ML20198L409

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 981005-1122.Violation Noted:Mod DI-96-007,replacement of Mssrv 3 Way Solenoid Valves,Conducted Feb 1996 Forced Outage Installed Cabling to Mssrv Solenoid Valves Without Use of Conduit
ML20198L409
Person / Time
Site: FitzPatrick 
Issue date: 12/17/1998
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20198L408 List:
References
50-333-98-07, 50-333-98-7, NUDOCS 9901050010
Download: ML20198L409 (2)


Text

.-

l.*

l i

ENCLOSURE 1 NOTICE OF VIOLATION New York Power Authority Docket No. 50-333 James A. FitzPatrick Nuclear Power Plant License No. DPR-59 During an NRC inspection conducted from October 5 to November 22,1998, a violation of NRC requirements was identified, in accordance with NUREG 1600, the " General Statement of Policy and Procedure for NRC Enforcement Actions," the violation is listed below:

10CFR50, Appendix B, Criteria 111, Design Control, requires that the design basis for systems, structures and components be correctly translated into specifications and instructions. The final safety analysis report (FSAR), section 7.1.9, states that all cabling inside the primary containment is routed inside of conduit.

Contrary to the above, modification DI-96-007, " Replacement of MSSRV 3-veay C$noid Valves," conducted during a February 1996, forced outage installed

]

cabling to the MSSRV solenoid valves without the use of conduit.

1 This is a Severity level IV violation (Supplement 1).

i The NRC has concluded that information regarding the reason for the violation, the corrective actions taken and planned to correct the violation and prevent recurrence and the date when full compliance was achieved is already adequately addressed on the docket in Inspection Report 50-333/98-07, dated December 17,1998. However, you are required to submit a written statement or explanation pursuant to 10 CFR 2.201 if the description therein does not accurately reflect your corrective actions or your position, in that case, or if you choose to respond, clearly mark your response as a " Reply to a Notice of Violation,"

and send it to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555 with a copy to the Regional Administrator, Region I, and a copy to the NRC Resident inspector at the facility that is the subject of this notice, within 30 days of the date of the letter transmitting this Not!ae of Violation (Notice).

If you contest this enforcement action, you should also provide a copy of your response to the Director, Office of Enforcement, Unites States Nuclear Regulatory Commission, Washington, DC 20555-0001.

l 9901050010 981217 PDR ADOCK 0$000333 0

PDR

l l

2 Because your response will be placed in the NRC Public Document Room (PDR), to the l

extent possible, it should not include any personal privacy, proprietary, or safeguards j

information so that it can be placed in the PDR without redaction. If personal privacy or l

proprietary information is necessary to provide an acceptable response, then please provide l

a bracketed copy of your response that identified the information that should be protected l

and a redacted copy of your response that deletes such information. If you request withholding of such material, you nLs_t specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of

~

withholding (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2.790(b) to support a request for withholding confidential commercial or financial information). If safeguards information is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

Dated at King of Prussia, Pennsylvania this 17th day of December,1998 1

i i

.