR-402 Rev. 22 Page 53

i ENCLOSURE 1 O

.~

(Page 52 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 l

AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0248 INDICATED CONDITION:

4 o DWP-IA BREAKER CLOSED WITH THE CONTROL STATION IN NORMAL AFTER STOP.

t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON DWP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER DW SYSTEM OPERATION.

O INVESTIGATE CAUSE OF AUTO START DISCUSSION:

DWP-1A WILL AUTO START WHEN DW PRESSURE IS <100 PSIG AS SENSED BY DW-6-PS1

REFERENCES:

DRAWING 208-025 SHEET DW-01 SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 22 Page 54

ENCLOSURE 1 O

(Page 53 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0249 INDICATED CONDITION:

o DWP-1A BREAKER OPEN WITH THE CONTROL STATION IN NORMAL AFTER START.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON DWP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY DWP-1B STARTS.

o INVESTIGATE CAUSE OF TRIP.

DISCUSSION:

DWP-1A WILL TRIP IF LEVEL IN DWT-1 IS <2 FEET AS SENSED BY DW-14-LS

REFERENCES:

DRAWING 208-025 SHEET DW-01 SENSING ELEMENT: CONTROL STATION CONTACTS

-AR-402 Rev. 22--

Page 55

l ENCLOSURE 1 O

(Page 54 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0250 INDICATED CONDITION:

o DWP-1B BREAKER CLOSED WITH THE CONTROL STATION IN NORMAL AFTER STOP.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON DWP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY PROPER DW SYSTEM OPERATION.

o INVESTICATE CAUSE OF AUTO START DISCUSSION:

DWP-1B WILL AUTO START WHEN DW PRESSURE IS <100 PSIG AS SENSED BY DW-6-PS1 4

REFERENCES:

DRAWING 208-D25 SHEET DW-02

\\

SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 22 Page 56

~ -.-

ENCLOSURE 1 1

(Page 55 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-05-03 G-05-03 AUX BLDG DW SYSTEM TROUBLE EVENT POINT 0251 INDICATED CONDITION:

o DWP-13 BREAKER OPEN WITH THE CONTROL STATION IN NORMAL AFTER START.

i O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o GREEN LIGHT ON WITH A RED FLAG ON DWP-1B CONTROL STATION i

l l-OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY DWP-1A STARTS.

o INVESTIGATE CAUSE OF TRIP, DISCUSSION:

DWP-1B WILL TRIP IF LEVEL IN DWT-1 IS <2 FEET AS SENSED BY DW-14-LS l

L l

REFERENCES:

DRAWING 208-025 SHEET DW-02

~

SENSING ELEMENT: CONTROL STATION CONTACTS

-AR-402

~Rev. 22 Page.57

ENCLOSURE 1 (Page 56 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-01 G-06-01 i

I I

BORIC ACID PP l

I TRIP j

l i

i I

I I

I 6

EVENT POINT 0068 INDICATED CONDITION:

o CAP-1A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON CAP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE cal'5E OF PUMP TRIP o IF BORIC ACID PUMP OPERATION IS REQUIRED START CAP-IB DISCUSSION:

SHUTTING DOWN CAP-1A LOCALLY WILL CAUSE THIS ALARM TO ACTUATE

REFERENCES:

DRAWING 208-010 SHEET CA-01 SENSING ELEMENT: CONTACTS IN CONTROL STATION AR-402 Rev. 22 Page 58

~

..a...-

fdCLOSURE 1 (Page 57 of 86)

PSA-C ANNUNCIATOR RESPONSE PSA-Y-06-01 G-06-01 I

I I

I BORIC ACID PP l

l I

I TRIP I

I I

I l

EVENT POINT 0069 INDICATED CONDITION:

o CAP-1B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSIT 10tl REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON CAP 18 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF PUMP TRIP o IF BORIC ACID PUMP OPERATION IS REQUIRED START CAP-1A DISCUSSION:

SHUTTING DOWN CAP-1B LOCALLY WILL CAUSE THIS ALARM TO ACTUATE

REFERENCES:

DRAWING 208-010' SHEET CA 02 SENSING ELEMENT: CONTACTS IN CONTROL STATION AR-102 Rev. 22 Page 59

ENCLOSEL1 (Page 58 of 86) i PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 G-06-02 i

i BORIC ACID STOR TNK LEVEL

{

HIGH/ LOW EVENT POINT 0072 l

INDICATED CONDITION:

o CAT-5A LEVEL IS >95" WATER AS SENSED BY CA-11-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-201 o LOCAL TANK LEVEL INDICATION 4

