OM 6 4 Rw. 0 j
Millstone Unit 1 OPERATIONS MANUAL SECTION 6.4 "Consumables and Service" 1
l N
Sponsor: D.J. Meekhoff Effec'tive D' ate T. 0LE OF CONTENTS PAGE NUMBER 1.0 PURPOSE 2
2.0 DETERMINING AND RECORDING CONSUMABLE STATUS 2
3.0 ORDERING CONSUMABLES OR SERVICE 4
4.0 CONSUMABLE AND SERVICE INFORMATION 4
Approved by:
c 0 (Y W hb s
3 MP16perations Manager
- J*188!!!!8sA!
4 w
P PDR
Page 2 or4 OM 6.4 i
Rev.0 0
1.0 PURPOSE 1,1 Provide direction to maintain A reliable supply of required consumables 2.0 Determining and Recording Consumable Status 2.1 Daily on the day shift, the Outside Rounds Plant Equipment Operator shall submit a completed CM 6,4, Attachment 1, Daily Operations Consumable Status Sheet to the Shift Manager.
2.2 Daily on the day shift, the Shift Manager or designee shall record consumable status via the Shift Narrative Logging Program.
2.3 The Shift Manager or designee will order consumables when required as described in Section 3.0, ' Ordering Consumables or Service."
2.4, Daily on the night shift, the inside Rounds Plant Equipment Operator shall record House Heating Bol'er running hours and Totalizer readings on OPS Form 696.2, O
2.5 Daily on the night shift, the Shift Manager or designee shall record House Heating Boller running hours and Totalizer readings via the Shift Narrative Logging Program.
o
.,r
. --m$
4
,.~._. _ -
Page 3 or4 oM 6.4 i
Rev.0 3.0 Ordering Consumables or Service 3.1 At ' oefor a consumable reorder limit, place an order for consumable as follows:
3.1.1 -
Refer in Section 4.0 for appropriate vendor information.
3.1.2 Contact vendor and request delivery of consumable 3.1.3 Provide information requested by vendor 3.1.4 State delivery date required 3.1.5 Obtain name of vendor representative contacted 3.1.6 Notify VAP at Extension 4633 of pending delivery 3.1.7 If ordering Diesel Generator or Gas Turbine Fuel Oil, notify Unit 1 Chemistry of expected delivery and delivery rate O
4.0 Consomabio and So,*e info-anon 4.1 flydrogen Reorder limit - Normal Bank - 1000 PSI. Plan to have delivery arrive when normal bank is at approximately 800 psl. Call Liquid Carbonics at (401) 767-3450. The P.O. No is 047235.
4.2 Nitrosen_(for the Liquid N2 Storage Tank)
. Reordor limit 400M cu. ft. Call Bulk Air Products at 800 224-2724 for delivery, the P.O. No. is 006901. Customor Service Account # H6193. For Maintenance and Service' call (617) 481-6970. Call Security at extension 4720 for specific guard request. (Need delivery time) 4.3 Nitrogen Bottles (back-un Nitrogen to Drvwelli Reorder limit 4 full bottles. Contact Operations Department Technician or Control Roem Clerk to create a MIMS request to order nitrogen bottles. The Stock Code for compressed gas is 0351978. Stock Code for NGL 160 bottles is 0206899. The Stock Code for NGL 180 bottles is 0352043. : In case of emergency during off hours call Connecticut AIRGAS directly at 800-750-4427, Refer to P.O.
'1O 1022008403.
e-
-r-e h--
,v e+-py 3--e
,p--s
.ise,w.e m
.g 9-
-q---
g---w-y v--
er-+-
'gwP-y
i l' age 4 or 4 OM 6.4 Rev.0 c
4.4.
Hypochlorite Reorder limit 1000 gallons total. H. Krevit & Co. @ (203) 772 3350, P.O. #
02010982. Contact Department Technician or Control Room Clerk to create a MIMS request to order. The Stock Code # is 0390467. Check with other Units for their delivery: MP2 @ 43!,2, MP3 @ 4589. Note: Hypo Circ Bays Thurs. & Sun.
Use appror.175 gallons.
