e Attachment I to JPN-98-054 Revised Technical Specification Page 258f i

l l

l l

l

[

i.

l l:

l l-s I-I New York Power Authority

~ JAMES A. FITZPATRICK NUCLEAR POWER PLANT Docket No. 50-333 DPR-59 9901050373 981230 PDR. ADOCK 05000333' P-PDR j r

6.21. CONFIGURATION RISK MANAGEMENT PROGRAM i

The Configuration Risk Management Program (CRMP) provides a proceduralized risk-informed assessment to manage the risk associated with equipment inoperability.

The program applies to technical specification structures, systems, or components for which a risk-informed allowed outage time has been granted. The program is to include the following:

Provisions for the control and implementation of a Level 1 at-power internal a.

events PRA-informed methodology. The assessment is to be capable of evaluating the applicable plant configuration.

b.

Provisions for performing an assessment prior to entering the plant configuration described by the Limiting Conditions for Operation (LCO) Action Statement for preplanned activities.

Provisions for performing an assessment after entering the plant c.

configuration described by the LCO Action Statement for unplanned entry into the LCO Action Statement.

d.

Provisions for assessing the need for additional actions after the discovery of additional equipment-out-of-service conditions while in the plant configuration described by the LCO Action Statement, e.

Provisions for considering other applicable risk-significant contributors such as Level 2 issues and external events, qualitatively or quantitatively.