OPERATOR ACTIONS FOR A VALIO ALARM:

o INVESTIGATE CAUSE OF HIGH LEVEL.

o IF BAST FILL IS IN PROGRESS. STOP THE FILL.

l DISCUSSION:

BORIC ACID STORAGE TANKS OVERFLOW TO letE 119' FLOOR. IF A SPILL OCCURS NOTIFY HEALTH PHYSICS.

i

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMENT: CA-11-LS AR-402 Rev. 22 Page 60

i i

j LNCLQiML1 (Page 59 of 86) j PSA-G ANNUNCIATOR RESPONSE PSA Y-06-02 G-06-02 l

i l

1 l

BORIC ACID STOR TNK LEVEL Hl0H/ LOW

[

EVENT POINT 0073 INDICATED CONDITION:

o CAT-5A LEVEL IS <30" WATER AS SENSEli BY CA-11-LS O

Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o COMPUTER POINT X-201 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW LEVEL.

o FILL BAST AS REQUIRED.

DISCUSSION:

THIS CONDITION SHOULD ALSO DE-ENERGIZE-THE BAST HEATERS.

I

REFERENCES:

DRAWING 208-010 SHEET CA-24 c

SENSING ELEMENT: CA-11-LS i

l AR-402' Rev. 72 Page 61

_.._.....__.._.m_

j GCLOSURE 1 (Page 60 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 G-06-02 i

(

1 BORIC ACID STOR TNK LEVEL HIGH/ LOW

' - - " ' ~

n i

EVENT POINT 0076 l

1 INDICATED CONDITION:

o CAT-5B LEVEL IS >95" WATER AS SENSED BY CA-13-LS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-204 o LOCAL TANK LEVEL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH LEVEL.

o IF BAST FILL IS IN PROGRESS, STOP THE FILL.

DISCUSSION:

PORIC ACID STORAGE TANKS OVERFLOW TO THE 119' FLOOR. IF A SPILL OCCURS NOTIFY HEALTl! PHYSICS.

t l

REFERENCES:

DRAWING 208-010 SHEET CA-24 V

SENSING ELEMENT: CA-13-LS AR-402 Rev. 22 Page 62

(.

)

(Pcge 61 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-02 G-06-02

_.e-..

BQNC AO:D

)

9.iOR TNh I cT!!!L H! tin A DW

. -. - -..i E \\ ;'iT P o l N T 0 0 7 7 INDICATED CONDITION:

o CAT-50 LEVEL IS <30" WATER AS SENSED BY CA-13-LS

(~x,

)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-204 o LOCAL TANK LEVEL INDICATION OPERAIOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF LOW LEVEL.

o FILL BAST AS REQUIRED.

DISCUSSION:

THIS CONDITION SHOULD ALSO DE-ENERGIZE THE BAST HEATERS.

REFERENCES:

DRAWING 208-010 SHEET CA-24

-s j

\\

(_)

SENSING ELEMENT: CA-13-LS l

AR-402 Rev. 22 Page 63

__._ _ ~ _.._.. _ _ _

i r

EELOSURE_1 I

(Page 62 of 86)

[

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06 '

i BORIC ACID STOR TNK TEMP HIGH/ LOW i

EVENT POINT 0070 INDICATED CONDITION:

9 o CAT-5A TEMPERATURE IS 104' F AS SENSED BY CA-10-TSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

[

o COMPUTER POINT X-200 o LOCA!. TANv TE.MPfRATURE INDICATION OPERATOR ACTIONS FOR A Vm.ID ALARM:

o ENSURE BAST HEATER, CAHE-3A IN AUTO.

o INVESTICATE CAUSC 0F HIGt! Tr.MPERATURE.

e' SECURE BAST HEATERS IF ON, DISCUSSION:

THE BAST HEATERS CYCLE ON AT 156' F AND CYCLE OFF AT 162' F.