4.5.
HJi_Bt.iler Fuel Oil (No. 4)
Reorder limit 30,000 gallons tatal or 15,000 gallons per tank, (total capacity 50,000 gallons). Call East River Energy P.O. # 02044955. Phone (203) 453-1200, ask for dispatch. State gallons needed of #4 fuel with a maximum of 0.5%
sulfur. (Approximately 6000 gallons per load) 4.6 Diesel. Generator Fuel Oil 1,
Reorder limit a.
24,103 gals, by gage - In ground - Diesel Storage tank (Capacity o
25,400 gals.)
b.
1/4 tank or less locallevel indication (1/4 tank = 500 gal)- Above ground - Diesel Reserve Storage tank (Capacity 2,000 gals.)
O c.
Total capacity 27,400 gals, of Diesel Fuel Oil 2.
Call trucking company, D. J. King, at 1-4813421 to arrange delivery. P.O number 2020402. Contact Mike Pulg @ 850 2431 if problems.
4.7 Diesel Firo Pumo Reorder limit - 150 gals. (total capacity 275 gals.). Before next order of Diesel Fire Pump or Met Tower propane check with SM or Department Manager. Orders could be turned into FPQA orders. Call Site Services @ Ext. 5247.
4.8 Gas Turbine _EuaLQil NOTE: Prior to ordering reference memo MP1 OPS97-105.
1.
Reorder limit - 44,100 gals. Order sufficient fuel to return total level to at least 46,000 gals. (total capacity 50,000 gals.).
- 2, Call trucking company, D. J. King, at 1-481-3421 to arrange delivery. Contact Mike Puig @ 850-2431 if problems (Jot A 1 Fuel, ASTM D1655). P.O.
information (P.O. # 2020423) 4.9.
Elevator Service For elevator problems contact Site Fire Protection.
~_
l Pcc $ or4 OM 6.4 Rev.0 4.10.
Roller Propane Reorder limit 20%. Call Hendel's @ 443 5337. Have bill sent to John Flannigan Unit One Operations, P.O. Box 128 Waterford, CT. 06385..
4.11 Met Tower _ LP Gaa Reorder limit 40%. Call Hendel's @ 443 5337. Have bill sent to John Flannigan Unit Ons Operations, P.O. Box 128 Waterford, CT. 06385.
5.0 Receiving Consumables 5.1 Receiving Gas Turbine Fuel:
5.1.1 Receive Gas Turbine Fuel Oilin accordcnce with C-OP 600.5 5.2 Receiving Diesel Generator Fuel:
5.2.1 Receive Diesel Generator Fuel Oil in accordance with C-OP 600.5 5.2.2 IF receiving Diesel Generator Fuelinto the Diesel Reserve Storage Tank, hang red tags to prevent transfer of Diesel Fuel to the Diesel Storage Tank until satisfactory off-site analysis is received.
5.3 Forward all receipts for consumables to NRG. Warehouse.
6.0 Forms 1.
Daily Consumables Status a
w
,,--e,ag se.--
e g
p-r-. - -.
nF M
tt i
e Pasc 6 er4 oM 6.4 Rev.0 ATTACHMENT 1 i
DAILY OPERATIONS CONSUMABLES STATUS Time:
Date:
REORDER ITEM IN Service LIMIT INVENTORY A
HYPOCHLORITE B
TOTAL 1000 GAL.
HYDROGEN NORMAL 1000 PSIG RESERVE 1000 PSIG
- 1 H.H. FUEL OIL
- 2 TOTAL 30,000 GAL.
DIESEL GEN.
STORAGE
- 24,100 GAL.
RESERVE 500 GAL, NORTH GAS TURBINE SOUTH TOTAL
'44,100 GAL, PROPANE 20 %
NITROGEN 400 MSCF DIESEL FIRE PUMP FUEL OIL 150 GAL.
DRYWELL B.U. NITROGEN 4 FULL BOTTLES
- This assumes the diesel fuel oil day tank is at a level above the fuel oil forwarding pump auto set point of approximately 1543 gallons. Notes:
SHIFT MANAGER:
--