1

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMENT: CA-10-TS1 AR-402 Rev. 22 Page 64-

_ ~

_. -. _ _ -. - _.. _ _.. _. ~. _

EBCLOSURE 1 i

(Page 63 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06-03 P

wORIC ACID STOR TNK TEMP HIGH/ LOW ll EVENT POINT 0071 INDICATED CONDITION:

o CAT-5A TEMPERATURE IS <152* F AS SENSED BY CA-10-TSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-200 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY BAST LEVEL IS >30" WATER.

o ENSURE BAST HEATER, CAHE-3A IN AUTO.

o INVESTIGATE CAUSE OF LOW TEMPERATURE.

o PLACE BAST HEATERS IN ON.

l DISCUSSION:

l THE BAST HEATERS CYCLE ON AT 156* F AND CYCLE OFF AT 162* F.

i

REFERENCES:

DRAWING 208-010~ SHEET CA-24 SENSING ELEMEh'T: CA-10-TS1

-AR-402

-Rev. 22 Page 65

ENCLOSURE 1 (Page 64 of 86)

PSA-G ANNUNCIATOR RESPONSE-

!PSA-Y-06-03 G-06-03 1

BORIC ACID STOR TNK TEMP HIGH/ LOW i

~

EVENT POINT 0074 INDICATED CONDITION:

o CAT-58 TEMPERATURE IS >I64' F AS SENSED BY CA-12-TSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-203 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE BAST HEATER ~AHE-38 IN AUTO.

o INVESTIGATE CAUSE OF HIGH TEMPERATURE.

o SECURE BAST HEATERS IF ON.

DISCUSSION:

THE BAST HEATERS CYCLE ON AT 156' F AND CYCLE OFF AT 162' F.

REFERENCES:

DRAWING 208-010 SHEET CA-24 5

-SENSING ELEMENT: CA-12-TS1 AR-402 Rev. 22 Page 66 V

-.m._..

.~

.4

,--..,,v..

i 1

ENCLOSURE 1

[

(Page 65 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-03 G-06-03 BORIC ACID STOR TNK TEMP HIGH/ LOW c

EVENT POINT 0075 INDICATED CONDITION:

'o CAT-5B TEMPERATURE IS <152*F AS SENSED BY CA-12-TS1, REDUNEANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X-203 o LOCAL TANK TEMPERATURE INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY BAST LEVEL IS >30" WATER.

o ENSURE BAST HEATER, CAHE-38 IN AUTO.

o INVESTIGATE CAUSE OF LOW TEMPERATURE.

c PLACE BAST HEATERS IN ON.

DISCUSSION:

i THE BAST HEATERS CYCLE ON AT 156' F AND CYCLE OFF AT 162* F.

l

REFERENCES:

DRAWING 208-010 SHEET CA-24 SENSING ELEMENT: CA-12-TS1 l

AR-402 -

Rev. 22 Page 67

~

.. ~ - - -.

t ENCLOSURE 1 (Page 66 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-04 G-06-04 HEAT TRACING DE ENEROlZED EVENT POINT 1994 INDICATED CONDITION:

o HEAT TRACING FROM ES BUS "A" IS DE-ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON HEAT TRACE PANEL LOCATED BY ESMCC-3A2 OPERATOR ACTIONS FOR A VALID ALARM:

o RESET HEAT TRACE CIRCUITS BY DEPRESSING RESET PUSH-BUTTON LOCATED ON HEAT TRACE PANEL NEAR ESMCC-3A2 DISCUSSION:

480V ESA LOCK 0UT WILL DE-ENERGIZE HEAT TRACE AND HEAT TRACE WILL NOT BE ABLE TO BE RESET UNTIL THIS LOCK 0UT IS RESET.

DEPRESSING THE TEST PUSH-BUTTON ON THE HEAT TRACE PANEL WILL DE-ENERGIZE HEAT TRACE. THE RESET PUSH-BUTTON WILL HAVE TO BE DEPRESSED TO RE-ENERGIZE THE HEAT TRACE CIRCUITS,

REFERENCES:

DRAWING 208-035 SHEET HT-03 SENSING ELEMENT: 42-1A 2A,3A,4A,5A HEAT TRACE CONTACTS AR-402 Rev. 22 Page 6B

~.

i ENCLOSURE 1 (Page 67 of 86) t PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-04 G-06-04 I

HEAT TRACING DE ENERGlZED EVENT POINT 1995 I

INDICATED CONDITION:

o HEAT TRACING FROM ES BUS "B" IS DE-ENERGIZED f3Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON HEAT TRACE PANEL LOCATED ON 95' BY AUX BLDG ELEVATOR OPERATOR ACTIONS FOR A VALID ALARM:

o RESET HEAT TRACE CIRCUITS BY DEPRESSING RESET PUSH-BUTTON LOCATED ON HEAT TRACE PANEL NEAR AUX BLDG ELEVATOR ON 95' ELEVATION.

DISCUSSION:

480V ESB LOCKOUT WILL DE-ENERGIZE HEAT TRACE AND HEAT TRACE WILL NOT BE ABLc TO BE RESET UNTIL THIS LOCKOUT IS RESET.

DEPRESSING THE TEST PUSH-BUTTON ON THE HEAT TRACE PANEL WILL DE-ENERGIZE HEAT TRACE. THE RESET PUSH-BilTTON WILL HAVE TO BE DEPRESSED TO RE-ENERGIZE THE HEAT TRACE CIRCUITS.

REFERENCES:

DRAWING 208-0?5 SHEET HT-01 SENSING ELEMENT: 42-1B,28,38,4B HEAT TRACE CONTACTS AR-402 Rev. 22 Page 69

ENCLOSURE 1 O

(Page 68 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-05 G-06-05 GW PUMP TRIP EVENT POINT 1247 4

INDICATED CONDITION:

o GWP-1A BREAKER OPEN WITH CONTROL DANDLE IN THE NORMAL AFTER START POSITION.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON GWP-1A CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE GWP-1B IS OPERATING.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

STOPPING GWP-1A LOCALLY WILL ACTUATE THIS ALARM A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER B0OSTER PUMPS.

REFERENCES:

DRAWING 208-034 SHEET GW-01 L-SENSING ELEMENT: CONTACTS IN THE CONTROL STATION l

AR-402

.Rev. 22 Page 70-

l i

ENCLOSURE 1 (Page 69 of 86)

PSA-G ANNUNCIATOR RESPONSE M A-Y-06-05 G-06-05 GW PUMP 3;p i

EVENT POINT 1249 INDICATED CONDITION:

o GWP-1B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START

POSITION, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LICHT ON WITH A RED FLAC ON GWP-1B CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALAkM:

o ENSURE CWP-1A IS OPERATING.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

STOPPING GWP-1B LOCALLY WILL 4 70 ATE THIS ALARM A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS.

REFERENCES:

-DRAWING 208-034' SHEET GW-02 SENSING ELEMENT: CONTACTS IN THE CONTROL STATION i

.AR-402 Rev. 22 Page 71

4 ENCLOSURL1 (Page 70 of 86)

PSA-G ANNUNCIATOR RESPONSF PSA-Y-06-06 G-06-06 4

A GW PRESS LOW l

t EVENT POINT 1245 INDICATED CONDITION:

o GLAND WATER PRESSURE IS <190 PSIG AS SENSED BY CW-39-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o STANDBY GLAND WATER PUMP /JTO STARTS.

o LOCAL GLAND WATER PRESSURE LOW.

E OPERATOR ACTIONS FOR A VAU D ALARM:

o ENSURE ST/WBY GLAND WATER PUMP IS RUNNING.

o INVESTIGATE CAUSE OF LOW PRESSURE CONDITION.

DISCUSSION:

A LOSS OF Ct.AND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS.

REFERENCES:

DRAWING 208-034 SHEET GW-01 SENSTNG ELEMENT: GW-39-PS AR-402 Rev. 22 Page 72

1 l

l ENCLOSURE 1 (Page 71 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-07 G-06-07 GW PUMP MOTOR OVERLOAD I

EVENT POINT 1253 INDICATED CONDITION:

o GWP-1A MOTOR AMPS >115% RATED LOAD a

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CWP-1A TRIPS

, o HIGH AMPS READ LOCALLY ON THE 480V BUS l.....

ULT dATOR ACTIONS FOR A VALID ALARM:

o CONSIDERATION SHOULD BE GIVEN TO STARTING GWP-1B AND STOPPING GWP-1A o IF GWP-1A HAS TRIPPED THEN ENSURE GWP-1B IS OPERATING.

o INSPECT GWP-1A FOR ABNOP. MAL OPERATION DISCUSSION:

A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-034 SHEET GW-01 (q

SENSING ELEMENT: 49X OVERLOAD RELAY AR-402 Rev. 22 Page 73

ENCLOSURE 1 (Page 72 of 86)

PSA-G ANNUNCIATOR RESPONSE PSAg03-07 G-06-07 GW PUMP MOTOR OVERLOAD EVENT POINT 1254 INDICATED CONDITION:

o CWP-1B MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GWP-1B TRIPS o HIGH AMPS READ LOCALLY ON THE 480V BUS OPERATOR ACTIONS FOR A VALID ALARM:

o CONSIDERATION SHOULD BE GIVEN TO STARTING GWP-1A AND STOPPING GWP-18 o IF GWP-18 HAS TRIPPED THEN ENSURE GWP-1A IS OPERATING.

o INSPECT GWP-1B FOR ABNORMAL OPERATION DISCUSSION:

A LOSS OF GLAND WATER MAY CAUSE SEVERE WATER HAMMER IN THE SEAL RETURN LINES FROM THE MAIN FEED PUMPS AND THE FEEDWATER BOOSTER PUMPS.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-034 SHEET CW-02

'Q SENSING ELEMENT: 49X OVERLOAD RELAY l

l AR-402 Rev. 22 Page 74

9 ENCLOSURE 1 O

(Page 73 of 86)

PSA-G ANNUNCIA10R RESPONSE PSA-Y-06-08 G-06-08 GW PUMP AUTO START EVENT POINT 1246 INDICATED CONDITION:

o GWP-IA BREAKER CLOSED WITH CONTROL HAN?LE IN NORMAL AFTER' STOP D

, Q REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON GWP-IA CONTROL STATION OPERATOR AGIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW GLAND WATER PRESSURE DISCUSSION:

THE GLAND WATER PUMP THAT IS SELECTED ON THE LOCAL CONTROL STATION WILL AUTO START AT <I95 PSIG. THE NON SELECTED GLAND WATER PUMP WILL START AT

<I85 PSIG GLAND WA1ER PRESSURE.

REFERENCES:

DRAWING 208-034 SHEET GW-01 p) x_

SENSING ELEMENT: CONTROL STATION CONTACTS AR-402 Rev. 22 Page 75

-. -.~ _.._ - -.-.

1 ENCLOSURE 1 O

=

(Page 74 of 86).

~

PSA-G ANNUNCIATOR RESPONSE PSA-Y-06-08 G-06-08 i

l I

l l

l GW PUMP AUTO START l

l 2222-2 EVENT POINT 1248 INDICATED CONDITION:

o GWP-1B BREAKER CLOSED WITH CONTROL HANDLE IN NORMAL'AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON GWP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM; o INVESTICATE CAUSE OF LOW GLAND. WATER PRESSURE DISCUSSION:

THE GLAND WATER PUMP THAT-IS SELECTED ON THE LOCAL CONTROL STATION WILL AUTO START AT <195 PSIG. THE NON-SELELTED GLAND WATER PUMP WILL START AT

.<185 PSIG GLAND WATER PRESSURE.

1

REFERENCES:

DRAWING 208-034 SHEET GW-02 O

- () -

SENSING ELEMENT: CONTROL STATION CONTACTS i

AR-402 Rev~. 22 Page 76

-y

ENCLOSURE 1 (Page 75 of 86)

PSA-C ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 I

I l

l SPENT FUEL POOL LEVEL l

l

.l l

HIGH/ LOW I

I I

I EVENT POINT 0340 INDICATED CONDITION:

o SPENT FUEL POOL "A" LEVEL > +.5 FT AS SENSED BY SF-1-LS1 USING 158'6" AS A REFERENCE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LIl OPERATOR ACTIONS FOR A VALID ALARM:

o IF FILLING SPENT FUEL POOLS, SECURE FILLING.

o VERII-Y SPENT FUEL COOLING VALVE LINEUP.

o REDUCE SPENT FUEL POOL LEVEL BELOW ALARM SETPOINT DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS E(UATES TO 158'6" IF CWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT DECREASING.

IF BWST LEVEL IS DROPPING 20NSIDERATION SH0l'LD BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED.

IF SF TRANSFER TUBES ARE OPEN CHANCES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 51EET SF-04 O

V SENSING ELEMENT: SF-1-LS1 AR-402 Rev. 22 Page 77

ENCLOSURE 1 (s

.t

)

~~~

_(Page 76 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 l

l SPENT FUEL POOL LEVEL l

l l

l HIGH/ LOW l

I I

I EVENT POINT 0341 INDICATED CONDITION:

o SPENT FUEL POOL "A" LEVEL < -2 FT AS SENSED BY SF-1-LS1 USING 158'6" AS A REFERENCE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LIl OPERATOR ACTIONS FOR A-VALID ALARM:

o VERIFY SPENT FUEL COOLING VALVE LINEUP.

o FILL SPENT FUEL POOL PER OP-406 DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS 9N RECIRC THEN VERIFY BWST LEVEL IS NOT INCREASING.

IF BWST LEVEL IS INCREASING CONSIDERATION SHOULD BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED.

IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 f"5 V

SENSING ELEMENT: SF-1-LS1 AR-402 Rev. 22 Page 78

l ENCLOSURE 1 (Page 77 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 SPENT FUEL POOL LEVEL l

l HIGH/ LOW l

i EVENT POlfJT 0342 INDICATED CONDITION:

o SPENT FUEL POOL "B" LEVEL > +.5 FT AS SENSED BY SF-1-LS2 USING 158'6" AS A REFERENCE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2 OPERATOR ACTIONS FOR A VALID ALARM:

o IF FILLING SPENT FUEL POOLS, SECURE FILLING.

o VERIFY SPENT FUEL COOLING VALVE LINEUP.

o REDUCE SPENT FUEL POOL LEVEL BELOW ALARM SETPOINT DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT DECREASING.

IF BWST LEVEL IS DROPPING CONSIDERATION SHOULD BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BF VERIFIED.

IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 O)

(

SENSING ELEMENT: SF-1-LS2 AR-402 Rev. 22 Page 79

EEL 01URE_.1 T

(Page 78 of 86)

G PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-01 G-08-01 SPENT FUEL POOL LEVEL HIGH/ LOW EVENT POINT 0343 INDICATED CONDITION

o SPENT FUEL POOL "B" LEVEL < -2 FT AS SENSED BY SF-1-LS2 USING 158'6" AS A REFERENCE.

(j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2 OPERATOR ACTIONS FOR A VALID ALARM:

o VERIFY SPENT FUEL COOLING VALVE LINEUP.

o FILL SPENT FUEL POOL PER OP-406 DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF BWST IS ON RECIRC THEN VERIFY BWST LEVEL IS NOT INCREASING.

IF BWST LEVEL IS INCREASING CONSIDERATION SHOULD BE GIVEN TO SECURING BOTH SPENT FUEL PUMPS UNTIL LINEUPS CAN BE VERIFIED.

IF SF TRANSFER TUBES ARE OPEN CHANGES IN R8 PRESSURE WILL EFFECT SPENT FUEL POOL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 V

SENSING ELEMENT: SF-1-LS2 i

AR-402 Rev. 22 Page 80

^

ENCLOSURE 1 (3

s

-(Page 79 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-02 G-08-02 FUEL TRANSFER CANAL LEVEL HIGH/ LOW EVENT POINT 0346 INDICATED CONDITION:

o FUEL TRANSFER CANAL LEVEL > +.5 FT AS SENSED BY SF-10-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON.

Ah itEDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN TRANSFER TUBES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE TRANSFER CANAL FILL OPERATIONS o VERIFY SPENT FUEL / DECAY VALVE LINEUPS DISCUSSION:

"O" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT FUEL TRANSFER CANAL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 p

SENSING ELEMENT: SF-IO-LS AR-402 Rev. 22 Page 81

ENCLOSURE 1 O

i (Page 80 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-02 G-08-02 FUEL TRANSFER CANAL LEVEL HIGH/ LOW EVENT POINT 0347 INDICATED CONDITION:

o FUEL TRANSFER CANAL LEVEL < -1 FT AS SENSED BY SF-10-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON.

10 V

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, _SF-1-LI2, WHEN TRANSFER TUBES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-1080 o FILL FUEL TRANSFER CANAL DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT FUEL TRANSFER CANAL LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04

() ~

SENSING ELEMENT: SF-10-LS AR-402 Rev. 22 Page 82

ILNCLOSURE 1 (Page 81 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-03 G-08-03 CASK AREA LEVEL HIGH/ LOW EVENT POINT 0344 INDICATED CONDITION:

o CASK AREA LEVEL > +.S FT AS SENSED BY SF-11-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN CASK AREA GATES ARE OPEN o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o SECURE SPENT FUEL POOL FILL OPERATIONS o VERIFY SPENT FUEL VALVE LINEUPS DISCUSSION:

"0" INDICATION ON SPENT FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT CASK AREA LEVEL.

REFERENCES:

DRAWING 208-053~ SHEET SF-04 C)

SENSING ELEMENT: SF-11-LS AR-402 Rev. 22 Page 83

r ENCLOSURE 1 p-

~ ~ -

(Page 82 of 86) g PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-03 G-08, _ _

CASK AREA LEVEL HIGH/ LOW EVENT POINT 0345 INDICATED CONDITION:

o CASK AREA LEVEL < -1 FT AS SENSED BY SF-11-LS USING 158'6" AS A REFERENCE, WITH SELECTOR SWITCH SELECTED TO ON.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SPENT FUEL POOL LEVEL INDICATION, SF-1-LI2, WHEN CASK AREA GATES ARE OPEN

.o LOCAL VISUAL INDICATION OPERATOR ACTIONS FOR A VALID ALARM:

o FILL THE CASK AREA o VERIFY SPENT FUEL VALVE LINEUPS DISCUSSION:

"0" INDICATION ON SP..T FUEL LEVEL INDICATORS EQUATES TO 158'6" IF SF TRANSFER TUBES ARE OPEN CHANGES IN RB PRESSURE WILL EFFECT CASK AREA LEVEL.

REFERENCES:

DRAWING 208-053 SHEET SF-04 SENSING ELEMENT: SF-11-LS

-AR-402I Rev. 22 Page 84'

~

u-

V h

ENCLOSURE 1

(,q (Page 83 of 86)

)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-04 G-08-04 SPENT FUEL PUMPS TRIP EVENT POINT 0337 INDICATED CONDITION:

o SFP-1A BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON SFP-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE SFP-1A FOR MALFUNCTIONS DISCUSSION:

-SECURING SFP-1A LOCALLY WILL CAUSE THIS ALARM TO ACTUATE ESA 480V UNDERVOLTAGE LOCK 0UT WILL TRIP THE SPENT FUEL PUMPS, START Oc THESE PUMPS WILL BE BLOCKED UNTIL THIS LOCK 0UT IS RESET,

REFERENCES:

DRAWING 208-053 SHEET SF-01 SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION AR-402 Rev. 22 Page 85

4 c

ENCLOSURE 1

.(

(Page 84 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-04 G-08-04 SPENT FUEL PUMPS TRIP EVENT POINT 0338 INDICATED CONDITION:

o SFP-1B BREAKER'IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON SFP-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE SFP-16 FOR MALFUNCTIONS DISCUSSION:-

SECURING SFP-1B LOCALLY WILL CAUSE THIS ALARM TO ACTUATE ESA 480V UNDERVCLTAGE LOCK 0UT WILL TRIP THE SPENT FUEL PUMPS, START OF THESE PUMPS WILL BE BLOCKED UNTIL THIS LOCK 0UT IS RESET.

g

REFERENCES:

DDAWING 208-053 SHEET SF-02 b

SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION AR-402 Rev. 22 Page 86

ENCLOSURE 1 (Page 85 of 86)

%)'

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-04 G-08-04 SPENT FUEL PUMPS TRIP I

EVENT POINT 0339 INDICATED CONDITION:

o SFP-2 BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CREEN LIGHT ON WITH A RED FLAG ON SFP-2 CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE SFP-2 FOR MALFUNCTIONS DISCUSSION:

SECURING SFP-2 LOCALLY WILL CAUSE THIS ALARM TO ACTUATE

REFERENCES:

DRAWING 208-053 SHEET SF-03

)

w/

SENSING ELEMENT: 42 RELAY AND CONTACTS IN THE CONTROL STATION AR-402 Rev. 22 Page 87 t,

i g

ENCLOSURE 1 (Page 86 of 86)

PSA-G ANNUNCIATOR RESPONSE PSA-Y-08-08 G-08-08 WASTE DISPOSAL PANEL TROUBLE

,3 c

i EVENT POINT 1588 INDICATED CONDITION:

o AN UNACKNOWLEDGED ALARM HAS EXISTED ON THE AUX BUILDING WASTE DISPOSAL PANEL FOR 30 MINUTES REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

t OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY AUXILIARY BUILDING OPERATOR DISCUSSION:

REFERENCES:

SENSING ELEMENT:

AR-402 t Rev. 22 Page 88 (LAST PAGE)